The setting communication unit is used to set various parameters in and perform running operations of the JW Series. The setting communication unit is available as a type to be built in the JW series thyristor regulator or a type to be installed on a panel separately according to a model code specified on ordering. The setting communication unit can also be used to connect the JW Series thyristor regulator to a master unit (a personal computer, etc.) via a communication interface.
□ 1 NOMENCLATURE AND FEATURES Lights in MODE 0 Displays parameter items, Lights in the measured measured value or error value display mode Displays a set value Lights in the manual setting mode Mode lamp Lights in MODE 2 to 4 Mode key Lights in MODE 1 Down key...
Page 6
Front controls Setting terminals Main circuit terminals Setting communication unit Protective conductor terminal Front controls Setting communication unit...
□ 3 OPERATION 3.1 Basics of Display Switching 3.1.1 Switching between the mode and parameter displays MODE Returns to the measured value display mode Measured Setting mode Value Display (MODE0~ Moves to the MODE Mode MODE4) setting mode Switches between MODE 0 and MODE 4 Selects a parameter Returns to the setting mode MODE...
3.2.2 Measured value in zero-cross control In the zero-cross control, the correct RM values cannot be displayed due to the characteristics of this control system. In consequence, this unit employs the average values as the measured values only in the case of zero-cross control.
Page 10
3.2.5 Measured value display mode After the reference screen, MODE To MODE 0 Current (Ave.) DISP2 : Current value (Ave.) Average current value of 3 phases [Current value (U) + Current value (V) + Current value (W)] ÷ 3 Current (U) DISP2 : Current value (U) Measured value of current of the U-phase...
Page 11
To the measured value display When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Reference screen Reference screen Reference screen selection • Select a measured value screen (reference screen) Selection of a reference screen DISP1 displayed at the power ON or at ...
Page 13
Return to MODE 0 When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Control system setting Control system Phase/Zero-cross switching : Phase control. Switching of Phase or Zero-cross DISP1 : Zero-cross control. DISP2 DISP2 •...
Page 14
Return to MODE 0 When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Alarm output Alarm output Alarm output switching : Alarm output signal Switching of the alarm ON or OFF DISP1 is enabled.
Page 15
3.4 MODE 1 MODE 1 MODE Setting DISP1 DISP2 DISP1 MODE 2 Return to a reference screen DISP2 Alarm DISP1 MODE 0 DISP2 When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Priority Priority...
Page 16
Return to MODE 1 When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Elevation Elevation Elevation setting • For the Elevation, see the chapter Setting in the range from 0% DISP1 “4.GLOSSARY.” to 100% When there is a change, the dot at the lowest digit of DISP2 blinks.
Page 17
3.5 MODE 2 MODE 2 MODE Alarm DISP1 DISP1 DISP2 MODE 3 DISP2 Communication Return to a reference screen DISP1 MODE 1 DISP2 Setting When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Priority Priority...
Page 18
Return to MODE When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Heater Heater disconnection ratio Ratio setting disconnection ratio • Set the heater disconnection ratio, which is the set value for the heater DISP1 Setting in the range from ...
Page 19
Return to MODE 2 Initial resistance WU MODE Initial resistance W U • The Initial resistance “between W & U” is used for the judgment of heater DISP1 disconnection alarm. Conversion using a formula is required to obtain the value in Ω.
Page 20
Return to MODE 2 When there is a change, the dot at the lowest digit of DISP2 goes off. Imbalance alarm MODE : Imbalance alarm OFF Imbalance alarm Imbalance alarm switching : Imbalance alarm ON DISP1 Switch between “ON“ & “OFF” ...
Page 21
3.6 MODE 3 MODE 3 MODE When the password is other than 1000: Communication DISP1 MODE 0 DISP1 DISP2 DISP2 PASS=1000 DISP1 MODE 4 Return to a reference screen DISP2 Engineering DISP1 ...
Page 22
Return to MODE 3 When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Transmission rate Transmission rate Transmit rate switching : 9600 bit/sec DISP1 Switching between “9600” :19200 bit/sec & “19200” DISP2 DISP2 ...
3.7 MODE 4 MODE 4 MODE Engineering DISP1 DISP1 DISP2 MODE 0 DISP2 Return to a reference screen DISP1 MODE 3 DISP2 Communication When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Pulse interval Pulse interval...
Page 24
Return to MODE 4 When there is a change, the dot at the lowest digit of DISP2 goes off. MODE Voltage scaling Voltage scaling Voltage scaling setting • This setting is for the scaling DISP1 Switching between 1.0 & value of the voltage value ...
3.8 Initialization The set parameters can be initialized (reset to the factory defaults) with the following procedure. With the instrument turned on, press the key and key simultaneously and hold them for more MODE than 3 seconds. Press and hold the MODE keys simultaneously.
□ 4 GLOSSARY 4.1 Slope The slope setting provides the output (actually the internal SV used processing) with slope (inclination). effective example in a 3-zone controlled electrical furnace system in which a single controller is used to control 3 sets of thyristor regulators. Control input (%) 4.2 Elevation The elevation setting provides the...
4.5 Heater Disconnection Alarm (a) This alarm is turned ON when the load resistance exceeds the set disconnection ratio. Ratio = [(Disconnection detection target resistance – Initial resistance) ÷ Initial resistance] × 100 (b) Alarm setting procedure 1. Enter the set value (SV) for use in normal control and continue running until the control stabilizes. 2.
In addition to the imbalance adjustment function, the JW Series also incorporates the imbalance alarm function that judges the degree of imbalance status of load currents as an alarm. This imbalance alarm is judged by the “Imbalance rate,”...
4.10 Priority The “priority” screen is provided with the beginning of the “MODE 0”, “MODE 1” and “MODE 2”. The “priority” screen is used to select whether the settings made on the thyristor regulator or those made on the setting communication unit become effective for the parameters to be set in these modes.
□ 5 ERROR MESSAGES AND MEASURES When any of the following messages is displayed in DISP1, an alarm activates or an error occurs. Identify the cause and take proper measure or repair before reusing the instrument. DISP1 display Error details & measures This display is for an abnormality between the internal circuitry of thyristor regulator and the ...
□ 7 DIMENSIONS & INSTALLATION 7.1 Dimensions 14.5 Panel cutout (Panel installation) 2-M3 2-∅3.5 *The actual designs differ from those shown. 7.2 Cable Connection for Panel Installation When the panel installation type is specified, connect the cable of the thyristor regulator, which is shown below, to the setting communication unit using a cable (SH-JUK3 for 3 m or SH-JUK5 for 5 m –...