Advertisement
SAVE THESE INSTRUCTIONS - This manual contains important instructions that shall be followed during installation and maintenance.
Danger of explosion from sparking
Danger of electric shock
The charge controller is able to charge a lower nominal-voltage battery from a higher nominal voltage PV array.
The controller will automatically adjust to a 12 or 24V nominal battery voltage.
Especially in case of a clouded sky, when light intensity is changing continuously, an ultra fast MPPT controller will improve energy harvest by up to 30% compared to PWM charge controllers and by up to 10% compared to slower MPPT controllers.
If partial shading occurs, two or more maximum power points may be present on the power-voltage curve.
Conventional MPPTs tend to lock to a local MPP, which may not be the optimum MPP.
The innovative SmartSolar algorithm will always maximize energy harvest by locking to the optimum MPP.
No cooling fan. Maximum efficiency exceeds 98%. Full output current up to 40°C (104°F).
Over-temperature protection and power derating when temperature is high.
PV short circuit and PV reverse polarity protection. PV reverse current protection.
Compensates absorption and float charge voltages for temperature.
The controller will automatically adjust itself to a 12V or a 24V system one time only.
If a different system voltage is required at a later stage, it must be changed manually, for example with the Bluetooth app.
Fully programmable charge algorithm, and eight preprogrammed algorithms, selectable with a rotary switch.
The Controller is configured for a three step charging process:
Bulk – Absorption – Float.
The MPPT 100/50 can be controlled remotely by a VE.Direct non inverting remote on-off cable (ASS030550300). An input HIGH (Vi > 8V) will switch the controller on, and an input LOW (Vi < 2V, or free floating) will switch the controller off.
Application example: on/off control by a VE.Bus BMS when charging Li-ion batteries.
Several parameters can be customized with the VictronConnect app.
The VictronConnect app can be downloaded from
http://www.victronenergy.nl
Use the manual – VictronConnect - MPPT Solar Charge Controllers – to get the most out of the VictronConnect App when it's connected to a MPPT Solar Charge Controller: http://www.victronenergy.com/live/victronconnect: mppt-solarchargers
DC (PV) INPUT NOT ISOLATED FROM BATTERY CIRCUIT.
FOR PROPER TEMPERATURE COMPENSATION THE AMBIENT CONDITION FOR CHARGER AND BATTERY MUST BE WITHIN 5°C,
We recommend installing the Smart Battery Sense option if larger temperature differences or extreme ambient temperature conditions are expected.
WHEN A GROUND FAULT IS INDICATED, BATTERY TERMINALS AND CONNECTED CIRCUITS MAY BE UNGROUNDED AND HAZARDOUS.
(also see the MPPT Excel sheet on our website)
For example:
12V battery and mono- or polycristalline panels
24V battery and mono- or polycristalline panels
Remark: at low temperature the open circuit voltage of a 144 cell solar array may exceed 100V, depending on local conditions and cell specifications. In that case the number of cells in series must be reduced.
(see figure 1)
First: connect the battery.
Second: connect the solar array (when connected with reverse polarity, the controller will heat up but will not charge the battery).
Fully programmable charge algorithm (see the software page on our website) and eight preprogrammed charge algorithms, selectable with a rotary switch:
Pos | Suggested battery type | Absorption V | Float V | Equalize V @%Inom | dV/dT mV/°C |
0 | Gel Victron long life (OPzV) Gel exide A600 (OPzV) Gel MK | 28,2 | 27,6 | 31,8 @8% | -32 |
1 | Gel Victron deep discharge Gel Exide A200 AGM Victron deep discharge Stationary tubular plate (OPzS) | 28,6 | 27,6 | 32,2 @8% | -32 |
2 | Default setting Gel Victron deep discharge Gel Exide A200 AGM Victron deep discharge Stationary tubular plate (OPzS) | 28,8 | 27,6 | 32,4 @8% | -32 |
3 | AGM spiral cell Stationary tubular plate (OPzS) Rolls AGM | 29,4 | 27,6 | 33,0 @8% | -32 |
4 | PzS tubular plate traction batteries or OPzS batteries | 29,8 | 27,6 | 33,4 @25% | -32 |
5 | PzS tubular plate traction batteries or OPzS batteries | 30,2 | 27,6 | 33,8 @25% | -32 |
6 | PzS tubular plate traction batteries or OPzS batteries | 30,6 | 27,6 | 34,2 @25% | -32 |
7 | Lithium Iron Phosphate (LiFePo4) batteries | 28,4 | 27,0 | n.a. | 0 |
Note 1: divide all values by two in case of a 12V system.
