Galletti WLE052 Technical Manual

Galletti WLE052 Technical Manual

Chillers and heat pumps 42 kw-750 kw

Advertisement

Quick Links

EN
Technical manual
WLE
chillers and heat pumps
42 k W - 7 50 kW
R-454B
A2L gas leak
Scroll
Cooling only Heating/Cooling
 
refrigerant
detection
compressor
PLUS
» Refrigerant with GWP of less than 500
» Electronic expansion valve
» Up to 6 compressors
» 1 or 2 cooling circuits
» Remote connectivity with the most common protocols
» Compact dimensions
» 3 different acoustic configurations
» High seasonal efficiency values

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WLE052 and is the answer not in the manual?

Questions and answers

Summary of Contents for Galletti WLE052

  • Page 1 Technical manual chillers and heat pumps 42 k W - 7 50 kW R-454B A2L gas leak Scroll Cooling only Heating/Cooling   refrigerant detection compressor PLUS » Refrigerant with GWP of less than 500 » Electronic expansion valve » Up to 6 compressors »...
  • Page 2 Dear Customer, Thank you for placing your trust in one of the products of Galletti S.p.a This product is the result of our work and our commitment to design, research, and production and has been made from the finest materials, employing state-of-the-art components and production technology.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS SERIES                                         p 4 BEYOND CONVENTIONAL EFFICIENCY LIMITS                                                 p 4 CONSTRUCTIVE FEATURES...
  • Page 4: Series

    SERIES WLE series water chillers and water-cooled monobloc reversi- requirements specified in Uni En 378-3. ble heat pumps are designed for heating or cooling water for WARNING: The design of machinery room are on responsa- residential and commercial air-conditioning systems as well as bility of the installer.
  • Page 5: Configuration Options

    0 Indoor 1 Outdoor NOTE: The choice of some options can make the choice of some others forbidden or make some selection (fields) mandatory. Please contact Galletti S.p.A. for verification. Power factor capacitors Soft starter Service kit (advanced controller required)
  • Page 6: Technical Features

    TECHNICAL FEATURES WLE C WATER CHILLERS RATED TECHNICAL DATA Cooling capacity (1)(E) 45,3 57,9 66,3 76,8 85,7 Total power input (1)(E) 10,5 13,5 15,2 17,7 19,8 26,3 29,9 (1)(E) 4,30 4,27 4,36 4,35 4,32 4,39 4,37 SEER (2)(E) 5,72 5,98 6,02 5,78 5,95...
  • Page 7 Cooling capacity (1)(E) Total power input (1)(E) 51,9 58,8 66,6 76,6 81,9 89,3 99,2 (1)(E) 4,45 4,46 4,44 4,56 4,59 4,69 4,81 SEER (2)(E) 6,14 6,08 6,40 6,38 6,11 6,71 6,77 Water flow user side 39728 45112 50884 59992 64563 72043 82068 Water pressure drop user side...
  • Page 8: Heat Pumps Rated Technical Data Wle H

    HEAT PUMPS RATED TECHNICAL DATA WLE H Power supply V-ph-Hz 400/3N/50 Cooling capacity (1)(E) 44,9 55,6 65,4 76,4 85,7 Total power input (1)(E) 11,6 13,9 16,1 18,9 20,6 28,3 32,0 (1)(E) 3,87 4,00 4,06 4,04 4,16 4,04 4,07 SEER (2)(E) 5,64 5,89 5,93...
  • Page 9 Power supply V-ph-Hz 400/3N/50 Cooling capacity (1)(E) Total power input (1)(E) 37,0 36,3 42,4 43,7 49,1 51,2 54,4 (1)(E) 4,02 4,00 4,11 4,05 4,16 3,96 4,23 SEER (2)(E) 5,97 5,46 6,00 6,38 5,75 6,02 5,69 Water flow user side 25587 24972 29949 30431...
  • Page 10 Power supply V-ph-Hz 400/3N/50 Cooling capacity (1)(E) Total power input (1)(E) 57,3 64,7 73,9 85,1 91,0 96,2 (1)(E) 4,00 4,03 4,01 4,11 4,14 4,37 4,46 SEER (2)(E) 6,05 5,99 6,31 6,29 6,02 6,61 6,67 Water flow user side 39448 44776 50946 60069 64702...
  • Page 11: Ped Category

