WaterFurnace TruClimate 100 Installation Manual

WaterFurnace TruClimate 100 Installation Manual

R-454b 60hz potable hot water heat pump
Hide thumbs Also See for TruClimate 100:

Advertisement

Available languages

Available languages

Quick Links

INSTALLATION GUIDE
TruClimate 100
R-454B
60Hz
Potable Hot Water Heat Pump
General Installation Information ................................................................................................ 2
Refrigeration Detection and Mitigation ................................................................................. 4
Serial Plate ......................................................................................................................................... 8
Dimensional Data ............................................................................................................................ 9
Physical Data .................................................................................................................................... 10
Electrical Data .................................................................................................................................. 11
Installation ......................................................................................................................................... 12
Water Connections & Water Quality ....................................................................................... 15
Field Wiring and Control Setup ................................................................................................ 17
Reference Calculations, Legend, Unit Startup ..................................................................... 19
Refrigerant Removal and Evacuation ..................................................................................... 20
Charging Procedures ..................................................................................................................... 20
Refrigerant Recovery..................................................................................................................... 21
Refrigeration Cycle Analysis ....................................................................................................... 22
Revision Guide ................................................................................................................................. 24
WARNING: Before performing service or maintenance
operations on the system, turn off main power switches
to the unit. Electrical shock could cause serious personal
injury.
WARNING: All WaterFurnace products are designed,
tested, and manufactured to comply with the latest
publicly released and available edition of UL 60335-2-
40 for electrical safety certification. All field electrical
connections must follow the National Electrical Code
(NEC) guide standards and / or any local codes that may
be applicable for the installation.
WARNING: Only factory authorized personnel are
approved for startup, check test and commissioning of
this unit.
INSTALLER: Please take the time to read and understand
these instructions prior to any installation. Installer must
give a copy of this manual to the owner.
Definition of Warnings and Symbols
DANGER
W
WARNING
CAUTION
NOTICE
Conforms To UL STDS 60335-1 & 60335-2-40
Certified To CSA STDS C22.2 # 60335-1 & 60335-2-40
WARNING
Indicates a situation that results in death or
serious injury.
Indicates a situation that could result in
death or serious injury.
Indicates a situation that could result in
minor or moderate injury.
Indicates a situation that could result in
equipment or property damage.
For the User
This appliance is not intended for use by persons (including
children) with reduced physical, sensory, or mental capabilities,
or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play
with the appliance.
Keep this manual in a safe place in order to provide your
serviceman with necessary information.
NOTICE
NOTICE: To avoid equipment damage, do not leave the system
filled in a building without heat during cold weather, unless
adequate freeze protection levels of antifreeze are used. Heat
exchangers do not fully drain and will freeze unless protected,
causing permanent damage.
All TruClimate 100 products are tested in accordance to
ISO 13256-2 Standard for Water-Cooled Water Chilling
and Heat Pump Water-Heating Packages.
IGT1-0028W
WARNING

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TruClimate 100 and is the answer not in the manual?

Questions and answers

Summary of Contents for WaterFurnace TruClimate 100

  • Page 1: Table Of Contents

    Indicates a situation that could result in NOTICE equipment or property damage. All TruClimate 100 products are tested in accordance to Conforms To UL STDS 60335-1 & 60335-2-40 ISO 13256-2 Standard for Water-Cooled Water Chilling Certified To CSA STDS C22.2 # 60335-1 & 60335-2-40...
  • Page 2: General Installation Information

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP General Installation Information NOTICE: Do not store or install units in corrosive environments No person carrying out work in relation to a REFRIGERATING SYSTEM which involves exposing any pipe work shall use any or in locations subject to temperature or humidity extremes.
  • Page 3 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP General Installation Information Installation Space Requirements WARNING Ventilated Area: ensure that the area is in the open or that it NOTE: Equipment with refrigerant charge less than 64 oz does is adequately ventilated before breaking into the system of not require have a minimum floor area requirement and does not conducting any hot work.
  • Page 4 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation Example: For instance, if your elevation is 5249Ft (1500mm) WARNING your area factor would be 1.12.  If your charge weight is 80oz (2.268 kg) at a floor height installation.  The Amin would be Check that cabling will not be subject to wear, corrosion, excessive 516 square Ft (48.0 square meters). ...
  • Page 5 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation Exhaust Area Charge Amin Area (A1) Ventilation (Qmin) (EAmin) Model ft^3/min m^3/hr T1DM120SN2 4.75 2.15 10.3 11.0 T1DM180SN2 5.00 2.27 12.6 11.2 T1DM240SN2 6.00 2.72 11.8 13.6 T1DM360S*2 8.00...
  • Page 6 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation External Relay/Blower for Mitigation For applications in an ASHRAE 15 Room, wire these Alarm Connections to Room Mitigation System. Otherwise, field wire to External Relay/Blower for Mitigation.
  • Page 7 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP General Installation Information: Refrigerant Detection and Mitigation Natural Ventilation to the Outdoors or Adjacent Indoor Space Nature ventilation can be achieved by ensuring that there is a connected space to the room housing the equipment. There must be a permanent opening between the spaces.
  • Page 8: Serial Plate