Note 2: equalize normally off, see "Automatic equalization" to activate
(do not equalize VRLA Gel and AGM batteries)
Note 3: any setting change performed with Bluetooth or via VE.Direct will override the rotary switch setting. Turning the rotary switch will override prior settings made with Bluetooth or VE.Direct.
On all models with software version V 1.12 or higher a binary LED code helps determining the position of the rotary switch. After changing the position of the rotary switch, the LEDs will blink during 4 seconds as follows:
Switch position | LED Bulk | LED Abs | LED Float | Blink frequency |
0 | 1 | 1 | 1 | Fast |
1 | 0 | 0 | 1 | Slow |
2 | 0 | 1 | 0 | Slow |
3 | 0 | 1 | 1 | Slow |
4 | 1 | 0 | 0 | Slow |
5 | 1 | 0 | 1 | Slow |
6 | 1 | 1 | 0 | Slow |
7 | 1 | 1 | 1 | Slow |
Thereafter, normal indication resumes, as described below.
Remark: the blink function is enabled only when PV power is present on the input of the controller.
LED indication:
permanent on
blinking
off
Regular operation | |||
LEDs | Bulk | Absorption | Float |
Bulk (*1) | ![]() | ![]() | ![]() |
Absorption | ![]() | ![]() | ![]() |
Automatic equalisation (*2) | ![]() | ![]() | ![]() |
Float | ![]() | ![]() | ![]() |
Note (*1): The bulk LED will blink briefly every 3 seconds when the system is powered but there is insufficient power to start charging.
Fault situations | |||
LEDs | Bulk | Absorption | Float |
Charger temperature too high | ![]() | ![]() | ![]() |
Charger over-current | ![]() | ![]() | ![]() |
Charger or PV over-voltage | ![]() | ![]() | ![]() |
Internal error (*3) | ![]() | ![]() | ![]() |
Note (*2): E.g. calibration and/or settings data lost, current sensor issue.
The charge controller starts a new charge cycle every morning, when the sun starts shining.
Default setting:
The maximum duration of the absorption period is determined by the battery voltage measured just before the solar charger starts up in the morning:
Battery voltage Vb (@startup) | Maximum absorption time |
Vb < 23,8V | 6h |
23,8V < Vb < 24,4V | 4h |
24,4V < Vb < 25,2V | 2h |
Vb > 25,2V | 1h |
(divide voltages by 2 for a 12V system)
If the absorption period is interrupted due to a cloud or due to a power hungry load, the absorption process will resume when absorption voltage is reached again later on the day, until the absorption period has been completed.
The absorption period also ends when the output current of the solar charger drops to less than 2Amps, not because of low solar array output but because the battery is fully charged (tail current cut off).
This algorithm prevents over charge of the battery due to daily absorption charging when the system operates without load or with a small load.
User defined algorithm:
Any setting change performed with Bluetooth or via VE.Direct will override the rotary switch setting. Turning the rotary switch will override prior settings made with Bluetooth or VE.Direct.
Automatic equalization is default set to 'OFF'. With the Victron Connect app (see section "Remote on-off") this setting can be configured with a number between 1 (every day) and 250 (once every 250 days). When automatic equalization is active, the absorption charge will be followed by a voltage limited constant current period. The current is limited to 8% of the bulk current for the factory default battery type, and to 25% of the bulk current for a user defined battery type. The bulk current is the rated charger current unless a lower maximum current setting has been chosen.
