INSTALLATION GUIDE
5 Series 3D
/
R-454B
60Hz
General Installation Information ................................................................................................ 2
Nomenclature ................................................................................................................................... 6
Water Quality ................................................................................................................................... 10
Hot Water Generator Connections .......................................................................................... 11
Buffer Tank Installation ................................................................................................................. 11
Hydronic ............................................................................................................................................. 12
Electrical Connections .................................................................................................................. 14
Electronic Thermostat Installation ........................................................................................... 15
Blower Data ....................................................................................................................................... 16
Dimensional Data ............................................................................................................................ 17
Physical Data .................................................................................................................................... 18
Reference Calculations ................................................................................................................. 18
Operating Limits.............................................................................................................................. 18
Refrigerant Removal & Evacuation .......................................................................................... 19
Charging Procedures ..................................................................................................................... 19
Refrigerant Recovery..................................................................................................................... 20
Unit Startup ....................................................................................................................................... 21
Revision Guide ................................................................................................................................. 25
WARNING: Before performing service or maintenance
operations on the system, turn off main power switches
to the unit. Electrical shock could cause serious personal
injury.
WARNING: All products are designed, tested, and
manufactured to comply with the latest publicly released
and available edition of UL 60335-2-40 for electrical
safety certification. All field electrical connections must
follow the National Electrical Code (NEC) guide standards
and / or any local codes that may be applicable for the
installation.
WARNING: Only factory authorized personnel are
approved for startup, check test and commissioning of
this unit.
INSTALLER: Please take the time to read and understand
these instructions prior to any installation. Installer must
give a copy of this manual to the owner.
Definition of Warnings and Symbols
DANGER
WARNING
CAUTION
NOTICE
WARNING
Indicates a situation that results in death or
serious injury.
Indicates a situation that could result in
death or serious injury.
Indicates a situation that could result in
minor or moderate injury.
Indicates a situation that could result in
equipment or property damage.
For the User
This appliance is not intended for use by persons (including
children) with reduced physical, sensory, or mental capabilities,
or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play
with the appliance.
Keep this manual in a safe place in order to provide your
service personnel with necessary information.
NOTICE
NOTICE: To avoid equipment damage, do not leave the system
filled in a building without heat during cold weather, unless
adequate freeze protection levels of antifreeze are used. Heat
exchangers do not fully drain and will freeze unless protected,
causing permanent damage.
IGW5-0017W
WARNING

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 5 Series 3D 036 and is the answer not in the manual?

Questions and answers

Summary of Contents for WaterFurnace 5 Series 3D 036

  • Page 1: Table Of Contents

    INSTALLATION GUIDE 5 Series 3D R-454B 60Hz IGW5-0017W General Installation Information ....................2 Nomenclature ........................... 6 Water Quality ........................... 10 Hot Water Generator Connections ..................11 Buffer Tank Installation ......................... 11 Hydronic ............................. 12 Electrical Connections ........................14 Electronic Thermostat Installation ................... 15 Blower Data ............................
  • Page 2: General Installation Information

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE General Installation Information NOTICE: Do not store or install units in corrosive environments No person carrying out work in relation to a REFRIGERATING SYSTEM which involves exposing any pipe work shall use any or in locations subject to temperature or humidity extremes.
  • Page 3: Installation Space Requirements

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE General Installation Information Installation Space Requirements WARNING NOTE: Equipment with refrigerant charge less than 62 oz does Ventilated Area: ensure that the area is in the open or that it is adequately ventilated before breaking into the system of not require have a minimum floor area requirement and does not conducting any hot work.
  • Page 4 GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE General Installation Information WARNING meter Check that cabling will not be subject to wear, corrosion, excessive 1.00 pressure, vibration, sharp edges or any other adverse environmental 1.00 1312 1.00 effects.
  • Page 5 GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE General Installation Information If H is greater than or equal to 7.22 FT (2.2 M), use Table Value 7.22 FT (2.2 M) If H is under 23.6 IN (0.6 M), use Table Value 23.6 IN (0.6 M) If H is between these values,...
  • Page 6: Nomenclature

