InstallatIon, use and maIntenance manual chillers and heat pumps 4 kW - 76 k W Axial fan Scroll compressor Refrigerant Cooling only Heating/Cooling Packaged Rotary R-410A execution compressor PLUS » Completely configurable » Dual-compressor version that guarantees high efficien- cy at partial loads »...
Page 2
Dear Customer, Thank you for placing your trust in one of the products of Galletti S.p.a This product is the result of our work and our commitment to design, research, and production and has been made from the finest materials, employing state-of-the-art components and production technology.
Page 3
By en- ranty. suring this product is disposed of correctly, you will help Ū Galletti S.p.A. shall not accept any liability for injury to prevent potential negative consequences for the envi- or damage resultingcfrom improper use of the equip- ronment and human health.
Do not install the unit in environments with gas or flamma- ble dusts. MAIN FEATURES MPE water chillers and heat pumps are designed for outdoor installation in both residential and industrial applications. The range uses R410A refrigerant, which assures high levels of per-...
R410A refrigerant. NOTE: The choice of some options can make the choice of some The MPE series consists of 11 models only cooling mode and others forbidden or make some selection (fields) mandatory. 28 models in heat pumps with different powers. All models Please contact Galletti S.p.A.
(included). ELECTRONIC MICROPROCESSOR CONTROL COOLING CIRCUIT The electronic control enables the complete control of the MPE Ū Scroll type compressors in a tandem configuration that can unit. It can be easily accessed through a polycarbonate flap with be sound insulated (Frame 3 e 4).
Ū Heat recovery 25% (chiller) Ū Special exchangers (hydrophilic treatment, copper-copper, cataphoresis, anti-corrosion) FAN DRIVE ASSEMBLY Electric fan with 6/8-pole external rotor motor directly keyed to the axial fan, with internal thermal protection on the windings, complete with safety grille and dedicated supporting structure. The fan is housed in a special compartment having a profile de- signed to optimise ventilation.
Ū Solidity of the supporting surface; Galletti S.p.A. Must be notified of the entity of the damage with- Ū Avoid obstacles to the outflow of air from the fan which could in 8 days of the delivery date.
MPE H 04 - 08 , spazi installazione MPE 09-15 , spazi installazione MPE H 18-27; MPE C T18-T25 , spazi installazione MPE 28-40 - T30 - T42 and spazi installazione MPE T54 - T76 . Ū Verify that there are no obstacoles in front of the fans air out- let.
Page 11
» MPE H 04 - 08 RG66019585-04 All copying, even partial, of this manual is strictly forbidden...
Page 12
» MPE 09 - 15 » MPE T18-T25 INSTALLATION, USE AND MAINTENANCE MANUAL...
Page 13
» MPE 28 - 40 - T30 - T42 » MPE T54 - T76 RG66019585-04 All copying, even partial, of this manual is strictly forbidden...
TECHNICAL FEATURES MPE C WATER CHILLERS RATED TECHNICAL DATA » MPE C water chillers rated technical data Power supply V-ph-Hz 400 - 3N - 50 Cooling capacity (1)(E) 19,9 23,4 26,0 31,9 35,9 42,5 54,6 56,9 65,8 71,5 Total power input...
Page 22
MPE H HEAT PUMPS RATED TECHNICAL DATA » MPE H heat pumps rated technical data 004M 005M 007M 008M Power supply V-ph-Hz 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 400 - 3N - 50...
MICROPROCESSOR CONTROL Below are specified the microprocessor control functions in the The advanced control instructios are described in service basic version. manual. USER INTERFACE The control panel of the unit enables the user to display and set been triggered. Any new settings saved are stored in the card the unit's operating parameters and read the main operating and used the next time the unit is switched on, even following data.
KEYS FUNCTIONS PROGRAMMING BY KEY The control parmeters were collected in functional groups (CF=- KEYS FUNCTION configuration, CO=compressor) each identified with a label; Push and release in main display: general group ALL contain all control's parameters. allows to display chiller (label SetC) or pdc (label 5.3.1 How to access the “Pr1”...