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Serial Plate Unit Nomenclature and Serial Number Unit Voltage Fuse/Breaker Size Component Electrical Information Min. distance to combustible surface (in/cm) Max. outlet air temperature )F/C) Unit Restrictions Max. external static pressure (in water/Pa) Max.
  • Page 9: Dimensional Data

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Dimensional Data: Potable Water Option Dimensional Data for unit with enclosure Model 57.3 24.1 42.5 13.0 11.9 15.4 11.9 120-180 [1455] [612] [1080] [157] [330] [302] [391] [302] [117] 64.2 24.1 50.5 13.0 18.1 15.4 12.1...
  • Page 10: Physical Data

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Physical Data Model Domestic Hot Water Heat Pump Refrigerant R-454B Number of Circuits Factory Charge, lbs [kg]* 4.75 [2.15] 5.00 [2.27] 6.00 [2.72] 8.00 [3.63] Compressor Compressor Quantity [tons] 2 [35] 2 [40] 2 [10] 2 [15] Compressor Weight, lbs [kg] (each)
  • Page 11: Electrical Data

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Electrical Data Total Compressor Rated Voltage Model Unit Circ Fuse/ Fuse/ Voltage Min/Max HACR HACR 208-230/60/3 187/253 36.0 23.1 160.0 46.2 52.0 60.0 460/60/3 414/506 19.0 12.2 87.0 24.4 27.5 30.0 575/60/3 517/633 13.5 62.0 17.4...
  • Page 12: Installation

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Installation Information Safety Considerations Unit Location Installing and servicing air conditioning and heating Provide sufficient room to make water and electrical equipment can be hazardous due to system pressure and connections. If the unit is located in a confined space, electrical components.
  • Page 13 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Installation Information Mounting Units Remove the unit from the wooden shipping skids (see physical dimensions). Units do not ship standard with vibration isolation hardware, however, non-standard options are selectable for the unit. Non-standard options include: •...
  • Page 14 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Installation Information - Field Connected Water Piping General NOTE: The placement and connection of the water circulating pump(s) must be taken into consideration prior System piping should be kept as simple as possible to to designing the final water piping systems.
  • Page 15 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Water Quality 1.0. Minimum Fluid Volume 1.4. Flow Sensing Devices Water-to-water heat pumps require a minimum amount A fl ow switch or equivalent must be installed on the of source and load side fl uid volume to ensure accurate evaporator for each unit to be installed.
  • Page 16 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Water Quality cont. 1.6. Insulation 1.7. Brine Applications Heat pumps are built with factory installed insulation Applications where the leaving fl uid temperature goes on any surface that may be subject to temperatures below 40°F a suitable brine solution must be used.
  • Page 17: Field Wiring And Control Setup

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Field Wiring and Control Setup Line Voltage Pump Control Power supply wiring connects directly to lugs on the top Slow Opening Valve Wiring of the electrical disconnect. In 208-230V applications, heat pumps are factory wired for 208V supply. In the case of The accessory output on either one of the ABC Aurora 230V supply, the blue and red wires from the primary of the boards can be used to control either a slow opening valve...
  • Page 18 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Field Wiring and Control Setup cont. Flow Switch Operation Slow Opening Valve Wiring cont. Slow Source Flow Switch (SFS) Unit is factory shipped with no connections on Flow Switch wires from HA1 off AXB-A (entering). If flow proving switch is required, hook up as shown in the figure and Note 1.
  • Page 19 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Reference Calculations Heating Calculations: Cooling Calculations: LWT = EWT - LWT = EWT + GPM x 500* GPM x 500* NOTE: * When using water. Use 485 for 15% methanol/water or Environol solution. Legend Abbreviations and Definitions = entering load fluid temperature to heat pump...
  • Page 20: Refrigerant Removal And Evacuation

