micropilot M BA 248F/00/en/12.03 Nr. 52012490 Valid as of software version: FMR 244 V 01.02.00 (amplifier) V 01.02.00 (communication) HART/4...20 mA Level-Radar Operating Instructions HART FIELD COMMUNICATION PROTOCOL...
Page 2
Micropilot M FMR 244 with HART/4...20 mA Brief operating instructions KA 159F/00/a2/05.02 Micropilot M - Brief operating instructions 52006292 Contrast: measured value dist./ meas value Group selection basic setup tank shape medium process empty full pipe dist./ check range of start cond.
Safety instructions Designated use The Micropilot M FMR 244 is a compact radar level transmitter for the continuous, contactless measurement of liquids, pastes and sludge. The device can also be freely mounted outside closed metal vessels because of its operating frequency of about 26 GHz and a maximum radiated pulsed energy of 1mW (average power output 1 µW).
Micropilot M FMR 244 with HART/4...20 mA Safety instructions Notes on safety conventions and symbols In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin.
Identification Micropilot M FMR 244 with HART/4...20 mA Identification Device designation 2.1.1 Nameplate The following technical data are given on the instrument nameplate: L00-FMR2xxxx-18-00-00-en-001 Fig. 1: Information on the nameplate of the Micropilot M (example) 2.1.2 Ordering structure Ordering structure Micropilot M FMR 244...
Page 7
Micropilot M FMR 244 with HART/4...20 mA Identification Ordering structure Micropilot M FMR 244 (continued) Output and menu based operation A 4…20 mA HART with VU 331 (4-line alphanumeric display) B 4…20 mA HART K 4...20 mA HART, prepared for FHX40, mounting of remote display (accessory)
"Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures". The instrument described in this manual thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the instrument by affixing to it the CE mark.
Micropilot M FMR 244 with HART/4...20 mA Mounting Mounting Quick installation guide Observe orientation when installing! Turn housing The housing can be turned 350° Installation in tank (free space): in order to simplify access to the Mark on process connector facing the nearest tank wall!
Mounting Micropilot M FMR 244 with HART/4...20 mA Incoming acceptance, transport, storage 3.2.1 Incoming acceptance Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
Page 12
Mounting Micropilot M FMR 244 with HART/4...20 mA Micropilot M FMR 244 - process connection, type of antenna F12 / T12 housing Threaded connection G 1 ½” or 1 ½ NPT Ø 71.5 PVDF PTFE (FDA-listed TFM 1600) Ø 39...
Page 13
Micropilot M FMR 244 with HART/4...20 mA Mounting 3.3.2 Engineering hints Orientation • Recommended distance (1) wall – outer edge of nozzle: ~1/6 of tank diameter. Nevertheless the device should not be installed closer than 15 cm (6“) to the tankwall.
Mounting Micropilot M FMR 244 with HART/4...20 mA Beam angle The beam angle is defined as the angle a where the energy density of the radar waves reaches half the value of the maximum energy density (3dB-width). Microwaves are also emitted outside the signal beam and can be reflected off interfering installations.
Micropilot M FMR 244 with HART/4...20 mA Mounting Measuring conditions Note! Please use FMR 230 respectively FMR 231 for boiling surfaces or in case of a tendency for foaming. The maximum measuring range of the FMR244 may decrease in case of heavy steam development, depending on density, temperature and composition of the steam (→...
Mounting Micropilot M FMR 244 with HART/4...20 mA Measuring range The usable measuring range depends on the size of the antenna, the reflectivity of the medium, the mounting location and eventual interference reflections. The maximum configurable range is 20 m (65 ft) for all Micropilot M (larger ranges up to 35 m (114 ft) on request).
Micropilot M FMR 244 with HART/4...20 mA Mounting Installation instructions 3.4.1 Mounting kit Beside a key AF 60 for installation you need the following tool: • 4 mm/0.1" Allen wrench for turning the housing. 3.4.2 Installation in tank (free space)
Mounting Micropilot M FMR 244 with HART/4...20 mA 3.4.3 Installation in stilling well Optimum mounting position mark at threaded boss G 1½” 1½ NPT Caution! Use only the threaded boss AF 60 max. torque 20 Nm L00-FMR244xx-17-00-00-en-004 Standard installation For installations in a stilling well, follow the engineering hints on Page 13 and note the following points: •...
Micropilot M FMR 244 with HART/4...20 mA Mounting Examples for the construction of stilling wells Micropilot M FMR 244 marker threaded connection G 1½" or 1½ NPT stilling well with slots < 1/10 Ø pipe 100 % < 1/10 Ø pipe...
