Endress+Hauser iTHERM SurfaceLine TM611 Operating Instructions Manual
Endress+Hauser iTHERM SurfaceLine TM611 Operating Instructions Manual

Endress+Hauser iTHERM SurfaceLine TM611 Operating Instructions Manual

Surface thermometer, non-invasive rtd/tc thermometer with high measurement performance for demanding applications

Advertisement

Quick Links

BA02366T/09/EN/01.24-00
71679397
2024-12-02
Products
Operating Instructions
iTHERM SurfaceLine TM611
Surface thermometer
Non-invasive RTD/TC thermometer with high
measurement performance for demanding applications
Solutions
Services

Advertisement

loading
Need help?

Need help?

Do you have a question about the iTHERM SurfaceLine TM611 and is the answer not in the manual?

Questions and answers

Summary of Contents for Endress+Hauser iTHERM SurfaceLine TM611

  • Page 1 Products Solutions Services BA02366T/09/EN/01.24-00 71679397 2024-12-02 Operating Instructions iTHERM SurfaceLine TM611 Surface thermometer Non-invasive RTD/TC thermometer with high measurement performance for demanding applications...
  • Page 2 SurfaceLine TM611 Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3: Table Of Contents

    10.1 Cleaning ......24 10.2 Endress+Hauser services ....25...
  • Page 4: About This Document

    About this document iTHERM SurfaceLine TM611 About this document Document function These Operating Instructions contain all the information required in the various life cycle phases of the device: from product identification, incoming acceptance and storage, to installation, connection, operation and commissioning, through to troubleshooting, maintenance and disposal.
  • Page 5: Documentation

    • Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the nameplate • Endress+Hauser Operations app: Enter serial number from nameplate or scan matrix code on nameplate. The following documentation may be available depending on the device version ordered: Document type...
  • Page 6: Registered Trademarks

    Link Community at: www.io.link.com. Bluetooth® The Bluetooth® wordmark and logos are registered trademarks of Bluetooth SIG, Inc. and any use of these trademarks by Endress+Hauser is licensed. Other trademarks and trade names are those of their respective owners. FOUNDATION™ Fieldbus Registration-pending trademark of the FieldComm Group, Austin, Texas, USA ethernet-apl™...
  • Page 7: Safety Instructions

    SurfaceLine TM611 Safety instructions Safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task. ‣...
  • Page 8: Product Safety

    Safety instructions iTHERM SurfaceLine TM611 Hazardous area To avoid danger to individuals or the facility when the device is used in the approval- related area (e.g. explosion protection or safety instrumented systems): ‣ Based on the technical data on the nameplate, check whether the ordered device is permitted for the intended use in the hazardous area.
  • Page 9: Product Description

    SurfaceLine TM611 Product description Product description Design A0055896 Options 1: Terminal head →  44 Terminal heads made of aluminum, polyamide or stainless steel 2: Wiring, electrical connection, • Ceramic terminal block output signal →  29 • Flying leads •...
  • Page 10: Incoming Acceptance And Product

    (www.endress.com/deviceviewer): all the information about the measuring device is displayed. • Enter the serial number on the device label into the Endress+Hauser Operations App or scan the 2-D matrix code (QR code) on the measuring device with the Endress+Hauser Operations App: all the information about the measuring device is displayed.
  • Page 11: Storage And Transport

    SurfaceLine TM611 Incoming acceptance and product identification Storage and transport Storage temperature: –40 to +85 °C (–40 to +185 °F). Avoid the following environmental influences during storage: • Direct sunlight • Proximity to hot objects • Mechanical vibration • Aggressive media Maximum relative humidity: <...
  • Page 12: Mounting

    Mounting iTHERM SurfaceLine TM611 Mounting Mounting requirements Depending on the nominal width, the device is attached either at an angle or perpendicularly to the process: • At an angle for pipe outer diameters øD < DN100, see "Installation examples" graphic.
  • Page 13: Mounting The Measuring Instrument