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Refrigerant Removal and Evacuation When breaking into the refrigerant circuit to make repairs – or This process might need to be repeated several times. Com- for any other purpose conventional procedures shall be used. pressed air or oxygen shall not be used for purging refriger- However, for flammable refrigerants it is important that best ant systems.
  • Page 21: Refrigerant Recovery

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Refrigerant Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available.
  • Page 22: Refrigeration Cycle Analysis

    INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Refrigeration Cycle Analysis PSIG = Condenser Discharge Filter Suction Drier Compressor Evaporator PSIG = Unit Amp Draw Entering Hot Water Line Voltage Entering Water Pressure PSIG Subcooling Leaving Hot Water Superheat Leaving Water Pressure PSIG Entering Chilled Water Entering Water Pressure...
  • Page 23 INSTALLATION GUIDE: POTABLE HOT WATER HEAT PUMP Notes...
  • Page 24: Revision Guide

    10-30 Tons Document: Installation Manual IGT1-0028W 05/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifi cations without notice.
  • Page 25 à moins que celles-ci ne bénéficient d’une surveillance AVERTISSEMENT : Tous les produits WaterFurnace sont ou d’instructions concernant l’utilisation de l’appareil de la part conçus, testés et fabriqués dans le respect de l’édition la plus d’une personne responsable chargée de veiller à...
  • Page 26: Informations Générales Sur L'installation

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Informations générales sur l’installation AVIS : Ne pas installer les unités dans un environnement corrosif Si des travaux à chaud doivent être effectués sur le matériel de ou dans des endroits soumis à des températures extrêmes ou à réfrigération ou toute pièce associée, un matériel d’extinction d’incendie approprié...
  • Page 27 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Informations générales sur l’installation Espace d’installation requis AVERTISSEMENT REMARQUE : Le matériel dont la charge de réfrigérant est inférieure Zone ventilée : assurez-vous que la zone est à découvert ou qu’elle à 64 oz n’exige pas une surface de plancher minimale et ne nécessite est correctement ventilée avant d’intervenir dans le système ou de pas de capteur de détection de fuite de réfrigérant.
  • Page 28: Détection Et Atténuation Des Fuites De Réfrigérant

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Exemple : si votre altitude est de 1500 m (5249 pi) votre facteur AVERTISSEMENT de zone serait 1,12. Si le poids de votre charge est de 2,268 kg (80 oz) à...
  • Page 29 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Section de sortie Charge Smin Surface (A1) Ventilation (Qmin) (SSmin) Modèle pi^3/min m^3/hr T1DM120SN2 4,75 2,15 10,3 11,0 T1DM180SN2 5,00 2,27 12,6 11,2 T1DM240SN2...
  • Page 30 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Relais externe/ventilateur soufflant pour l’atténuation Pour les applications dans une salle ASHRAE 15, câblez ces raccords d’alarme au système d’atténuation de la salle. Sinon, câblez sur place le relais externe/ventilateur soufflant pour...
  • Page 31 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Informations générales sur l’installation : Détection et atténuation des fuites de réfrigérant Ventilation naturelle vers l’extérieur ou l’espace intérieur adjacent La ventilation naturelle peut être obtenue en veillant à ce qu’il y ait un espace connecté à la salle abritant le matériel. Il doit y avoir une ouverture permanente entre les espaces.
  • Page 32: Plaque Signalétique

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Plaque signalétique Unit Nomenclature and Serial Number Unit Voltage Fuse/Breaker Size Component Electrical Information Min. distance to combustible surface (in/cm) Max. outlet air temperature )F/C) Unit Restrictions Max. external static pressure (in water/Pa) Max.
  • Page 33: Données Dimensionnelles

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Données dimensionnelles : Option d’eau potable Données dimensionnelles pour l’unité avec enceinte Modèle 57,3 24,1 42,5 13,0 11,9 15,4 11,9 120-180 [1455] [612] [1080] [157] [330] [302] [391] [302] [117] 64,2 24,1 50,5 13,0 18,1 15,4 12,1...
  • Page 34: Données Physiques

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Données physiques Modèle Thermopompe à eau chaude domestique R-454B Réfrigérant Nombre de circuits Charge d’usine, lb [kg]* 4,75 [2.15] 5,00 [2,27] 6,00 [2,72] 8,00 [3.63] Compresseur Volume du compresseur [tonnes] 2 [35] 2 [40] 2 [10] 2 [15] Poids du compresseur, lb [kg] (chaque)
  • Page 35: Données Électriques

