INSTALLATION GUIDE
TruClimate 100
2-5 Tons / Water-to-Water Heat Pump
R-454B / 60Hz
General Installation Information ................................................................................................ 2
Refrigeration Detection and Mitigation ................................................................................. 4
Serial Plate ......................................................................................................................................... 8
Dimensional Data ............................................................................................................................ 9
Physical Data .................................................................................................................................... 10
Installation ......................................................................................................................................... 11
Water Quality ................................................................................................................................... 12
Field Connected Water Piping................................................................................................... 13
Potable Water Systems ................................................................................................................ 16
Electrical Information .................................................................................................................... 18
Converting to Dedicated Cooling Unit ................................................................................... 20
Reference Calculations, Legend ................................................................................................ 21
Unit Startup ....................................................................................................................................... 22
Refrigerant Removal and Evacuation ..................................................................................... 23
Charging Procedures ..................................................................................................................... 23
Refrigerant Recovery..................................................................................................................... 24
Refrigeration Cycle Analysis ....................................................................................................... 25
Revision Guide ................................................................................................................................. 27
WARNING: Before performing service or maintenance
operations on the system, turn off main power switches
to the unit. Electrical shock could cause serious personal
injury.
WARNING: All products are designed, tested, and
manufactured to comply with the latest publicly released
and available edition of UL 60335-2-40 for electrical
safety certification. All field electrical connections must
follow the National Electrical Code (NEC) guide standards
and / or any local codes that may be applicable for the
installation.
WARNING: Only factory authorized personnel are
approved for startup, check test and commissioning of
this unit.
INSTALLER: Please take the time to read and understand
these instructions prior to any installation. Installer must
give a copy of this manual to the owner.
Definition of Warnings and Symbols
DANGER
W
WARNING
CAUTION
NOTICE
Conforms To UL STDS 60335-1 & 60335-2-40
Certified To CSA STDS C22.2 # 60335-1 & 60335-2-40
WARNING
Indicates a situation that results in death or
serious injury.
Indicates a situation that could result in
death or serious injury.
Indicates a situation that could result in
minor or moderate injury.
Indicates a situation that could result in
equipment or property damage.
For the User
This appliance is not intended for use by persons (including
children) with reduced physical, sensory, or mental capabilities,
or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play
with the appliance.
Keep this manual in a safe place in order to provide your
serviceman with necessary information.
NOTICE
NOTICE: To avoid equipment damage, do not leave the system
filled in a building without heat during cold weather, unless
adequate freeze protection levels of antifreeze are used. Heat
exchangers do not fully drain and will freeze unless protected,
causing permanent damage.
All TruClimate 100 products are tested in accordance to ISO
13256-2 Standard for Water-Cooled Water Chilling and Heat
Pump Water-Heating Packages.
IGT1-0014W
WARNING

Advertisement

loading
Need help?

Need help?

Do you have a question about the TruClimate 100 and is the answer not in the manual?