    SurfaceLine TM611 Mounting The extension neck length influences the heating of the head transmitter: The greater the distance between the outer pipe wall and terminal head, the lower the heating. The following installation option achieves the highest measurement accuracy: •...
  • Page 14 Mounting iTHERM SurfaceLine TM611 A0056412 3. On the opposite side of the pipe, insert the open ends of each of the hose clips into the screw head. 4. Tighten and secure each of the hose clips to the screw head with a maximum torque of 5 Nm.
  • Page 15: Insulation Of The Measuring Point

    SurfaceLine TM611 Mounting A0056399 2. Push the union nut upwards to the extension neck of the thermometer. 3. Turn the terminal head so that no moisture can accumulate in the cable entry. 4. Tighten the union nut on the extension neck of the thermometer with a max. torque of 20 Nm.
  • Page 16: Post-Mounting Check

    Electrical connection iTHERM SurfaceLine TM611 A0055913 Coupling element Heat insulation Extension neck length Insulation thickness The maximum permissible thickness of the insulation depends on extension neck length E and can be calculated using the following formula: Connection angle Formula 90 °...
  • Page 17: Terminal Assignment

    SurfaceLine TM611 Electrical connection The RTD or TC cable thermometers can be wired, e.g. to a separate DIN rail transmitter in the cabinet, without any tools. CAUTION Risk associated with the uncontrolled activation of processes! Risk of short-circuit and injury! ‣...
  • Page 18 Electrical connection iTHERM SurfaceLine TM611 A0052495  4 Head-mounted iTEMP TMT36 transmitter (single sensor input) RTD sensor input: 4-, 3- and 2-wire Display connection 18 to 30 V power supply power supply C/Q IO-Link or switch output A0045466  5...
  • Page 19 SurfaceLine TM611 Electrical connection A0045474  7 Head-mounted iTEMP TMT8x transmitter (dual sensor input) Sensor input 1 Sensor input 2 Fieldbus connection and power supply Display connection A0045353  8 Head-mounted iTEMP TMT7x transmitter (single sensor input) Sensor input...
  • Page 20 Electrical connection iTHERM SurfaceLine TM611 A0056032  9 Wiring diagram for RTD cable thermometer 1x Pt100, 4-wire 2x Pt100, 3-wire For the highest accuracy, a 4-wire connection is recommended or use of a transmitter. 6.2.4 Sensor connection type: Cable thermometer (TC) Wiring diagram The cable thermometer is wired to the flying leads of the connection cable.
  • Page 21: Connecting The Measuring Instrument

    SurfaceLine TM611 Electrical connection Connecting the measuring instrument Proceed as follows to wire a mounted iTEMP head transmitter: 1. Open the cable gland and the housing cover at the terminal head or the field housing. 2. Feed the cables through the opening in the cable gland.
  • Page 22: Special Connection Instructions

    Electrical connection iTHERM SurfaceLine TM611 5. Pull the wire gently to ensure it is connected correctly. Repeat from step 1 if necessary. Item C, releasing the connection: 1. Press down on the lever opener. 2. Remove the wire from the terminal.
  • Page 23 SurfaceLine TM611 Electrical connection Electrical connection Notes Does the supply voltage match the specifications on the nameplate? Do the cables have adequate strain relief? Are the power supply and signal cables connected correctly? Are all the screw terminals firmly tightened and have...
  • Page 24: Operation Options

    Operation options iTHERM SurfaceLine TM611 Operation options See the technical documentation for the specific transmitter. Commissioning Function check Perform the following final checks before commissioning the measuring point: 1. Perform the post-mounting check using the checklist. →  12 2. Perform the post-connection check using the checklist. →  16 Switching on the measuring instrument Once you have completed the post-connection checks, switch on the supply voltage.
  • Page 25: Endress+Hauser Services

    Endress+Hauser services Service Description Calibration RTD inserts may drift depending on the application. Regular recalibration to verify accuracy is recommended. The calibration can be performed by Endress+Hauser or by qualified technical staff using calibration devices on site. Repair 11.1 General notes For the purpose of repair, individual components can be replaced by the customer' s technical personnel.
  • Page 26: Disposal