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Données électriques Compresseur Total Min. Min. Max. Tension Tension Modèle de l’unité Circ fusible/ fusible/ nominale min/max HACR HACR 208-230/60/3 187/253 36,0 23,1 160,0 46,2 52,0 60,0 460/60/3 414/506 19,0 12,2 87,0 24,4 27,5 30,0 575/60/3...
  • Page 36: Installation

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Information sur l’installation Considérations de sécurité Emplacement de l’unité Prévoyez un espace suffisamment grand pour effectuer les L’installation et l’entretien des appareils de climatisation et de raccords d’eau et d’électricité. Si l’unité est placée dans un chauffage peuvent être dangereux en raison de la pression espace exigu, des dispositions doivent être prises pour les du système et des composants électriques.
  • Page 37 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Information sur l’installation Montage des unités Retirez l’unité des palettes d’expédition en bois (voir les dimensions physiques). Les unités ne sont pas livrées de série avec du matériel d’isolation des vibrations, mais des options non standard peuvent être sélectionnées pour l’unité. Les options non standard comprennent : •...
  • Page 38 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Informations sur l’installation – Tuyauterie d’eau raccordée sur place Généralités REMARQUE : L’emplacement et le raccordement des pompes de circulation d’eau doivent être pris en compte avant de La tuyauterie du système devrait être aussi simple que possible concevoir les systèmes de tuyauterie d’eau finaux.
  • Page 39 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Qualité de l’eau 1.0 Volume minimal de liquide 1.4 Dispositifs de détection de débit Les thermopompes eau-eau exigent une quantité minimale Un régulateur de circulation d’eau ou l’équivalent doit être de liquide du côté source et du côté charge pour assurer des installé...
  • Page 40 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Qualité de l’eau (suite) 1.6 Isolant 1.7 Application de saumure Les thermopompes sont construites avec un isolant Pour les applications où la température du liquide de installé en usine sur toute surface qui peut être soumise à départ est inférieure à...
  • Page 41: Câblage Sur Place Et Configuration Des Commandes

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Câblage sur place et configuration des commandes Tension composée Commande de pompe Le câblage d’alimentation électrique est raccordé directement Câblage de robinet à ouverture lente aux cosses sur le dessus du disjoncteur. Dans les applications de 208-230 V, les thermopompes sont câblées en usine pour une La sortie accessoire sur l’une ou l’autre des cartes ABC Aurora alimentation de 208 V.
  • Page 42 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Câblage sur place et configuration des commandes (suite) Fonctionnement du régulateur de Câblage de robinet à ouverture lente (suite) Câ Câ Câbl blag circulation d’eau Régulateur de circulation d’eau de la source (RCES) L’unité...
  • Page 43 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Calculs de référence Calculs de chauffage : Calculs de refroidissement : LWT = EWT - LWT = EWT + GPM x 500* GPM x 500* REMARQUE : * lorsque vous utilisez de l’eau, utilisez 485 pour 15 % de méthanol/eau ou de solution Environol. Légende Abréviations et définitions = entering load fluid temperature to heat pump (tmpérature du...
  • Page 44: Retrait Et Évacuation Du Réfrigérant

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Retrait et évacuation du réfrigérant Lorsque vous ouvrez le circuit frigorifique pour effectuer des Ce processus devra peut-être être répété plusieurs fois. L’air réparations, ou pour toute autre fin, vous devez suivre les comprimé...
  • Page 45: Récupération Du Réfrigérant

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Récupération du réfrigérant Lors du retrait du réfrigérant d’un système, que ce soit pour l’entretien ou la mise hors service, il est recommandé de retirer tous les réfrigérants en toute sécurité. Lors du transfert du réfrigérant dans des bouteilles, assurez- vous que seules des bouteilles appropriées de récupération de réfrigérant sont utilisées.
  • Page 46: Analyse Du Cycle De Réfrigération

    MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Analyse du cycle de réfrigération PSIG = Condenseur Décharge Déshydra- Aspiration teur-filtre Compresseur Évaporateur PSIG = Ampérage de l’unité Entrée eau chaude Pression de l’eau à l’entrée PSIG Tension composée Sous-refroidissement Sortie eau chaude Sortie pression à...
  • Page 47 MANUEL D’INSTALLATION THERMOPOMPE À EAU CHAUDE POTABLE Notes...
  • Page 48: Guide De Révision

    IGT1-0028W  05/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. La politique de WaterFurnace en matière de recherche et de développement de produits est continue; elle se réserve le droit de modifi er la conception et les spécifi cations sans préavis.

Table of Contents