Page 2
The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document.
About This Manual 1. About This Manual This manual contains information on the software and hardware features of the Beijer Electronics GL-9031 Network Adapter Module. It provides in-depth specifications, guidance on installation, setup, and usage of the product. 1.1. Symbols Used in This Manual This publication includes Warning, Caution, Note and Important icons where appropriate, to point out safety-related, or other important information.
Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions! In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product. The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.
IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc. • Expansion Module - Expansion module types: Digital IO, Analog IO, and Special modules. • Messaging - The system uses two types of messaging: Service messaging and IO messaging. Beijer Electronics, Doc ID: 172909 2025-02...
Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data. 2025-02 Beijer Electronics, Doc ID: 172909...
IO cable max. 2.0 mm (AWG 14) Weight 71 g Dimensions 22 mm x 109 mm x 70 mm 4.3. Communication Interface Specification Adapter type Slave node (CC-Link Version 1) Max. expansion slot 12 slots Beijer Electronics, Doc ID: 172909 2025-02...
Page 10
Module status (MOD) - Green/Red Current running status (NET) - Green Error status (ERR) - Green Expansion module status (IOS) - Green/Red Module location Starter module left side of G-series system Station class Remote device station 2025-02 Beijer Electronics, Doc ID: 172909...
5. Wiring Diagram Pin no. Signal description System power, 24 V System power, ground Frame ground Field power, ground Field power, 24 V WARNING Never connect system power to field power! Use separate power supplies. Beijer Electronics, Doc ID: 172909 2025-02...
Exceeded number range of device station. 6.4. IOS (Expansion Module Status) Status Indicates Not powered, no Device has no expansion module or is not powered. expansion module No expansion module Flashing Adapter has no expansion module. 2025-02 Beijer Electronics, Doc ID: 172909...
Page 13
• Detect invalid expansion module ID. • Overflowed input/output size. • Too many expansion modules. • Initialization failure. • Communication error. • Changed expansion module configuration. • Mismatch vendor code between adapter and expansion module. Beijer Electronics, Doc ID: 172909 2025-02...
5-Pin Open Connector 7. 5-Pin Open Connector Connector no. Signal name Description DATA+ Transceiver data high DATA- Transceiver data low Signal common Shield Shield Frame Ground. Internally shorted with shield. 2025-02 Beijer Electronics, Doc ID: 172909...
Default baud rate: 156 Kbps Node address pole setting examples ID = 0 ID = 1 ID = 10 ID = 42 ID = 64 8.2. 4 Pole Switch Pole# Description Fixed station OFF: Auto addressable. ON: 4station occupied. Beijer Electronics, Doc ID: 172909 2025-02...
Mode switch is ON, the IO size will be increased 2 bytes more respectively. STOP action OFF: Master value dependent. ON: Output clear. Reserved 8.3. 2 Pole Switch Pole# Description Terminator resistor 1 ON, 2 ON: Terminator resistor set. Other: Terminator resistor not set. 2025-02 Beijer Electronics, Doc ID: 172909...
Installation position is valid vertical and horizontal. The drawings are illustrative and may be out of proportion. CAUTION NOT following the space requirements may result in damaging the product. Beijer Electronics, Doc ID: 172909 2025-02...
• GT-5XXX • GT-7XXX GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module. Mount to DIN rail Dismount from DIN rail 2025-02 Beijer Electronics, Doc ID: 172909...
Page 19
9.2.2. Mount GN-9XXX Module To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example GN-9251 or GN-9371, see the following instructions: Mount to DIN rail Dismount from DIN rail Beijer Electronics, Doc ID: 172909 2025-02...
Token output port of processor module Serial output Transmitter output port of processor module Serial input Receiver input port of processor module Reserved Reserved for bypass token Field GND Field ground Field VCC Field supply voltage (24 VDC) 2025-02 Beijer Electronics, Doc ID: 172909...
Error status flag Reserved Remote station ready Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 10.5. Reaction on Network Error Description Hold last value Clear output to zero Stop bus Not used (internally switched to 10) 2025-02 Beijer Electronics, Doc ID: 172909...
User data 17 User data 16 RWw[12] User data 19 User data 18 RWw[13] User data 21 User data 20 RWw[14] User data 23 User data 22 RWw[15] User data 25 User data 24 Beijer Electronics, Doc ID: 172909 2025-02...
User data 17 User data 16 RWw[12] User data 19 User data 18 RWw[13] User data 21 User data 20 RWw[14] User data 23 User data 22 RWw[15] User data 25 User data 24 2025-02 Beijer Electronics, Doc ID: 172909...