    Repair iTHERM SurfaceLine TM611 11.4 Disposal If required by the Directive 2012/19/EU on waste electrical and electronic equipment (WEEE), the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste. Do not dispose of products bearing this marking as unsorted municipal waste.
  • Page 27: Accessories

    Modems/Edge devices Netilion IIoT ecosystem: Unlock knowledge With the Netilion IIoT ecosystem, Endress+Hauser enables you to optimize plant performance, digitize workflows, share knowledge, and enhance collaboration. Drawing on decades of experience in process automation, Endress+Hauser provides the process industry with an IIoT ecosystem that unlocks valuable insights from data. These insights allow process optimization, leading to increased plant availability, efficiency, and reliability - ultimately resulting in a more profitable plant.
  • Page 28 Accessories iTHERM SurfaceLine TM611 Easily readable process indicators with various functions: loop-powered indicators for displaying 4 to 20 mAvalues, display of up to four HART variables, process indicators with control units, limit value monitoring, sensor power supply, and galvanic isolation.
  • Page 29: Technical Data

    SurfaceLine TM611 Technical data Technical data 13.1 Input Measured variable Temperature (temperature-linear transmission behavior) Measuring range Depends on the type of sensor used Sensor type Measuring range Pt100 (WW) –200 to +600 °C (–328 to +1 112 °F) Pt100 (TF) –50 to +200 °C (–58 to +392 °F)
  • Page 30 Technical data iTHERM SurfaceLine TM611 Connectors The manufacturer offers a wide variety of connectors for the simple and fast integration of the thermometer into a process control system. The following tables show the PIN assignments of the various plug connector combinations.
  • Page 31 SurfaceLine TM611 Technical data ® 1x FOUNDATION™ Fieldbus 1x PROFINET and Ethernet- Plug 1x PROFIBUS ® ™ (FF) signal 2x TMT PROFINET® signal - (#1) (#1) 1 BN 1 BN 1 BU 1 RD 2 GNYE 2 GNYE 2 BN...
  • Page 32 Technical data iTHERM SurfaceLine TM611 Plug 1x IO-Link®, 4-pin 4-wire terminal block (1x Pt100) Cannot be combined 6-wire terminal block (2x Pt100) 1x TMT 4 to 20 mA or HART ® Cannot be combined ® 2x TMT 4 to 20 mA or HART...
  • Page 33 SurfaceLine TM611 Technical data ® 2x FOUNDATION™ 2x PROFINET Plug 2x PROFIBUS ® ™ Fieldbus (FF) Ethernet-APL (#1)/ 2x TMT FF (#1)/ -(#2) (#2) 1x TMT PROFINET® Cannot be combined Cannot be combined Cannot be combined signal signa signa signal 2x TMT PROFINET®...
  • Page 34 Technical data iTHERM SurfaceLine TM611 Plug 4-pin / 8-pin 2x TMT PROFINET® Cannot be combined 2 BN 3 GN 1 BN 1 WH 2 GNYE 4 YE PIN position and color code 3 BU 8 RD 4 GY 7 BU...
  • Page 35: Performance Characteristics

    SurfaceLine TM611 Technical data Transmitter connection Insert iTEMP TMT31/iTEMP TMT7x iTEMP TMT8x 1x 1-channel 2x 1-channel 1x 2-channel 2x 2-channel 1x sensor (Pt100 or TC),with Sensor (#1) : transmitter Sensor (#1) : transmitter terminal block in cover in cover...
  • Page 36 Technical data iTHERM SurfaceLine TM611 Maximum measurement RTD resistance thermometer as per IEC 60751: error Class Max. tolerances (°C) Characteristics RTD maximum sensor error Cl. A ± (0.15 + 0.002 · |t| Max. deviation (°C) Cl. AA, ± (0.1 + 0.0017 · |t|) formerly 1/3 Cl.
  • Page 37 In addition to the measurement current, the size of the measurement error is also affected by the temperature conductivity and flow velocity of the process. This self-heating error is negligible when an Endress+Hauser iTEMP temperature transmitter (very small measurement current) is connected.
  • Page 38 For the device, Endress+Hauser offers standard calibrations at a reference temperature of –80 to +600 °C (–112 to +1 112 °F) based on the ITS90 (International Temperature Scale).
  • Page 39: Environment

