Ordering Information Sheet NXXXXX (included with the option code ‘/SET’ only) ■ MODEL NO. Confirm Model No. marking on the product to be exactly what you ordered. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• Using the unit continuously may result in a fire or electric shock. Do not throw the unit into the fire. • Doing so may result in rupture of the electronic component. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 7
• Doing so may result in electric shock, damage of the unit or injury. Do not use the unit in the atmosphere where combustible gas is present. • Doing so may result in inflammation, ignition or smoke. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• The watertight packing included in the product package must be placed between the body and panel when installing on the panel. • Fasten the body and panel together with four M4 × 10 screws (torque: 0.6 – 0.9 N·m). MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 9
– The packing is run off the edge. – The packing is cut off. – There are foreign objects sticking. • When replacement of the watertight packing is needed, consult us. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• The engineering unit sticker label position is our recommended position. • When an engineering unit is specified by the Ordering Information Sheet, the unit(s) will be shipped with the sticker label put on the above position. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 11
• When a tag No. is specified, the unit(s) will be shipped with the tag No. sticker label put on the above position. Max. 17 alphanumeric characters can be specified. Please consult us. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7...
Page 12
■ BOTTOM VIEW NOTE Contents of the specification label depend on the specifications. ■ REAR VIEW MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Panel cutout must be such as specified by us. unit: mm (inch) unit: mm (inch) IMPORTANT Remove burrs from the panel cut surface so that they may not damage the wires. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 14
Unit xing screws (M4 x 10) IMPORTANT To conform to degree of protection IP66, confirm visually that the packing is not contorted, cut off or excessively run off the edge after installation. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 15
(1) Tear off a protective seal, and attach it to the unit. Body Wire Magnet label sheet (2) Attach the stopper to the unit to fix the wire. Stopper MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 16
• For magnet mounting, DO NOT use where it is subjected to continuous vibration or DO NOT subject the unit to physical impact. • The sheath of wire must be 2 mm or less. • Clustered Mounting unit: mm (inch) 96.0 (3.78) min. 120 (4.72) MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Blade edge: 0.4 mm (0.02”) Blade width: 2 mm (0.08”) Procedures are as follows. (1) Insert a minus screwdriver into the dead end to open the spring. Minus screwdriver MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• Take measures to prevent the sheath of wire from being caught in terminal(s) to avoid contact failure. • Pull the wire(s) lightly to confirm that the wire is not pulled off. 1.6.4 TERMINAL ASSIGNMENT Alarm output Power Input signal MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• With inductive load such like an external relay or a motor, insert a CR circuit, a diode or a varistor in parallel to protect the contacts and eliminate noise. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• In order to prevent potential electric shock, wire the unit after turning off the power supply and making sure that the power is not supplied to the cable. • Be sure to confirm the polarity in wiring. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Return to Measuring Mode (measurement started). • Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to apply the new setting and return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
‘-’ . • The negative sign (-) must be set to the leftmost digit. For example, set ‘-040.0’ instead of ‘-40.0’ . * Fifth digit MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
■ IN MOVING ON TO EACH SETTING MODE FROM MEASURING MODE • The last values of the alarm outputs before mode transition are held. ■ ORDER TO DISPLAY PARAMETERS • Refer to 6. PARAMETER CONFIGURATION for details. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Hold down Scale/↑ button for 3 seconds or more to move on to Initial Setting Mode. • ‘F’ is indicated. • ‘Fnc’ indicator turns on. NOTE Skip to Step 6 if the default value is acceptable. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 25
Measuring Mode without applying the last changes. • If you get lost in a setting mode, you can execute initialization. (Refer to 16.2 INITIALIZING SETTING VALUES.) MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Hold down Scale↑ button for 3 seconds or more to move on to Initial Setting Mode. • The temperature unit is indicated. • ‘Fnc’ indicator turns on. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 27
Measuring Mode without applying the last changes. • If you get lost in a setting mode, you can execute initialization. (Refer to 16.2 INITIALIZING SETTING VALUES.) MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
‘P’ indicator on. Blinking Provide 100°C input and make sure that 100°C is indicated. NOTE When the indication is shifted, perform Input Compensation. (Refer to 14.1 INPUT COMPENSATION.) MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
■ TRANSITION FROM EACH MODE TO MEASURING MODE Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 30
• The display depends on the settings and input. The above displays show default values. • Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode from each parameter. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7...