    Power supply V-ph-Hz 400/3N/50 Cooling capacity (1)(E) Total power input (1)(E) (1)(E) 4,20 4,24 4,29 4,19 SEER (2)(E) 6,59 6,63 6,62 6,70 Water flow user side 93295 102590 111672 120233 Water pressure drop user side (1)(E) Water flow source side 114637 125788 136556...
  • Page 12: Performances

    PERFORMANCES Galletti has developed on its www.galletti.com web-area the new On-LinE integrated platform for product selection, configuration and the making of the economic offer. The software, whose use is easy and intuitive, allows the identification of the desired products by calculating their performances based on real working conditions and their configuration helping the user in choosing options and accessories.
  • Page 13: Sound Levels

    SOUND LEVELS 100 Hz 125 Hz 160 Hz 200 Hz 250 Hz 315 Hz 400 Hz 500 Hz 630 Hz 800 Hz 50 Hz (1) 63 Hz (1) 80 Hz (1) Mod. WLE052CS 67,0 61,0 25,2 43,4 62,5 WLE062CS 69,0 63,0 27,2 45,4...
  • Page 14 1000 Hz (1) 1250 Hz (1) 1600 Hz (1) 2000 Hz (1) 2500 Hz (1) 3000 Hz (1) 4000 Hz (1) 5000 Hz (1) 6000 Hz (1) LwA (2) Mod. dB(A) WLE052CS 61,3 60,2 50,8 WLE062CS 63,3 62,2 52,8 WLE072CS 64,3 63,2 53,8...
  • Page 15: Operating Limits

    Therefore, if you would like to operate continuously in the vicinity of the operating range, you should always make sure that the temperatures are in compliance with the operating limits, even under conditions of load regulation and splitting of the unit. if in doubt, contact the Galletti product support department. WARNING The units are designed to operate with water temperatures within the operating limits.
  • Page 16: 92 Operation Limits Wle H                     P

    OPERATION LIMITS WLE H » WLE H operating range - cooling mode OPT 1 Glycol T out U Outlet water temperature (user) T out S Outlet water temperature (source) » WLE H - 052-072 operating range T out U Outlet water temperature (user) T out S Outlet water temperature (source) TECHniCAL MAnUAL...
  • Page 17: 93 Thermal Carrying Fluid                    P

    » WLE H 082-122 e 154-214 operating range T out U Outlet water temperature (user) T out S Outlet water temperature (source) » WLE H 244-746 operating range T out U Outlet water temperature (user) T out S Outlet water temperature (source) THERMAL CARRYING FLUID The heat exchangers belonging to the WLE series can operate with mixtures of water and up to 35% ethylene glycol.
  • Page 18 fluid. TECHniCAL MAnUAL...
  • Page 19: Water Pressure Drop

    10 WATER PRESSURE DROP 10.1 Y FILTER PRESSURE DROPS The table below shows the pressure drops of the Y filter (Δp) as a function of the water flow rate (Qw), assuming an average water temperature of 10 °C, Water connections 2”...
  • Page 20 » Y Filter pressure drops Frame 4,5 kPa: Water pressure drop mc/h: Flow TECHniCAL MAnUAL...
  • Page 21: Water Circuit

    11 WATER CIRCUIT When setting up the water circuit of the unit, it is advisable to buffer tank: this operation may only be carried out when the follow the directions below and in any case comply with local or unit is disconnected from the power supply). national regulations.
  • Page 22: 112 Water Circuit                                P