    SurfaceLine TM611 Technical data Insulation resistance • RTD: Insulation resistance according to IEC 60751 > 100 MΩ at 25 °C between terminals and sheath material measured with a minimum test voltage of 100 V DC • TC: Insulation resistance according to IEC 1515 between terminals and sheath material with a test voltage of 500 V DC: •...
  • Page 40: Process

    Technical data iTHERM SurfaceLine TM611 Shock and vibration The Endress+Hauser inserts exceed the requirements of IEC 60751 with regard to shock resistance and vibration resistance of 3g in a range of 10 to 500 Hz. The vibration resistance of the...
  • Page 41 Technical data 9 (0.35) A0055923  13 Dimensions of iTHERM SurfaceLine TM611, vertical connection angle A = 90 ° Industrial thermometer with terminal head RTD or TC cable thermometer Thermometer connection thread - Coupling element G½" (AF 27) Coupling foil ⌀ID Insert diameter: ⌀3 mm (0.12 in)
  • Page 42 Technical data iTHERM SurfaceLine TM611 A0055929  14 Dimensions of iTHERM SurfaceLine TM611, inclined connection angle A < 90° Industrial thermometer with terminal head RTD or TC cable thermometer Thermometer connection thread - Coupling element G½" (AF 27) Coupling foil ⌀ID Insert diameter: ⌀3 mm (0.12 in)
  • Page 43 SurfaceLine TM611 Technical data Connecting cable; Diameter ⌀K in mm (in) sheath insulation PTFE; PTFE; 4-wire RTD 4.5 mm (0.178 in) PTFE; silicone; 2x3-wire 5.2 mm (0.2 in) Glass fiber; 1x or 2x TC 3.6 mm (0.14 in) for 1x TC connection 4.1 mm (0.16 in) for 2x TC connection...
  • Page 44 Technical data iTHERM SurfaceLine TM611 Material Short form Recommended max. Properties name temperature for continuous use in air AISI 316L/ X2CrNiMo17-12-2 650 °C (1 202 °F) • Austenitic, stainless steel 1.4404 • High corrosion resistance in general • Particularly high corrosion resistance in...
  • Page 45 "Ambient temperature range" section. →  39 As a special feature, Endress+Hauser offers terminal heads with optimized terminal accessibility for easy installation and maintenance. If the device is selected as a cable thermometer, no terminal head can be configured.
  • Page 46 Technical data iTHERM SurfaceLine TM611 TA30EB Specification • Screw cap 89.2 (3.51) • Degree of protection: IP 66/68, NEMA 4x • Temperature: –50 to +150 °C (–58 to +302 °F) • Material: aluminum; polyester powder coating; Klüber Syntheso Glep 1 dry-film lubricant •...
  • Page 47 SurfaceLine TM611 Technical data TA30H with display window in cover Specification • Flameproof (XP) version, explosion-protected, captive screw 125 (4.92) cap, available with one or two cable entries • Degree of protection: IP 66/68, NEMA Type 4x Encl. Ex-version: IP 66/67 •...
  • Page 48 Technical data iTHERM SurfaceLine TM611 TA30R (optionally with display window in Specification cover) • Degree of protection - standard version: IP69K (NEMA Type 96 (3.8) 4x encl.) 64 (2.52) Degree of protection - version with display window: IP66/68 (NEMA Type 4x encl.) •...
  • Page 49: Certificates And Approvals

    SurfaceLine TM611 Technical data Suitable for Degree of Type Temperature range Suitable cable diameter cable entry protection ½" NPT, M20x1.5 –20 to +95 °C IP69K (optionally 2x (–4 to +203 °F) cable entry) Cable gland for dust ignition-proof area, ½"...
  • Page 52 *71679397* 71679397 www.addresses.endress.com...