Rack Geometry; Cooling Footprint; Hot And Cold Aisle Spacing; Row Configuration - Compaq BL10e - HP ProLiant - 512 MB RAM Introduction Manual

Optimizing facility operation in high density data center environments
Hide thumbs Also See for BL10e - HP ProLiant - 512 MB RAM:
Table of Contents

Advertisement

from 25 percent (the most common) to 56 percent (for high airflow). A 25 percent perforated tile
provides approximately 500 cubic feet per minute (cfm) at a 5 percent static pressure drop, while a
56 percent perforated tile provides approximately 2000 cfm.

Rack geometry

Designing the data center layout to form hot and cold aisles is one step in the cooling optimization
process. Also critical is the geometry of the rack layout. Research by HP Laboratories has revealed
that minor changes in rack placement can change the fluid mechanics inside a data center and lead
to inefficient utilization of CRAC units. See the
information.

Cooling footprint

The floor area that each rack requires must include an unobstructed area to draw in and discharge
air. Almost all HP equipment cools from front to rear so that it can be placed in racks positioned side-
by-side. The cooling footprint (Figure 13) includes width and depth of the rack plus the area in front
for drawing in cool air and the area in back for exhausting hot air.
Equipment that draws in air from the bottom or side or that exhausts air from the side or top will have
a different cooling footprint. The total physical space required for the data center includes the cooling
footprint of all the racks plus free space for aisles, ramps, and air distribution. Typically, a width of
two floor tiles is needed in front of the rack, and a width of at least one unobstructed floor tile is
needed behind the rack to facilitate cable routing.
Figure 13. Cooling footprint

Hot and cold aisle spacing

The amount of space between rows of racks is determined as follows.
• Cold aisle spacing should be 48 inches, two full tiles, and hot isle spacing should be at least one
full tile, 24 inches minimum. This spacing is required for equipment installation and removal and for
access beneath the floor.
• Cold aisles should be a minimum of 14 feet apart, center-to-center, or seven full tiles.

Row configuration

Keep equipment rows as long as safety requirements will allow and avoid row gaps to prevent mixing
of the hot and cold air.
Where possible, locate high-density racks in the middle of equipment rows or mid-way between
opposing air-conditioners. Avoid locating high-density racks at the ends of rows or deep into room
corners.
"Thermal Assessment
Services" section for more
18

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BL10e - HP ProLiant - 512 MB RAM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents