Page 1
Technical manual air chillers and heat pumps with R290 refrigerant 37 - 63 k W R-290 Propane R-290 A3 gas leak R-290 Axial fan Cooling only Heating/Cooling EC scroll detection Refrigerant compressor PLUS » Refrigerant with GWP of less than 3 »...
Page 2
Dear Customer, Thank you for placing your trust in one of the products of Galletti S.p.a This product is the result of our work and our commitment to design, research, and production and has been made from the finest materials, employing state-of-the-art components and production technology.
SERIES PLP units are designed for heating and cooling the water to be protection, iP54 for the electrical control board), in a place not used in process air conditioning systems for residential, com- accessible to the public. mercial or industrial use. WARNING: Do not install the unit in environments with gas PLP units are designed for outdoor installation (guaranteed iPX4...
The choice of some options can make the choice of some 2 Compressor soundproof insulation others forbidden or make some selection (fields) mandatory. 5 Compressor soundproof insulation + low-noise fans Please contact Galletti S.p.A. for verification. Refrigeration circuit options 0 Absent Expansion valve...
TECHNICAL FEATURES RATED TECHNICAL DATA FOR PLP » Rated technical data for the PLP C water chiller PLP C Power supply V-ph-Hz 400-3-50 Cooling capacity (1)(E) 36,0 41,4 46,7 51,2 57,1 Total power input (1)(E) 12,0 14,0 16,4 18,1 19,2 (1)(E) 3,01 2,97...
PERFORMANCES Galletti has developed on its www.galletti.com web-area the new On-LinE integrated platform for product selection, configuration and the making of the economic offer. The software, whose use is easy and intuitive, allows the identification of the desired products by calculating their performances based on real working conditions and their configuration helping the user in choosing options and accessories.
CORRECTION OF THE HEATING CAPACITIES in the heat pump operation (heating mode), the actual heating capacities of units may be lower than the values shown in the tech- nical data table, due to the different values of the relative humidity of the external air. To obtain the actual heating capacity, multiply the capacity values by the corrective coefficients given in graphic.
Therefore, if you would like to operate continuously in the vicinity of the operating range, you should always make sure that the temperatures are in compliance with the operating limits, even under conditions of load regulation and splitting of the unit. if in doubt, contact the Galletti product support department. WARNING: the units are designed to operate with water and air temperatures falling within the range defined by the operating limits.
OPERATING LIMITS IN HEATING MODE PLP H » 8.2 PLP H operating range - heating mode T. Air (°C) T. W. Temperature of water produced T. A. Air temperature THERMAL CARRYING FLUID The hydraulic pumps belonging to the PLP series can operate with mixtures of water and ethylene glycol, with percentage indicated in the following table.
WATER PRESSURE DROP Y FILTER PRESSURE DROPS The table below shows the pressure drops of the Y filter (Δp) as a function of the water flow rate (Qw), assuming an average water temperature of 10 °C, Unit connections Unit connections type Threaded Threaded Threaded...
10 WATER CIRCUIT PLP units are equipped with a flow switch or water differential pressure switch, safety valve (supplied as standard), water pressure gauge, manual air vent valve, sludge remover (configurable) and deaerator (mandatory and configurable). See table below: » Water circuit design constraints Component always supplied as Installation mandatory Installation recommended...
Ū Silicon may pose a risk of corrosion. Limit: < 1 mg/l. Ū Electrical conductivity: the higher the specific resistivity, the lower the tendency of corrosion. Therefore, the following limit must be observed: Electrical conductivity: < 3,500 µS/cm Ū pH: neutral pH at 20 °C (7 < pH < 8) Ū...
Page 17
Ū safety valve conveyor pipe (VS), which, if the valve is opened, directs the water jet to areas where it cannot damage people or property (important!); Ū anti-vibration joints (GA) on the pipes to prevent vibration transmission to the system. important! it is advisable to ensure that the pipes connected upstream and downstream from the unit are not smaller in diameter than the unit's hydraulic connections.
