Edwards SIGA-CC1 Installation Sheet

Edwards SIGA-CC1 Installation Sheet

Single input signal module

Advertisement

Quick Links

SIGA-CC1 Single Input Signal Module
Installation Sheet
Description
The SIGA-CC1 Single Input Signal Module is an addressable
module that is used to connect the following circuits:
Audible and visible notification appliance circuits
(synchronized or unsynchronized)
Speaker circuits
Two-way telephone communication circuits (three-state or
four-state)
Upon command from the loop controller, the module connects
supervised Class B signal or telephone circuits to the
respective riser input. The riser input can be 24 VDC (to
operate polarized audible and visible signal notification
appliances), 25 or 70 VRMS (to operate audio evacuation
speakers), or firefighter telephones.
The module does not provide signal synchronization. To meet
UL 864 requirements for horn and strobe signal
synchronization, you must install a Genesis Signal Master
module.
The SIGA-CC1 module requires one address on the signaling
line circuit (SLC). Addresses are assigned electronically. There
are no address switches.
Diagnostic LEDs provide visible indication of the state of the
module through the cover plate:
Normal: Green LED flashes
Alarm/active: Red LED flashes
© 2017 United Technologies Corporation
Personality codes
Use the personality codes described below to configure the
SIGA-CC1 module. See Table 1 for listing information
Table 1: Personality code listing information
Code
Description
5
Signal - supervised
output (Class B)
6
Telephone - three-state
(Class B)
26
Telephone - four-state
(Class B)
Signal - supervised output (Class B).
Personality code 5:
Configures the SIGA-CC1 module as a riser selector for
audible and visible notification appliance circuits or for
single-channel audio circuits. The output circuit is monitored for
open or shorted wiring. If a short exists, the module will not
activate in order to prevent shorting the riser. The module will
activate once the short is cleared.
6: Telephone - three-state (Class B).
Personality code
Configures the module as a riser selector for a three-state
firefighter telephone. When a telephone handset is plugged
into its jack or lifted from its hook, the module generates its
own ring-tone signal, making a separate ring-tone riser
unnecessary. The module sends this signal to the control panel
to indicate the presence of an off-hook condition, and waits for
the system operator to respond to the call. When the system
operator responds, the ring-tone signal is disabled.
Personality code 26:
Configures the module as a riser selector for a four-state
firefighter telephone. Operation is the same as Personality
code 6 except that the module can distinguish when a
telephone is off-hook and when the circuit is shorted, which
causes a trouble condition.
Installation
Install this device in accordance with applicable national and
local codes, ordinances, and regulations.
Notes
The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not
be disassembled.
1 / 6
UL 864
CAN/ULC-
S527
Telephone - four-state (Class B).
P/N 387022P-EN • REV 13 • ISS 14MAR17
EN 54-18

Advertisement

loading
Need help?

Need help?

Do you have a question about the SIGA-CC1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Edwards SIGA-CC1

  • Page 1  (Class B) Signal - supervised output (Class B). Personality code 5: Configures the SIGA-CC1 module as a riser selector for audible and visible notification appliance circuits or for Description single-channel audio circuits. The output circuit is monitored for open or shorted wiring. If a short exists, the module will not The SIGA-CC1 Single Input Signal Module is an addressable activate in order to prevent shorting the riser.
  • Page 2 Each terminal on the module is limited to a single conductor. • Test resistors are supplied with the SIGA-CC1 to prevent trouble signals on unused circuits during installation. When connecting field wires, remove the test resistors and install a UL/ULC Listed 47 kΩ EOLR at the end of the circuit.
  • Page 3 Figure 3: Wiring diagram for NAC (personality code 5) (1)(2)(3)(4) (10) (3)(8) (1) Signal polarity is shown when the circuit is in supervisory state. (4) If using a G1-P Genesis series horn while connected to a Polarity reverses when the circuit is active. compatible fire alarm control panel, a CDR-3 Bell Coder must (2) Supervised.
  • Page 4 Figure 4: Wiring diagram for audio (personality code 5) (1)(2)(3)(4) (10) (1) Signal polarity shown when the circuit is in supervisory state. (4) Unshielded twisted pair. Polarity reverses when the circuit is active. (5) 47 kΩ EOLR (P/N EOL-47). (2) Supervised. (6) Signaling line circuit (SLC) to next device.
  • Page 5 (6.4 mm) space or by a nonconductive sleeve or nonconductive barrier from all other conductors. Refer to the NFPA 70 National Electrical Code for more details. (4) Required if the distance from the SIGA-CC1 to the phone is greater than 5 ft. Shield must be continuous, insulated, (10) and isolated from ground, except for the connection to chassis ground in the control panel.
  • Page 6 Specifications Regulatory information Operating voltage range 15.20 to 19.95 VDC FCC compliance This device complies with part 15 of the FCC Rules. Operation is subject to the following two Current conditions: (1) This device may not cause Standby 310 µA harmful interference, and (2) this device must Activated 135 µA...