(close=ON) Ū Connect summer/winter signal in terminal block on 19/30 Ū push SET key near rSt label for reset the alarm and move to (close =Summer) the next; Ū Enable the contacts through parameters CF8 = 4 e CF10 = 3 Ū...
The first start up must be carried out exclusively by qualified as residue from the work carried out (e.g. welding). Continue personnel and authorized by Galletti S.p.A. (see warranty flushing until the water (to be disposed of ) becomes clear.
Ū discharge cock and, where needed, drain tank in order to empty the system for maintenance or seasonal stops. Drain- All the units belonging to the MPE series are equipped with wa- age valve is provided on the optional water buffer tank: this...
sure there are no open flames in proximity to or inside the Percentage by weight of ethylene glycol Mixture freezing temperature (°C) unit. When setting up the water circuit, it is advisable to equip it with: Ū valves for regulating (VI) the unit on the water pipes, imme- diately upstream and downstream from the unit itself, to be used in the event maintenance work is required;...
IEC Standards (contacts must be Ū a remote switch for changing over between the cooling and open at least of 3 mm), with suitable interruption capacity heating mode (MPE H only), and differential protection, according to the electrical data Ū a remote alarm indicator...
ELECTRICAL DATA » MPE C Maximum power input 10,1 15,9 16,1 20,9 24,4 21,7 27,0 28,2 31,6 35,4 Maximum current absorption 16,2 25,5 25,8 33,5 39,1 34,8 43,3 45,2 58,7 56,8 Start up current Startup current with soft starter Fan motor rated power...
Page 34
» MPE H 004M 005M 007M 008M 010M Maximum power input 2,00 2,30 3,00 5,00 5,00 7,20 5,10 8,90 10,5 Maximum current absorption 9,00 11,0 11,0 9,00 17,6 8,00 12,0 24,0 15,0 11,0 18,0 Start up current Startup current with soft starter...
Page 35
maximum current allowed in the unit This value may never » PCD remote control panel electrical connection diagram be exceeded; it must be used as a reference for determining the size of the power supply line and the related safety de- vices (refer to the wiring diagram supplied with the units).
OPERATING LIMITS 1. Value achievable only for outdoor air temperatures above 0 The graphs below illustrate the operating limits of MPE units (in the case of continuous operation) in relation to the outlet water ° C. temperature and outdoor air temperature.
Parameters GAIN and INT TIME are regulation parameters; they have to be modified inside the electronic expansion valve driv- er. Both modifications should only made in the factory or im- plemented on the field, but only by Galletti S.p.A. authorized personnel. THERMAL CARRYING FLUID The units belonging to the MPEseries can work with mixtures of water and up to 25% ethylene glycol.
CONTROL AND SAFETY DEVICES 9.2.7 Safety device settings All the control and safety devices are set and tested in the facto- ry before the unit is dispatched. Safety device Start up Differential Resetting CONTROL DEVICES Maximum pressure switch (bars) Manual Pressure safety valve (bars) Manual Minimum pressure switch (bars)
10 ROUTINE MAINTENANCE AND CHECKS It is recommended to carry out periodic checks of the safety it must be inspected by qualified personnel who must first devices (pressure switches and safety valves) and verify the ab- check the integrity of the cooling circuit (pipes and compo- sence of refrigerant leaks.
Operations marked with the letter "S" may be performed exclusively by specialised personnel. Once the cause has been identified, you are advised to contact a Galletti S.p.A. service centre or a qualified technician for help.
Page 63
Who can take corrective action Possible control panel SYMPTOM U = User Probable cause Possible remedy indication S = specialised personnel Unit completely empty See item G Water circulation pump Release the pump blocked Water circulation pump Check the pump and replace it if necessary. blocked defective The compressor Presence of frost on the...
14 RETIRING THE UNIT When the unit has reached the end of its working life and needs quantities of copper, aluminium and steel present in the to removed and replaced, a series of operations should be car- unit. This will make the job of waste collection, disposal and ried out: recycling facilities easier and minimise the environmental Ū...