105 DE-SUPERHEATER 1051 Recommended water circuit The partial heat recovery option is provided by a braze-welded plate heat exchanger placed in series on the compressor delivery (typically in series in relation to the finned pack condenser). its size is designed to limit pressure drops on the refrigerant side to a minimum.
uT2 if VARiAnT "1" is configured Main utility side (UT1) Main utility buffer tank (UT1) DHW buffer tank (UT2) DHW side (UT2) Main utility supplementary heating element (UT1) DHW supplementary heating element (UT2) The software can manage the enabling signal of a maximum of 2 supplementary heating elements. 107 HYDRAULIC DIAGRAM WITH ANTI-LEGIONELLA On the PLP range, anti-legionella control can be used if option 1 field 15 is configured.
Page 25
Main utility side (UT1) Unit electrical control board Main utility buffer tank (UT1) Utility electrical control board DHW buffer tank (UT2) DHW recirculation pump 10 DHW thermostatic mixing valve (hybrid mixer with digital controller DHW side (UT2) Main utility supplementary heating element (UT1) recommended) 11 DHW 3-way valve DHW supplementary heating element (UT2)
11 INSTALLATION CLEARANCE REQUIREMENTS To guarantee the proper functioning of the unit and access for maintenance purposes, it is necessary to comply with the mini- mum installation clearance requirements shown in dimensional drawings. Verify that there are no obstacoles in front of the fans air outlet. Ū...
12 INSTALLATION SITE FEATURES The units of the PLP range are designed for outdoor installation, in a context where the natural dilution of the refrigerant that could escape as the result of a leak guarantees a degree of safety. Each installation site must provide a safe area around the unit with the following characteristics.
Page 28
» Safety zone Area required for maintenance operations 1.5 m Area required for maintenance operations 1 m Safety zone (see table) » Distance "D" value assigned to each unit Model D (m) PLP037H PLP045H PLP052H PLP057H PLP062H PLP037C PLP045C PLP052C PLP057C PLP062C WARNING: in any case, the above requirements should be...
Page 29
in any case, avoid installing the units in locations that could be dangerous during placement, start-up, operation, and mainte- nance operations, such as areas without adequate protection against falls, areas with obstacles that create a danger of trip- ping or falling, and areas with buffer spaces that are not compli- ant with the documentation.
13 SITING AND DAMPERS it is important to bear in mind the following aspects when (see section on 14 p. 31). choosing the best site for installing the unit: When installing the vibration dampers follow the instructions Ū Size and origin of water pipes; below: 1 Screw the jack (6) into the vibration damper with jack sup- Ū...
15 WEIGHTS This drawing shows the points of the machine for which weights » PLP F2 have been calculated, with respect to the basic chiller and heat pump model. The weights are shown in the tables below. » PLP F1 »...
Page 34
» Operating weight C version without hydraulic options PLP C Total » Version C weight distribution with empty tank and 1 pump PLP C Total » Version C weight distribution with empty tank and 2 pumps PLP C Total » Version C weight distribution with empty tank + 2 pumps + flow rate measurement + desuperheater PLP C Total »...
Page 35
» Version H weight distribution with empty tank and 1 pump PLP H Total » Version H weight distribution with empty tank and 2 pumps PLP H Total » Version H weight distribution with empty tank + 2 pumps + flow rate measurement + desuperheater PLP H Total »...
16 ELECTRICAL DATA » Electrical data PLP Power supply V-ph-Hz 400-3-50 Auxiliary power supply V-ph-Hz 230-1-50 External power supply sensor 24VAC/DC Maximum power input 20,0 24,0 28,0 30,0 33,0 Maximum current absorption 42,0 48,0 56,0 59,0 62,0 Start up current Cross-section area of power cables mm²...
Page 37
and the ATEX extractor fan control unit are always supplied with and in front of the main switch (which cuts off the power to all power, so that they remain operational even when the unit's ordinary electrical equipment downstream when the electrical control board is switched off.
17 SG READY CERTIFICATION All units in the range can be configured for smart grid integra- The activation/deactivation of the two digital inputs, hereafter tion/interface. Two 24V AC digital inputs are used to manage referred to as SG1 and SG2, (also indicated on the unit's wiring 4 different operating logics in accordance with the SG Ready diagram and in the MiuM supplied as standard) results in the (Smart Heat Pumps) regulation issued by the Federal Heat Pump...
Page 40
Romagnoli 12/a 40010 Bentivoglio (BO) - italy Ph. +39 051/8908111 - Fax +039 051/8908122 Galletti S.p.A Organization has a Management System Certified ac- cording to the uni En iSO 9001:2015, uni En iSO 14001:2015 and uni iSO wwwgalletticom 45001:2018 standards.