    11.2 WATER CIRCUIT » WLE (evaporator) LEGEND Evaporator Water filter (included) Flow switch 10 Antifreeze electric heating Pressure gauge ------ Internal and external borderline ——— OPTIONAL 11.3 DE-SUPERHEATER 11.3.1 Recommended water circuit The partial heat recovery option is provided by a braze-welded plate heat exchanger placed in series on the compressor deliv- ery (typically in series in relation to the finned pack condenser).
  • Page 23 Utility side Buffer tank Mixing valve Circulation pump On-board desuperheater The bulb of the 3-way mixer valve is placed at the de-superheat- er exchanger inlet. By mixing the hot water produced by the recovery with colder water from the tank, it reduces the time needed for the system to reach full operating capacity to a few moments.
  • Page 24 11.3.2 Water pressure drop no. of cooling circuits no. of desuperheaters De-superheater type CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 no. of cooling circuits no. of desuperheaters De-superheater type CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 CBH110 CBH110...
  • Page 25 » Dual-circuit pressure drops 11.3.3 Heating capacities » De-Superheather heating capacities De-superheater heating capacity circuit 1 De-superheater heating capacity circuit 2 De-superheater water flow for ciruit 1238 1569 1833 2163 2477 3220 3649 4161 4822 5713 6374 2031 2477 De-superheater water temperature 40/ 45 °C, sourse side water temperature 12 / 7°C De-superheater heating capacity circuit 1 De-superheater heating capacity circuit 2 De-superheater water flow for ciruit...
  • Page 26: Installation Clearance Requirements

    12 INSTALLATION CLEARANCE REQUIREMENTS During handling it is compulsory to check dimensions, weights, members and identified by means of appropriate stickers. The centre of gravity and anchorages. Check as well that lifting and pipes, which must project at least 300 mm on every side, will positioning devices conform to the current safety regulations.
  • Page 27: Dimensions

    14 DIMENSIONS » WLE 52 - 92 RG66022197-01 All copying, even partial, of this manual is strictly forbidden...
  • Page 28 » WLE 122 - 152 TECHniCAL MAnUAL...
  • Page 29 » WLE 182 - 242 RG66022197-01 All copying, even partial, of this manual is strictly forbidden...
  • Page 30 » WLE 154 - 274 TECHniCAL MAnUAL...
  • Page 31 » WLE 314 - 384 RG66022197-01 All copying, even partial, of this manual is strictly forbidden...
  • Page 32 » WLE 454-504 TECHniCAL MAnUAL...
  • Page 33 » WLE 606 - 746 RG66022197-01 All copying, even partial, of this manual is strictly forbidden...
  • Page 34: Weights

    15 WEIGHTS This drawing shows the points of the machine for which weights have been calculated, with respect to the basic chiller and heat pump model. The weights are shown in the tables below. » WLE Frame 1 » WLE Frame 2 »...
  • Page 35 » Lifting center of gravity for transporting unit C version without hydraulic options 1526 1507 1488 1376 1560 1551 1560 1545 » Lifting center of gravity for transporting unit H version without hydraulic options 1521 1502 1484 1375 1390 2669 2775 2734 2838...
  • Page 36: Electrical Data

    Total 1012 1121 1425 1523 Total 1555 1959 2008 16 ELECTRICAL DATA » Electrical data WLE Maximum current absorption 29,0 36,0 42,0 49,0 57,0 72,0 81,0 91,0 90,0 Start up current Startup current with soft starter Auxiliary power supply V-ph-Hz 230/1/50 Cross-section area of power cables mm²...
  • Page 37 » Main electrical connection of units RG66022197-01 All copying, even partial, of this manual is strictly forbidden...
  • Page 38 Romagnoli 12/a 40010 Bentivoglio (BO) - italy Galletti S.p.A Organization has a Ph. +39 051/8908111 - Fax +039 051/8908122 Management System Certified by Kiwa Cermet italia S.p.A, according to the Uni En iSO 9001:2015, Uni En iSO 14001:2015 and Uni iSO www.galletti.com...