Page 31
• Alarm Setting Mode is locked when “No alarm” is selected for the alarm point parameter. • Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode from each parameter. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7...
Page 32
• The display depends on the settings and input. The above displays show default values. • Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode from each parameter. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7...
Main display blinking at alarm No blinking Blinking in 1.0 second intervals Blinking in 0.5 second intervals Blinking in 0.2 second intervals Blinking in 0.1 second intervals MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 34
(2) The display value exceeds the setpoint and stays over the trip delay time period. Therefore alarm output is provided. Alarm output With deadband Without deadband (setting value: 0000) Preventing chattering MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 35
‘downscale burnout’ setting. • When the temperature unit and decimal point position are changed, the alarm setpoints will be reset to ‘-----’ . MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Skip to Step 2 in “7.2 ALARM SETPOINT” . ■ TO QUIT, Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
The setpoint is indicated within the range of -9999 to 9999 depending on the setting. Press Shift button to shift the display into the setting standby mode. Blinking • The fifth digit starts blinking, to which you can apply changes. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 39
Skip to Step 2 in “7.3 TRIP ACTION (LO/HI)” . ■ TO QUIT, Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• ‘LMLO’ is indicated. • ‘L’ (‘H’) indicator blinks and ‘Fnc’ indicator turns on. Blinking Display in setting H trip action Press Shift or Up button to select ‘LMHI’. Blinking MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 41
Skip to Step 2 in “7.4 DEADBAND” . ■ TO QUIT, Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
The L (H) deadband is indicated within the range of 0000 to 9999 depending on the setting. Press Shift button to shift the display into the setting standby mode. Blinking • The forth digit starts blinking, to which you can apply changes. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 43
Skip to Step 2 in “7.5 TRIP DELAY” . ■ TO QUIT, Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
The trip delay is indicated within the range of 00 to 99 depending on the setting. Press Shift button to shift the display into the setting standby mode. Blinking • The second digit starts blinking, to which you can apply changes. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 45
Skip to Step 2 in “7.6 ALARM OUTPUT LOGIC (coil energized or de-energized at alarm)” . ■ TO QUIT, Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• ‘L’ (‘H’) indicator blinks and ‘Fnc’ indicator turns on. Blinking Display in setting H coil at alarm Press Shift or Up button to select ‘RYDN’. Blinking MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 47
Skip to Step 2 in “7.7 MAIN DISPLAY BLINKING AT ALARM” . ■ TO QUIT, Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• The main display blinking at alarm is indicated. • ‘Fnc’ indicator turns on. NOTE ‘B 0’ , ‘B 1’ , ‘B 2’ , ‘B 3’ or ‘B 4’ is indicated depending on the setting. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 49
• Press Scale/↑ button, and the H coil at alarm ‘RYEN’ or ‘RYDN’ will be indicated depending on the setting. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7...
No. reaches the set value, all samples are averaged every 25 milliseconds. (2) After the sampling No. reaches the set value, a new sample is added to be averaged with the oldest one omitted. Such operation is repeated. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• Press Scale/↑ button, and the version indication will be indicated. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
‘C 1’ , ‘C 2’ , ‘C 3’ , ‘C 4’ or ‘C 5’ is indicated depending on the setting. Press Shift or Up button to select. Blinking • Select one among ‘C 1’ , ‘C 2’ , ‘C 3’ , ‘C 4’ and ‘C 5’ MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 54
• Press Scale/↑ button, and the moving average sampling No. ‘ A OFF’ , ‘ A 2’ , ‘ A 4’ , ‘ A 8’ , ‘ A 16’ , ‘ A 32’ or ‘ A 64’ will be indicated depending on the setting. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• The second digit starts blinking, to which you can apply changes. Press Shift and Up buttons to set the setting time out. • Set within the range of ‘R 00’ to ‘R 99’ . MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 57
• Press Scale/↑ button, and the brightness ‘C 1’ , ‘C 2’ , ‘C 3’ , ‘C 4’ or ‘C 5’ will be indicated depending on the setting. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7...