In case of all VRLA batteries and some flooded batteries (algorithm number 0, 1, 2 or 3) automatic equalization ends when the voltage limit maxV has been reached, or after t = (absorption time)/8, whichever comes first.
For all tubular plate batteries and the user defined battery type automatic equalization ends after t = (absorption time)/2.
When automatic equalisation is not completely finished within one day, it will not resume the next day, and the next equalisation session will take place as determined by the day interval.
Problem | Possible cause | Solution |
The unit does not function | Reversed PV connection | Connect PV correctly |
Reverse battery connection | Non replacable fuse blown. Return to VE for repair | |
The battery is not fully charged | A bad battery connection | Check battery connection |
Cable losses too high | Use cables with larger cross section | |
Large ambient temperature difference between charger and battery (Tambient_chrg > Tambient_batt) | Make sure that ambient conditions are equal for charger and battery | |
Only for a 24V system: wrong system voltage chosen (12V instead of 24V) by the charge controller | Set the controller manually to 24V (see section "Configuring and monitoring") | |
The battery is being overcharged | A battery cell is defect | Replace battery |
Large ambient temperature difference between charger and battery (Tambient_chrg < Tambient_batt) | Make sure that ambient conditions are equal for charger and battery |
SmartSolar Charge Controller | MPPT 100/30 | MPPT 100/50 |
Battery voltage | 12/24V Auto Select | |
Rated charge current | 30A | 50A |
Nominal PV power, 12V 1a, b) | 440W | 700W |
Nominal PV power, 24V 1a, b) | 880W | 1400W |
Maximum PV open circuit voltage | 100V | 100V |
Max. PV short circuit current 2) | 35A | 60A |
Maximum efficiency | 98% | 98% |
Self-consumption | 10 mA | |
Charge voltage 'absorption' | Default setting: 14,4V / 28,8V / 57,6V (adjustable) | |
Charge voltage 'equalization' 3) | Default setting: 16,2V / 28,8V / 64,8V (adjustable) | |
Charge voltage 'float' | Default setting: 13,8V / 27,6V / 55,2V (adjustable) | |
Charge algorithm | multi-stage adaptive (eight preprogrammed algorithms) or user defined algrithm | |
Temperature compensation | -16 mV / °C resp. -32 mV / °C | |
Protection | Battery reverse polarity (fuse, not user accessible) Output short circuit, Over temperature | |
Operating temperature | -30 to +60°C (full rated output up to 40°C) | |
Humidity | 95%, non-condensing | |
Maximum altitude | 5000m (full rated output up to 2000m) | |
Environmental condition | Indoor type 1, unconditioned | |
Pollution degree | PD3 | |
Data communication port | Bluetooth and VE.Direct See the data communication white paper on our website | |
ENCLOSURE | ||
Colour | Blue (RAL 5012) | |
Power terminals | 16 mm² / AWG6 | |
Protection category | IP43 (electronic components), IP22 (connection area) | |
Weight | 1,3 kg | |
Dimensions (h x w x d) | 130 x 186 x 70 mm | |
STANDARDS | ||
Safety | EN/IEC 62109-1, UL 1741, CSA C22.2 | |
1a) If more PV power is connected, the controller will limit input power. 1b) The PV voltage must exceed Vbat + 5V for the controller to start. Thereafter the minimum PV voltage is Vbat + 1V. 2) A higher sort circuit current may damage the controller in case of reverse polarity connection of the PV array. 3) Default setting: OFF |
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Victron energy SmartSolar MPPT 100/30, SmartSolar MPPT 100/50 Manual
Advertisement
Need help?
Do you have a question about the SmartSolar MPPT 100/30 and is the answer not in the manual?
Questions and answers