Questions and answers

Summary of Contents for WaterFurnace TruClimate 100

  • Page 1 Indicates a situation that could result in NOTICE equipment or property damage. All TruClimate 100 products are tested in accordance to ISO Conforms To UL STDS 60335-1 & 60335-2-40 13256-2 Standard for Water-Cooled Water Chilling and Heat Certified To CSA STDS C22.2 # 60335-1 & 60335-2-40...
  • Page 2 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP General Installation Information sources of ignition in such a manner that it may lead to the risk of NOTICE: Do not store or install units in corrosive environments or in locations subject to temperature or humidity extremes. fire or explosion.
  • Page 3 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP General Installation Information Installation Space Requirements WARNING Ventilated Area: ensure that the area is in the open or that it NOTE: Equipment with refrigerant charge less than 62 oz does is adequately ventilated before breaking into the system of not require have a minimum floor area requirement and does not conducting any hot work.
  • Page 4 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation WARNING meter Check that cabling will not be subject to wear, corrosion, excessive 1.00 1.00 pressure, vibration, sharp edges or any other adverse environmental 1312 1.00 effects.
  • Page 5 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation Equipment containing R-454B refrigerant shall be installed, Natural Ventilation operated, and stored in a room with fl oor area larger than the When the opening for connected rooms or natural ventilation area defi...
  • Page 6 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation nvmin Model Confi guration Horizontal Floor 26.2 440.9 41.0 Horizontal Floor +2 Ft 50.2 120.1 11.2 Horizontal Floor +4 Ft 74.2 55.0 Rack Installation The unit can be mounted in a rack to get it off of the fl oor. As you can see in table 1, as the mounting height of the unit goes up the A goes down.
  • Page 7 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation External Relay/Blower for Mitigation For applications in an ASHRAE 15 Room, wire these Alarm Connections to Room Mitigation System. Otherwise, field wire to External Relay/Blower for Mitigation.
  • Page 8 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Serial Plate Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min. distance to combustible surface (in/cm) Max. outlet air temperature (F/C) Unit Restrictions Max.
  • Page 9 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Dimensional Data 2/15/16 Electrical Knockouts Overall Cabinet Water Connections 1/2" 3/4" 3/4" cond cond cond Model Load Load Source Load Source Source Power Depth Height Width Liquid Liquid Liquid HWG In Water Water Water Liquid In Voltage...
  • Page 10 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Physical Data 024 Heating Model Compressor (1 each) Scroll Factory Charge R410a, oz [kg] 46.0 [1.30] 42.0 [1.19] 62 [1.76] 82 [2.32] Coax & Piping Water Volume - gal [l] .89 [3.38] .89 [3.38] 1.4 [5.25] 1.6 [6.13] Weight - Operating, lb [kg]...
  • Page 11 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Installation Information Safety Considerations WARNING: To avoid equipment damage, do not leave the system filled in a building without heat Installing and servicing air conditioning and heating during cold weather, unless adequate freeze equipment can be hazardous due to system pressure and protection levels of antifreeze are used.
  • Page 12 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Water Quality General The heat exchangers and water lines in the units are copper or cupronickel tube. There may be other materials in the Water-to-water heat pumps may be successfully applied in a building’s piping system that the designer may need to take wide range of residential and light commercial applications.
  • Page 13 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Field Connected Water Piping General The proper water flow must be delivered to each unit whenever the unit heats or cools. To assure proper flow, Each unit is equipped with captive FPT water connections the use of pressure/temperature ports is recommended to eliminate ‘egg-shaping’...
  • Page 14 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Field Connected Water Piping cont. Multiple Units on One Flow Center Earth Coupled Systems with Flow Center To connect multiple units on one fl ow center follow the wiring Once piping is completed between the unit, flow center diagram shown in Figure 2a.
  • Page 15 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Field Connected Water Piping cont. Open Loop Well Water Systems Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit. Use a closed bladder type expansion tank to minimize mineral deposits.
  • Page 16 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Potable Water Systems Hot Water Generator Connections The heat reclaiming hot water generator coil available on the 048-060 is vented double-wall copper construction and is suitable for potable water. To maximize the benefits of the hot water generator a minimum 50-gallon water heater is recommended. For higher demand applications, use an 80-gallon water heater as shown below or two 50-gallon water heaters connected in a series.
  • Page 17 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Potable Water Systems The 024 models can be equipped to provide domestic hot water generation. Alternate Hot Water Installation with Direct Coupling to a Double Wall Unit LOOP FIELD COLD Dielectric Unions FLOW CENTER 1-1/2˝...