Press Alarm/↓ or Scale/↑ button to go to the burnout setting. • ‘BN U’ is indicated. • ‘Fnc’ indicator turns on. Press Shift or Up button to select ‘BN D’. Blinking MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 59
• Press Scale/↑ button, and the transition time to Lockout Setting Mode will be indicated within the range of ‘P 00’ to ‘P 99’ depending on the setting. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• The third digit starts blinking, to which you can apply changes. Press Shift and Up buttons to set the display refreshing rate. • Set within the range of ‘F00.0’ to ‘F99.9’ . MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 62
• Press Scale/↑ button, and the burnout ‘BN U’ or ‘BN D’ will be indicated depending on the setting. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7...
• The alarm setpoints can be confirmed even when MAX or MIN value is indicated. After confirmation, the indication will be back to MAX or MIN value. • The alarm setpoints cannot be confirmed while ‘S.ERR’ or ‘B.ERR’ is indicated. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
(3) The internal memory is reset for approx. 5 seconds after the power is off and on again, and then the unit starts to meas- ure MAX and MIN values again. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 65
• Pressing Max/Min button while in confirming the alarm setpoints switches the indication to MAX or MIN value. • MAX and MIN values are not indicated while ‘S.ERR’ or ‘B.ERR’ is indicated. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
‘ A OFF’ or ‘ A ON’ is indicated depending on the setting. Press Alarm/↓ or Scale/↑ button to go to the advanced setting lockout setting. • ‘DOFF’ is indicated. • ‘D/P’ and ‘Fnc’ indicators turn on. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 67
• Press Scale/↑ button, and the initial setting lockout ‘IOFF’ or ‘I ON’ will be indicated depending on the setting. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7...
The transition time is indicated within the range of ‘P 00’ to ‘P 99’ depending on the setting. Press Shift button to shift the display into the setting standby mode. Blinking • The second digit starts blinking, to which you can apply changes. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 69
• Press Scale/↑ button, and the setting time out will be indicated within the range of ‘R 00’ to ‘R 99’ depending on the set- ting. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
After comp. = before comp. + comp. value Positive comp. value: addition • Set the values within the range of -9999 to 9999. Negative comp. value: subtraction MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• The input compensation A input value is registered. • The input compensation A compensation value is indicated. • ‘Zro’ , ‘Tch’ and ‘Fnc’ indicators turn on. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 72
* ‘Spn’ , ‘Tch’ and ‘Fnc’ indicators turn on with input compensation B compensation value setting. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• Check the wiring periodically. In checking the wiring, for safety, interrupt electricity to the power, input and alarm output. • Make sure periodically that the screws are fixed tightly. Loosened screws may cause drop of the unit. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7...
• The alarm setting lockout is indicated. • ‘D/P’ and ‘Fnc’ indicators turn on. NOTE ‘ A OFF’ or ‘ A ON’ is indicated depending on the setting. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 75
Press Alarm/↓ or Scale/↑ button to execute the initialization. • The initialization will be completed in approx. 3 seconds and the display will return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
• The above figures show the firmware version V1.00.0015. • The displays depend on the firmware version number. Hold down Alarm/↓ or Scale/↑ button for 3 seconds or more to return to Measuring Mode. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
JPt 100 (JIS ’89) 0.5 mA Pt 100 (JIS ’89) 0.5 mA Pt 100 (JIS ’97, IEC) 0.5 mA Pt 50 Ω (JIS ’81) 0.5 mA Pt 1000 0.05 mA MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Page 78
1500 V AC @ 1 minute (input to alarm output to power to ground) ■ STANDARDS & APPROVALS EU conformity EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
*1 Conforms to decimal point position setting. NOTE 1: Indicators with the present value in Measuring Mode depend on the set alarm trip action. NOTE 2: INDICATOR: = ON, = Blinking MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
H alarm setpoint NOTE • The display depends on the settings and input. • When “No alarm” is selected for the alarm point parameter, alarm setpoints cannot be confirmed. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Input comp. A input value -9999 to 9999 -9999 to 9999 Input comp. B comp. value -9999 to 9999 NOTE The display depends on the settings and input. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
NOTE • The display depends on the settings and input. • Alarm Setting Mode is locked when “No alarm” is selected for the alarm point parameter. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Version indication Indicating rmware version e.g. V1.00.0015 NOTE • The display depends on the settings and input. • Version indication is for indication only, not for setting. MG CO., LTD. www.mgco.jp 47NLR EM-9565-B Rev.7 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
Need help?
Do you have a question about the 47NL Series and is the answer not in the manual?
Questions and answers