NuAire EcoSmart EST 11 Series Installation And Maintenance Manual
NuAire EcoSmart EST 11 Series Installation And Maintenance Manual

NuAire EcoSmart EST 11 Series Installation And Maintenance Manual

3ph belt drive, run & standby, roof & plantroom twinfans

Advertisement

EST-X
Removable top panel
C
Commissioning
box
A
Figure 1. EST*-X Plantroom/roof mounted in line unit.
Table 1. Dimensions (mm)
Unit
A
EST 11-X to EST 12-X
974
EST 13-X to EST 14-X
1233
EST 15-X to EST 19-X
1430
EST 20-X to EST 26-X
2030
EST-R
A
Removable
top panel
C
Opposed outlet grilles
External
commissioning box.
Figure 2. EST*-R Roof mounted end inlet, side discharge unit.
Table 2. Dimensions (mm)
Unit
EST 11-R to EST 12-R
974
EST 13-R to EST 14-R
1233
EST 15-R to EST 19-R
1430
Introduction
The Nuaire EST Twinfan Belt Drive range consists of the
following units
EST-X (Duct Mounted, Plantroom/Roof) in line unit.
EST-R (Roof Mounted, end inlet) side discharge unit*.
EST-B (Roof Mounted bottom inlet) side discharge unit*.
Units are rectangular in section. The casing is manufactured
from heavy gauge 'Aluzinc' aluminium-zinc coated mild steel.
A full size internally lined access panel is fitted to the top face
and this panel is fully detachable for inspection purposes.
The motor plate and frames are supported on the base by
resilient mountings allowing the fan unit to be operated without
the need for separate anti vibration fan case mountings.
Nuaire: A Trading Division of Polypipe Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA
T: 029 2088 5911 F: 029 2088 7033 E: info@nuaire.co.uk W: www.nuaire.co.uk
3ph Belt Drive, Run & Standby,
Roof & Plantroom Twinfans
Installation and Maintenance
E
50mm
D dia
F
Circular spigots
size EST 11-19)
B
Rectangular spigots
size EST20-26)
For unit weights see page 4
B
C
D dia
E
974
622
400
-
1233
701
500
-
1635
780
630
-
2313
1183
-
1200
B
D dia
Control module
located internally
For unit weights see page 4
A
B
C
D dia
974
622
400
1233
701
500
1635
796
630
The units incorporate two independent motors driving high
efficiency, forward curved centrifugal impellers running in metal
scrolls. Taper locked pulleys and wedge drive belts are
employed. The fans discharge into a common outlet chamber
through a shutter system that prevents 'blowback' through the
standby fan. The motors are manufactured to BS5000 and are
suitable for three phase supply.
Airflow and failure monitors are standard as is Class F insulation.
Suitable for operation in ambient temperatures up to 40
Handling
Always handle the units carefully to avoid damage and distortion.
Eyebolts are provided on all units for lifting purposes.
If mechanical aids are used to lift the unit, spreaders should be
employed and positioned so as to prevent the slings, webbing
etc. making contact with the casing.
F
-
EST-B
-
-
700
C
Opposed outlet grilles
Figure 3. Bottom inlet unit.
Table 3. Dimensions (mm)
Unit
EST 11-B to EST 12-B
EST 13-B to EST 14-B
EST 15-B to EST 19-B
EST-B/R larger units
Commissioning box
C
F
Figure 4. Bottom inlet unit.
Table 4. Dimensions (mm)
Unit
EST 20-B to EST 26-B
EST 20-R to EST 26-R
1
The EMC Directive
2014/30/EU
The Low Voltage
Directive
2014/35/EU
Commissioning box
B
A
Removable
top panel
Bottom inlet
Control module
F
E
located internally
For unit weights see page 4
A
B
C
974
974
622
457
1233
1233
701
762
1430
1635
796
889
* larger units have end discharge
End inlet rectangular spigot Code: EST*-R
B
A
E
Bottom rectangular inlet
F
E
spigot Code: EST*-B
For unit weights see page 4
A
B
C
2030
2313
1183
1200
2030
2313
1183
1200
10. 02. 25. Leaflet Number 671143
o
C.
Rect Spigot
E
F
229
304
381
Louvred
end outlet
Rect Spigot
E
F
700
700

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EcoSmart EST 11 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for NuAire EcoSmart EST 11 Series

  • Page 1 EST 20-R to EST 26-R 2030 2313 1183 1200 Nuaire: A Trading Division of Polypipe Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA T: 029 2088 5911 F: 029 2088 7033 E: info@nuaire.co.uk W: www.nuaire.co.uk 10. 02. 25. Leaflet Number 671143...
  • Page 2: Installation And Maintenance

    Installation and Maintenance ECOSMART Belt Drive Roof & Plantroom Twinfans Installation Testing after installation IMPORTANT Ensure that the Fan unit and any specified controls are fitted The installation must be carried out by competent personnel securely according to the instructions. in accordance with the appropriate authority and conforming Switch on the mains supply.
  • Page 3: Electrical Details

    Electrical Installation typical layout Figure 8. Typical internal layout. Isolation - Before commencing work make sure that the unit, switched live and Nuaire control are electrically isolated from the mains supply. Warning - Inverter Speed Control An Inverter is used to provide speed control. When the fan is isolated, allow 5 minutes for the capacitors in the inverter to discharge before commencing any work on the unit.
  • Page 4 Installation and Maintenance ECOSMART Belt Drive Roof & Plantroom Twinfans Electrical, Sound and Weights Table 7. Run currents etc. Motor Induct inlet Sound Power levels dB re lpW power (+ correction for outlet) Breakout Weight Code Phase RPM (kW) (amps) (amps) dBA@3m (Kg) EST11A...
  • Page 5 Installation and Maintenance ECOSMART Belt Drive Roof & Plantroom Twinfans Connections Note that the volt free contacts are not fused. If these are used to power any external equipment, the installer must provide a) Mains connections adequate fusing or other protections. Mains cables should be suitably sized and terminated at These contacts are rated at 5A resistive, 0.5A inductive.
  • Page 6: Using The Test Button

    Installation and Maintenance ECOSMART Belt Drive Roof & Plantroom Twinfans Figure 14. The Control Module Three Phase No user Connection Remove this link wire if a switched live signal is connected to terminal SL Note: also remove link if a BMS system is connected. Connection Also remove link if an enabling;...
  • Page 7: Maintenance

    Maintenance Figure 17. Adjusting the drive belts (EST 11-19). Isolation - Before commencing work make sure that the unit, switched live and Nuaire control are electrically isolated from the mains supply. Warning - Inverter Speed Control An Inverter is used to provide speed control. When the fan is isolated, allow 5 minutes for the capacitors in the inverter to discharge before commencing any work on the unit.
  • Page 8 The equipment referred to in this Declaration of Incorporation is supplied by live are not prevented by the equipment panels or by fixed installation detail Nuaire to be assembled into a ventilation system which may or may not include (eg ducting), then guarding to the appropriate standard must be fitted.