Mounting Micropilot M FMR 244 with HART/4...20 mA 3.4.4 Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: •...
Micropilot M FMR 244 with HART/4...20 mA Wiring Wiring Quick wiring guide Wiring in F12 housing " Before connection please note the following: The power supply must be identical to the data on the Caution! ENDRESS+HAUSER nameplate (1). MICROPILOT M IP65 Switch off power supply before connecting up the device.
Wiring Micropilot M FMR 244 with HART/4...20 mA Wiring in T12 housing " Before connection please note the following: The power supply must be identical to the data on the nameplate (1). ENDRESS+HAUSER Caution! MICROPILOT M Switch off power supply before connecting up the device.
Micropilot M FMR 244 with HART/4...20 mA Wiring Connecting the measuring unit Terminal compartment Two housings are available: • Aluminium housing F12 with additionally sealed terminal compartment for: – standard, – EEx ia. • Aluminium housing T12 with separate terminal compartment for: –...
Wiring Micropilot M FMR 244 with HART/4...20 mA Terminal voltage Current Communication consumption minimal maximal Fixed current, standard 11 mA 10 V 36 V adjustable e.g. for solar power operation (measured value EEx ia 11 mA 10 V 30 V...
Page 25
Micropilot M FMR 244 with HART/4...20 mA Wiring 4.2.1 HART connection with E+H RMA 422 / RN 221 N - ToF Tool FXA 193 4...20 mA RMA 422 ENDRESS + HAUSER RMA 422 RN 221 N 1 2 3 4 dsdmdm df das.
Wiring Micropilot M FMR 244 with HART/4...20 mA Recommended connection 4.3.1 Equipotential bonding Connect the equipotential bonding to the external ground terminal of the transmitter. 4.3.2 Wiring screened cable " Caution! In Ex applications, the screen must only be grounded on the sensor side. Further safety instructions are given in the separate documentation for applications in explosion hazardous areas.
Micropilot M FMR 244 with HART/4...20 mA Operation Operation Quick operation guide ENDRESS + HAUSER – >3 s Return to basic setup tank shape medium property Group Selection dome ceiling unknown safety settings horizontal cyl DC: < 1.9 bypass DC: 1.9 ... 4...
Operation Micropilot M FMR 244 with HART/4...20 mA 5.1.1 General structure of the operating menu The operating menu is made up of two levels: • Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the instrument are split up roughly into different function groups. The function groups that are available include, e.g.: "basic setup", "safety settings", "output", "display", etc.
Micropilot M FMR 244 with HART/4...20 mA Operation Display and operating elements L00-FMR2xxxx-07-00-00-en-002 Fig. 2: Layout of the display and operating elements Note! To access the display the cover of the electronic compartment may be removed even in hazardous area (IS and XP).
Operation Micropilot M FMR 244 with HART/4...20 mA 5.2.2 Display symbols The following table describes the symbols that appear on the liquid crystal display: Sybmol Meaning ALARM_SYMBOL This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a warning.
Micropilot M FMR 244 with HART/4...20 mA Operation Local operation 5.3.1 Locking of the configuration mode The Micropilot can be protected in two ways against unauthorised changing of instrument data, numerical values or factory settings: "unlock parameter" (0A4): A value <> 100 (e.g. 99) must be entered in "unlock parameter" (0A4) in the "diagnostics"...
Page 32
There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the E+H service organization. Please contact Endress+Hauser if you have any questions. Endress + Hauser...
Micropilot M FMR 244 with HART/4...20 mA Operation 5.3.3 Factory settings (Reset) " Caution! A reset sets the instrument back to the factory settings. This can lead to an impairment of the measurement. Generally, you should perform a basic setup again following a reset.
Operation Micropilot M FMR 244 with HART/4...20 mA Display and acknowledging error messages Types of errors Errors that occur during commissioning or measuring are displayed immediately on the local display. If two or more system or process errors occur, the error with the highest priority is the one shown on the display.
5.5.2 ToF Tool operating program The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle. It is used to support commissioning, securing of data, signal analysis and documentation of the instruments. It is compatible with the following operating systems: Win95, Win98, WinNT4.0 and Win2000.
Operation Micropilot M FMR 244 with HART/4...20 mA Note! Further information you may find on the CD-ROM, which is enclosed to the instrument. Menu-guided commissioning L00-FMR2xxxx-20-00-00-en-002 Signal analysis via envelope curve: L00-FMR2xxxx-20-00-00-en-008 Connection options • Service-interface with adapter FXA 193 (see Page 25) •...
