6.2 Other
6.2.1 Safety valve
The purpose of the safety valve is to protect the substation from
excessive pressure.
The blow-off pipe from the safety valve must not be closed. The
blow-off pipe outlet should be placed so that it discharges freely
and it is possible to observe any dripping from the safety valve.
It is recommended to check the operation of safety valves at
intervals of 6 months. This is done by turning the valve head in
direction indicated.
6.2.2 Strainer
Strainers should be cleaned regularly by authorized personnel. The
frequency of cleaning would depend on operating conditions and
the manufacturer's instructions.
6.2.3 IHPT 180 controller (45–65 °)
IHPT is a self-acting flow-compensated temperature controller with
integrated differential pressure controller.
The IHPT operates at its best at DH supply temperatures of up to
100 °C.
By turning the handle for temperature setting in (+) direction
the setting is increased, by turning it in (-) direction the setting is
decreased.
Turns*
Scale
0
7
1
6
2
5
3
4
4
3
5
2
6
1
7
0
*Start position: Handle turned fully in (+) direction.
The values are intended as a guide.
18 | © Danfoss | 2024.08
DHW Temperature Setting [°C]
64
61
58
55
52
48
44
43