  • Page 18 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Electrical Connections Control Box Run Capacitor Transformer Load Pump Power Block Compressor Contactor Source Pump Power Block Aurora Base Control Board (ABC) Aurora Sensor Board (ASB) 060 model only Electrical Data Compressor Unit Rated Voltage Load...
  • Page 19 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Electrical Connections cont. 208 Volt Operation Control Box Relocation All 208-230 volt units are factory wired for 230 volt The control box can be installed on the rear of the unit. To operation. To convert the unit from a 230V unit to a 208V unit relocate the control box, follow the procedures below.
  • Page 20 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Converting to Dedicated Cooling Unit Procedure to Convert a Heating Only Unit to a Cooling Only Unit All non-reversible units are built at the factory as dedicated heating units. Follow the procedures below to make the unit a dedicated cooling unit.
  • Page 21 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Reference Calculations Heating Calculations: Cooling Calculations: LWT = EWT - LWT = EWT + GPM x C* GPM x C* HE = C* x GPM x (EWT - LWT) HR = C* x GPM x (LWT - EWT) NOTE: * C = 500 for pure water, 485 for brine.
  • Page 22 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Unit Startup Before Powering Unit, Check the Following: NOTE: Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket. • High voltage wiring is correct and matches the nameplate.
  • Page 23 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Refrigerant Removal and Evacuation This process might need to be repeated several times. Com- When breaking into the refrigerant circuit to make repairs – or for any other purpose conventional procedures shall be used. pressed air or oxygen shall not be used for purging refriger- However, for flammable refrigerants it is important that best ant systems.
  • Page 24 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Refrigerant Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available.
  • Page 25 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Refrigeration Cycle Analysis Heating Cycle Analysis Cooling Cycle Analysis...
  • Page 26 INSTALLATION GUIDE: 2-5 TONS WATER-TO-WATER HEAT PUMP Notes...
  • Page 27 Revision Guide Pages: Description: Date: Document Creation 10 Oct 2024...
  • Page 28 2-5 Tons Document: Installation Guide IGT1-0014W 12/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifi cations without notice.
  • Page 29 Indique une situation qui pourrait AVIS endommager l’équipement ou la propriété. Tous les produits TruClimate 100 sont testés conformément à la norme Conforme aux normes UL 60335-1 et 60335-2-40 ISO 13256-2 pour les ensembles de refroidissement par eau et de Certifié conforme aux normes CSA C22.2 # 60335-1 et chauffage de l’eau par thermopompe.
  • Page 30 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Informations générales sur l’installation Toutes les sources d’inflammation possibles, y compris l’usage de la AVIS : N’installez pas les unités dans un environnement corrosif ou dans cigarette, doivent être maintenues suffisamment loin du site d’installation, des endroits soumis à...
  • Page 31 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Informations générales sur l’installation Espace d’installation requis AVERTISSEMENT Zone ventilée : Assurez-vous que la zone est à découvert ou REMARQUE : Le matériel dont la charge de réfrigérant est inférieure à qu’elle est correctement ventilée avant d’intervenir dans le 1,83 L (62 oz) n’exige pas une surface de plancher minimale et ne nécessite pas de capteur de détection de fuite de réfrigérant.
  • Page 32 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant AVERTISSEMENT alte Assurez-vous que le câblage ne sera pas soumis à l’usure, à la corrosion, 1,00 à une pression excessive, à des vibrations, à des bords tranchants ou à 1,00 1 312 1,00...
  • Page 33 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Le matériel contenant du réfrigérant R-454B doit être installé, utilisé et Ventilation naturelle entreposé dans une salle dont la surface de plancher est plus grande Si l’ouverture des locaux raccordés ou la ventilation naturelle est que la surface défi...
  • Page 34 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant nvmin Modèle Confi guration Plancher horizontal 26,2 440,9 41,0 Plancher horizontal + 50,2 120,1 11,2 0,6 m (2 pi) Plancher horizontal + 74,2 55,0 1,3 m (4 pi)
  • Page 35 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant External Relay/Blower for Mitigation For applications in an ASHRAE 15 Room, wire these Alarm Connections to Room Mitigation System. Otherwise, field wire to External Relay/Blower for Mitigation.
  • Page 36 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Plaque signalétique Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min. distance to combustible surface (in/cm) Max.
  • Page 37 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Données dimensionnelles 2/15/16 Electrical Knockouts Overall Cabinet Water Connections 1/2" 3/4" 3/4" cond cond cond Model Load Load Source Load Source Source Power Depth Height Width Liquid Liquid Liquid HWG In Water Water Water...
  • Page 38 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Données physiques 024 Chauff age Modèle Compresseur (1 chacun) Spirale Charge d’usine R410a, kg (oz) 1,30 (46,0) 1,19 (42,0) 1,76 (62) 2,32 (82) Volume d’eau de la tuyauterie coaxiale 3,38 (0,89) 3,38 (0,89) 5,25 (1,4) 6,13 (1,6) et de la tuyauterie –...