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE General Installation Information Model Nomenclature Brand Brand IntelliStart W – WaterFurnace W – WaterFurnace 0 – None 1 – Yes Model Model 5 – 5 Series 5 – 5 Series Mitigation 1 –...
  • Page 7: Serial Plate - Example

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Serial Plate - Example Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min. distance to combustible surface (in/cm) Max.
  • Page 8 GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE General Installation Information Installing Vertical Units NOTICE Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket.
  • Page 9: Duct System

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE General Installation Information cont. Tighten the connectors by hand and then gently snug Duct System the fitting with pliers to provide a leak proof joint. When An air outlet collar is provided on vertical top flow units connecting to an open loop (ground water) system, thread to facilitate a duct connection, which is shipped inside the 1 in.
  • Page 10: Water Quality

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Water Quality Material Copper 90/10 Cupronickel 316 Stainless Steel Acidity/Alkalinity 7 - 9 7 - 9 7 - 9 Calcium and (Total Hardness) (Total Hardness) (Total Hardness) Scaling Magnesium Carbonate less than 350 ppm less than 350 ppm...
  • Page 11: Hot Water Generator Connections

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Hot Water Generator Connections adaptor and temperature limit switch. Be sure to burp the To maximize the benefits of the hot water generator a pump. Open the screw 2 turns only in the end of the pump minimum 50-gallon water heater is recommended.
  • Page 12: Hydronic Section

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Hydronic Section General guidelines are shown below for component selection restriction in the screen, the system could go to 0 psi (0 and design/installation criteria for the piping system. Local kPa), potentially causing pumps(s) failure.
  • Page 13 GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Hydronic Section cont. Adequate rate of flow (GPM) is very important to Geothermal Storage Tank Thermostat system performance and long term reliability. Follow the guidelines for recommended flow and pipe sizing in the recommendations table.
  • Page 14: Electrical Connections

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Electrical Connections General Accessory Relay Be sure the available power is the same voltage and phase A set of “dry” contacts has been provided to control as that shown on the unit serial plate. Line and low voltage accessory devices, such as water solenoid valves on open wiring must be done in accordance with local codes or the loop installations, electronic air cleaners, humidifiers, etc.
  • Page 15: Electronic Thermostat Installation

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Electronic Thermostat Installation Position the thermostat subbase against the wall so that Figure 22: Thermostat Wiring (Communicating Style Signals) it is level and the thermostat wires protrude through the middle of the subbase.
  • Page 16: Blower Data

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Blower Performance Data Setting Blower Speed - Variable Speed Selecting YES will enter ECM speed setup, while selecting NO will return to the previous screen. The ABC board’s Yellow Config LED will flash the current ECM Speed Setup - These screens allow the technician to ECM blower speed selections for “G”, low, and high continuously with a short pause in between.
  • Page 17: Dimensional Data

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Vertical Dimensional Data Topflow Discharge LEFT RETURN RIGHT RETURN LEFT FRONT FRONT RIGHT Electrical Connections Overall Cabinet Water Connections Vertical Topfl ow 1/2" cond 1/2" cond 3/4" cond Loop Hydronic Model...
  • Page 18: Physical Data

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Physical Data Model Copeland Scroll Compressor (1 each) Factory Charge R-454B, oz [kg] 62 [1.75] 76 [2.15] 98 [2.77] 98 [2.77] ECM Fan Motor & Blower Fan Motor Type/Speeds ECM Variable Speed Fan Motor- hp [W] 1/2 [373]...
  • Page 19: Refrigerant Removal & Evacuation

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Refrigerant Removal and Evacuation When breaking into the refrigerant circuit to make repairs – or This process might need to be repeated several times. Com- for any other purpose conventional procedures shall be used. pressed air or oxygen shall not be used for purging refriger- However, for flammable refrigerants it is important that best ant systems.
  • Page 20: Refrigerant Recovery

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Refrigerant Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
  • Page 21: Unit Startup

