Download Print this page

olympia electronics BAU LIGHT Series Manual

Self testing maintained / non-maintained emergency luminaries with wireless communication

Advertisement

Quick Links

Package Contents
1
Luminaire
Pictogram Sets
2
Mounting accessories
1
1
Manual
General
These devices are used indoors and (ta 40oC) in places where emergency light is needed. Each device
must be permanently connected to mains power supply. In normal operation the battery is charging. In
case of a mains power supply failure, the device enters emergency mode and the illumination LED
turns on. When the mains power supply is restored the device turns to normal operation.
Manual Operational Test
By pressing the test button briefly an operation test is initiated. The light source and the emergency
circuit of the device are tested. The manual test can be conducted only if the mains power supply and
the battery are connected. During this test period the CHARGE LED starts blinking fast. The battery must
have adequate charge. This test lasts for 3 seconds.
Manual Autonomy Test
A duration test can be conducted by pushing the button steadily for 5 to 10 seconds. In order to be
performed, the mains power supply should be connected and the battery should be fully charged. The
luminaire enters emergency mode, the charge LED starts blinking fast. Its duration is the stated
autonomy duration of the luminaire. If at the end of the test the autonomy is lower than the nominal,
the Fault LED will lit and battery needs to be replaced. If the result of the test is good then the luminaire
enters charging mode and the Charge led starts blinking fast until the battery is fully charged.
Automatic Operational Test
This test includes all the operations that are provided in Manual Operational Test and is conducted
automatically every 15 days and lasts 3 seconds.
Automatic Autonomy Test
The Automatic Autonomy Test is conducted every 6 months and measures the device's back up
operation and emergency duration. This test includes all functions of the Manual Autonomy Test.
Wireless communication
The WL luminaire models have the ability to communicate over the air with Olympia's control panels
for wireless emergency luminaires. The luminaires can also communicate with a PC/laptop through a
gateway (Ethernet, Wi-Fi, USB). For more information, please refer to Wireless Emergency Lighting
guides, available on the company's website.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or testing must be done by authorized personnel only.
2. Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type 2x1mm² or
any other type, at least equal to it's mechanical and electrical properties). ATTENTION!! The cable must
not be deformed in any way (This requirement is important to ensure the ΙΡ rating).
3. The device must be connected to the mains power supply through a circuit breaker that is depends
on the total line's power load.
4. In case of battery replacement, it must be replaced by the same type, by the manufacturer or a
competent person.
5. In case of inactive use for a period greater than 2 months, disconnect the battery by pulling out the
battery's connector.
6. It is not allowed to discard batteries into common trash bins, they must be discarded only in battery
recycling points. Do not incinerate.
Indications LED Status
GREEN
RED
Description
(charge)
(Fault)
Normal
Charging
(autonomy test not possible while charging)
Mains off
(battery not connected or charger fault)
Autonomy Test (Duration: 1h, 3h, 8h)
Battery Fault
Operational Test (Duration: 3s)
Light Source Fault
Battery Fault & Light Source Fault
Note:
Permanently ON
Fast Blink
1
Installation Instructions
Οδηγίες Εγκατάστασης
1
2
3
DS1
The user can select one of the 3 available minimum autonomy durations 1 hour, 3 hours and 8 hours. The
selection is achieved through Switches 2 & 3 of DS1. Two additional labels are included in the package, one
for 1 hour duration (60) and one for 8 hours duration (480). Depending on the selected duration, the
installer must replace the default 3 hours (180) label with one that has the required duration. Please take
notice of the orientation of the label.
The control of maintained or non maintained operation of the luminaire is achieved through Switch 4 of DS1.
ATTENTION! The selection must be done while the luminaire is disconnected from AC and battery
supplies.
Slow Blink
Off
Non relevant
4
2
923753004_09_002
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1h
3h
8h
Maintained
Non-Maintained
(Default Position)
Operation
Operation
(Default Position)
923753004_09_002
Install the included grommet in to the cable entry hole (verify that is not deformed). Make a hole in the
center of the grommet by using a small screwdriver. Pass the round cable through the grommet and
connect the wires. Install the included tie-wrap to the included adhesive tether loop and fasten
securely the power cable in order to anchor it. ATTENTION!! The cable must not be deformed in any
way (This requirement is important to ensure the ΙΡ rating).
Power Connection
N
L
Ν for neutral, L for live wire
5
Battery Connection
6
7
8
NOTE!!
After finishing the installation you must power the luminaire for at least 24 hours in order to
completely charge the battery. The rated autonomy duration can be achieved after that time.
Battery Replacement
It can be done only by a competent person and after the mains interruption.
1. Dismantle the luminaire.
2. Disconnect the battery connector and remove the old battery.
3. Connect the new battery with the same type and characteristics.
4. Assembly the luminaire.
3
923753004_09_002

Advertisement

loading
Need help?

Need help?

Do you have a question about the BAU LIGHT Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for olympia electronics BAU LIGHT Series

  • Page 1 Package Contents Installation Instructions Οδηγίες Εγκατάστασης Luminaire Pictogram Sets Mounting accessories Manual General Install the included grommet in to the cable entry hole (verify that is not deformed). Make a hole in the These devices are used indoors and (ta 40oC) in places where emergency light is needed. Each device center of the grommet by using a small screwdriver.
  • Page 2 Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done by a third party, Non Maintained operation: The luminaire lights its illumination source, only in power supply’s unless Olympia Electronics has fully agreed to them in writing.

This manual is also suitable for:

Gr-750/st/hp/ll/wlGr-751/st/lp/ll/wlGr-752/st/hp/hl/wlGr-753/st/lp/hl/wl