  • Page 39 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Information sur l’installation Considérations de sécurité AVERTISSEMENT : Pour éviter d’endommager l’équipement, ne laissez pas le système rempli dans L’installation et l’entretien des appareils de climatisation et de un bâtiment sans chauffage par temps froid, à moins chauffage peuvent être dangereux en raison de la pression du de prévoir des niveaux d’antigel adéquats pour la système et des composants électriques.
  • Page 40 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Qualité de l’eau Les échangeurs de chaleur et les conduites d’eau des unités sont en Généralités cuivre ou en cupronickel. Il pourrait y avoir d’autres matériaux dans Les thermopompes eau-eau peuvent être utilisées avec succès le système de tuyauterie du bâtiment que le concepteur devrait dans un large éventail d’applications résidentielles et commerciales peut-être prendre en considération pour décider des paramètres...
  • Page 41 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Tuyauterie d’eau raccordée sur place Le bon débit d’eau doit être acheminé à chaque unité chaque Généralités fois qu’elle chauffe ou refroidit. Pour assurer un débit adéquat, Chaque unité est équipée de raccords d’eau FPT captif pour on recommande l’utilisation des orifices de pression et de éliminer la « formation d’œufs »...
  • Page 42 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Tuyauterie d’eau raccordée sur place (suite) Plusieurs unités sur un seul centre de débit Systèmes reliés à la terre avec centre de débit Pour raccorder plusieurs unités sur un seul centre de débit, suivez le schéma de câblage indiqué...
  • Page 43 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Tuyauterie d’eau raccordée sur place (suite) Systèmes d’eau de puits en boucle ouverte Maintenez toujours la pression d’eau dans l’échangeur de chaleur en plaçant les valves de régulation d’eau à la sortie de l’unité. Utilisez un vase d’expansion de type vessie fermé...
  • Page 44 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Réseaux d’eau potable Raccords du générateur d’eau chaude Le serpentin du générateur d’eau chaude récupérant la chaleur offert sur 048-060 est fait de cuivre à double paroi ventilé et convient à l’eau potable. Pour optimiser les avantages du générateur d’eau chaude, un chauffe-eau d’au moins 189,3 L (50 gal) est recommandé.
  • Page 45 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Réseaux d’eau potable Les modèles 024 peuvent être équipés pour fournir une production d’eau chaude domestique. Installation d’option à l’eau chaude avec couplage direct à une unité à double paroi LOOP FIELD COLD Dielectric Unions...
  • Page 46 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Raccords électriques Boîtier de commande Condensateur de marche Transformateur Bloc d’alimentation de la pompe de charge Contacteur de Bloc d’alimentation de la compresseur pompe de source Panneau de commande de base Aurora (ABC) Carte de capteur Aurora (ASB) Modèle 060 seulement Données électriques...
  • Page 47 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Raccords électriques Fonctionnement de 208 V Déplacement du boîtier de commande Toutes les unités de 208 à 230 V sont câblées en usine pour un Le boîtier de commande peut être installé à l’arrière de l’unité. Pour fonctionnement à...
  • Page 48 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Conversion en unité de refroidissement spécialisée Procédure pour convertir une unité de chauffage seulement en unité de refroidissement seulement Toutes les unités non réversibles sont construites en usine comme unités de chauffage dédiées. Suivez les procédures ci-dessous pour convertir l’unité...
  • Page 49 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Calculs de référence Calculs de chauff age : Calculs de refroidissement : LWT = EWT - LWT = EWT + GPM x C* GPM x C* HE = C* x GPM x (EWT - LWT) HR = C* x GPM x (LWT - EWT) REMARQUE : * C = 500 pour l’eau pure, 485 pour la saumure.
  • Page 50 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Démarrage de l’unité Avant d’alimenter l’appareil, vérifier ce qui suit : REMARQUE : Enlevez et jetez le boulon d’expédition de fixation de compresseur situé à l’avant du support de fixation du compresseur. •...
  • Page 51 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Retrait et évacuation du réfrigérant Lorsque vous ouvrez le circuit frigorifique pour effectuer des répa- Ce processus devra peut-être être répété plusieurs fois. L’air rations, ou pour toute autre fin, vous devez suivre les procédures comprimé...
  • Page 52 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Récupération du réfrigérant Lors du retrait du réfrigérant d’un système, que ce soit pour l’entretien ou la mise hors service, il est recommandé de retirer tous les réfrigérants en toute sécurité. Lors du transfert du réfrigérant dans des bouteilles, assurez-vous que seules des bouteilles appropriées de récupération de réfrigérant sont utilisées.
  • Page 53 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Analyse du cycle de réfrigération Analyse du cycle de chauff age Analyse du cycle...
  • Page 54 GUIDE D’INSTALLATION THERMOPOMPE EAU-EAU DE 2 À 5 TONNES Notes...
  • Page 55 Guide de révision Pages Description Date Toutes Création de document 10 oct. 2024...
  • Page 56 12/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. La politique de WaterFurnace en matière de recherche et de développement de produits est continue; elle se réserve le droit de modifi er la conception et les spécifi cations sans préavis.