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Unit Startup It is highly recommended the installing/ the HW switch on the front cabinet) servicing contractor obtain an Aurora ii. DHW Setpoint – 130 °F is the default Interface and Diagnostic Tool (AID) and but can be changed from 100 to 140 °F specialized training before attempting...
  • Page 22 GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Unit Startup cont. Configuring the Sensor Kits f. Energy monitoring can be read on any of the following components: Configuring the Sensor kits i. AID Tool – instantaneous information only The Aurora Advanced Control allows Refrigeration, Energy, ii.
  • Page 23 GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Unit Startup cont. ii. Then set the VS Pump Min % to achieve 15. Adjust the heating setpoint below room temperature at least 2.5 gpm per ton for part load and verify that the compressor and water valve or loop operation.
  • Page 24 GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Notes...
  • Page 25: Revision Guide

    GEOTHERMAL HEAT PUMP WITH WATER HEATING FOR RADIANT FLOOR APPLICATIONS INSTALLATION GUIDE Revision Guide Pages: Description: Date: Document Creation 21 July 2023...
  • Page 26 3-6 Ton Dual Capacity Document: Installation Guide *IGW5-0017W* IGW5-0017W 10/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifi cations without notice.
  • Page 27: Manuel D'installation

    MANUEL D’INSTALLATION 5 Series 3D R-454B 60 Hz IGW5-0017W Informations générales sur l’installation ..................2 Nomenclature ............................6 Qualité de l’eau ............................10 Raccords du générateur d’eau chaude .................... 11 Installation du réservoir tampon ......................11 Hydronique ..............................12 Raccords électriques ..........................14 Installation du thermostat électronique ..................
  • Page 28: Informations Générales Sur L'installation

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Informations générales sur l’installation AVIS : N'installez pas les unités dans un environnement corrosif Si des travaux à chaud doivent être effectués sur le matériel de réfrigération ou toute pièce associée, un matériel d’extinction ou dans des endroits soumis à...
  • Page 29: Site D'installation

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Informations générales sur l’installation Espace d’installation requis AVERTISSEMENT REMARQUE : Le matériel dont la charge de réfrigérant est inférieure Zone ventilée : Assurez-vous que la zone est à découvert ou qu’elle à...
  • Page 30 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Informations générales sur l’installation AVERTISSEMENT alte Assurez-vous que le câblage ne sera pas soumis à l’usure, à la corrosion, 1,00 à une pression excessive, à des vibrations, à des bords tranchants ou à 1,00 tout autre effet nocif de l’environnement.
  • Page 31 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Informations générales sur l’installation Si H est supérieur ou égal à 2,2 m (7,22 pi), utilisez la valeur du tableau 2,2 m (7,22 pi). Si H est inférieur à...
  • Page 32: Nomenclature

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Informations générales sur l’installation Nomenclature du modèle Brand Brand IntelliStart W – WaterFurnace W – WaterFurnace 0 – None 1 – Yes Model Model 5 –...
  • Page 33 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Plaque signalétique – exemple Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min.
  • Page 34 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Informations générales sur l’installation Installation d’unités verticales AVIS Avant de mettre l’appareil en place, retirez et jetez le boulon de fixation du compresseur situé à l’avant du support de fixation du compresseur.
  • Page 35 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Informations générales sur l’installation (suite) Pour effectuer la connexion à un système de boucle de sol, Système de conduits attachez le connecteur en laiton (fourni dans les trousses de Un collier de sortie d’air est fourni sur les appareils à...
  • Page 36: Qualité De L'eau

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Qualité de l’eau Matériel Cuivre 90/10 Cupronickel Acier inoxydable 316 Acidité/Alcalinité 7 - 9 7 - 9 7 - 9 Calcium et carbonate (Dureté totale) (Dureté...
  • Page 37: Raccords Du Générateur D'eau Chaude

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Raccords du générateur d’eau chaude générateur d’eau chaude. La trousse DPK5 est fourni avec des Pour optimiser les avantages du générateur d’eau chaude, instructions d’installation, un circulateur, un adaptateur de un chauffe-eau d’au moins 189,27 L (50 gal) est recommandé.
  • Page 38 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Section hydronique Des directives générales sont présentées ci-dessous pour système. Certains sont munis de tamis, qui doivent être nettoyés la sélection des composants et les critères de conception après le remplissage initial.
  • Page 39 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Section hydronique (suite) Un débit adéquat (L/min [gal/min]) est très important pour le Thermostat du réservoir de stockage géothermique rendement du système et la fiabilité à long terme. Respectez les directives sur le débit et la taille des tuyaux recommandés dans le tableau des recommandations.
  • Page 40: Raccords Électriques

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Raccords électriques Généralités Relais d’accessoires Assurez-vous que l’alimentation disponible correspond au même Un ensemble de contacts « secs » a été fourni pour commander voltage et à la même phase que celles indiquées sur la plaque les dispositifs accessoires, comme les électrovannes d’eau sur les de série de l’appareil.
  • Page 41: Installation Du Thermostat Électronique

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Installation du thermostat électronique Placez la sous-base du thermostat contre le mur de façon à ce Figure 22 : Câblage du thermostat (signaux de communication) qu’elle soit de niveau et que les fils du thermostat dépassent au milieu de la sous-base.
  • Page 42 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Données sur le rendement du ventilateur Réglage de la vitesse du ventilateur – Si vous sélectionnez OUI, la configuration de la vitesse du moteur ECM s’ouvrira, tandis que si vous sélectionnez NON, ECM à...
  • Page 43: Données Dimensionnelles

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Données dimensionnelles verticales Décharge à débit supérieur LEFT RETURN RIGHT RETURN LEFT FRONT FRONT RIGHT Raccords électriques Ensemble de l’armoire Raccords d’eau Modèle Condensateur Condensateur Condensateur vertical...
  • Page 44: Données Physiques

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Données physiques Modèle Copeland Scroll Compresseur (1 chacun) Charge d’usine R-454B, kg (oz) 1,75 (62) 2,15 (76) 2,77 (98) 2,77 (98) Moteur du ventilateur ECM et ventilateur Type/vitesses du moteur du ventilateur Vitesse variable ECM Moteur du ventilateur –...
  • Page 45: Retrait Et Évacuation Du Réfrigérant

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Retrait et évacuation du réfrigérant Lorsque vous ouvrez le circuit frigorifique pour effectuer Ce processus devra peut-être être répété plusieurs fois. L’air des réparations, ou pour toute autre fin, vous devez suivre les comprimé...
  • Page 46: Récupération Du Réfrigérant

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Récupération du réfrigérant Lors du retrait du réfrigérant d’un système, que ce soit pour l’entretien ou la mise hors service, il est recommandé de retirer tous les réfrigérants en toute sécurité.
  • Page 47: Démarrage De L'unité

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Démarrage de l’unité ii. Point de consigne DHW – 54,4 °C (130 °F) est Il est fortement recommandé que la valeur par défaut, mais peut être modifiée de l’entrepreneur chargé...
  • Page 48 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Démarrage de l’unité (suite) Configuration des trousses de capteurs réglage de la puissance du compresseur de l’appareil pour un fonctionnement à haute Configuration des trousses de capteurs et à...
  • Page 49 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Démarrage de l’unité (suite) 5. Vérifiez que le débit d’eau est correct en mesurant la Surveillance du rendement chute de pression dans l’échangeur thermique à l’aide La trousse de surveillance du rendement en comprend trois des bouchons P/T et en la comparant aux données de capteurs de température, soit l’entrée et la sortie de l’eau, la...
  • Page 50 MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Notes...
  • Page 51: Guide De Révision

    MANUEL D’INSTALLATION DE LA POMPE À CHALEUR GÉOTHERMIQUE AVEC CHAUFFAGE D’EAU POUR APPLICATIONS DE SOL RADIANT Guide de révision Pages  Description  Date  Par  Toutes Création de document 21 juillet 2023...
  • Page 52 10/24 ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. La politique de WaterFurnace en matière de recherche et de développement de produits est continue; elle se réserve le droit de modifi er la conception et les spécifi cations sans préavis.