Page 37
Micropilot M FMR 244 with HART/4...20 mA Operation 5.5.3 Commuwin II-Operating Programm Commuwin II is an operating software with graphical support for intelligent transmitters with the communication protocols Rackbus, Rackbus RS 485, INTENSOR, HART or PROFIBUS-PA. It is compatible with the operating systems Win 3.1/3.11, Win95, Win98 and WinNT4.0.
Commissioning Micropilot M FMR 244 with HART/4...20 mA Commissioning Function check Make sure that all final checks have been completed before you start up your measuring point: • Checklist “Post installation check” (see Page 20). • Checklist “Post connection check” (see Page 26).
Micropilot M FMR 244 with HART/4...20 mA Commissioning Basic Setup tank shape dome ceiling threaded connection: reference point of measurement measuring cond. Unknown measuring cond. Standard empty calibr. full calibr. pipe diameter (for bypass/stilling well) mapping E = empty calibr. (= zero) setting in 005 F = full calibr.
Page 40
Commissioning Micropilot M FMR 244 with HART/4...20 mA The basic setup is sufficient for successful commissioning in most applications. Complex measuring operations necessitate additional functions that the user can use to customise the Micropilot as necessary to suit his specific requirements. The functions available to do this are described in detail in the BA 221F.
Micropilot M FMR 244 with HART/4...20 mA Commissioning Basic Setup with the VU 331 Function "measured value" (000) ⇒ This function displays the current measured value in the selected unit (see "customer unit" (042) function). The number of digits after decimal point can be selected in the "no.of decimals"...
Page 42
Commissioning Micropilot M FMR 244 with HART/4...20 mA Function "medium property" (003) ⇒ This function is used to select the dielectric constant. Selection: • unknown • DC: < 1.9 • DC: 1.9 ... 4 • DC: 4 ... 10 • DC: > 10 ε...
Page 43
Micropilot M FMR 244 with HART/4...20 mA Commissioning Function "process cond." (004) ⇒ This function is used to select the process conditions. Selection: • standard • calm surface • turb. surface • agitator • fast change • test:no filter standard calm surface turb.
Page 44
Commissioning Micropilot M FMR 244 with HART/4...20 mA Function "empty calibr." (005) ⇒ This function is used to enter the distance from the flange (reference point of the measurement) to the minimum level (=zero). L00-FMR2xxxx-14-00-06-en-008 " Caution! For dish bottoms or conical outlets, the zero point should be no lower than the point at which the radar beam hits the bottom of the tank.
Page 45
Micropilot M FMR 244 with HART/4...20 mA Commissioning Function "full calibr." (006) ⇒ This function is used to enter the distance from the minimum level to the maximum level (=span). L00-FMR2xxxx-14-00-06-en-009 Note! If bypass or stilling well was selected in the "tank shape" (002) function, the pipe diameter is requested in the following step.
Page 46
Commissioning Micropilot M FMR 244 with HART/4...20 mA Function "pipe diameter" (007) ⇒ This function is used to enter the pipe diameter of the stilling well or bypass pipe. L00-FMR2xxxx-14-00-00-en-011 Microwaves propagate more slowly in pipes than in free space. This effect depends on the inside diameter of the pipe and is automatically taken into account by the Micropilot.
Page 47
Micropilot M FMR 244 with HART/4...20 mA Commissioning display (008) ⇒ The distance measured from the reference point to the product surface and the level calculated with the aid of the empty adjustment are displayed. Check whether the values correspond to the actual level or the actual distance. The following cases can occur: •...
Page 48
Commissioning Micropilot M FMR 244 with HART/4...20 mA dist. too small • At the moment, an interference is being evaluated • Therefore, a mapping is carried out including the presently measured echoes • The range to be suppressed is suggested in the "range of mapping" (052) function dist.
Page 49
Micropilot M FMR 244 with HART/4...20 mA Commissioning display (008) ⇒ The distance measured from the reference point to the product surface and the level calculated with the aid of the empty adjustment are displayed. Check whether the values correspond to the actual level or the actual distance. The following cases can occur: •...
Commissioning Micropilot M FMR 244 with HART/4...20 mA 6.4.2 Envelope curve with VU 331 After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E) function group) is recommended. Function "plot settings" (0E1) ⇒...
Page 51
Micropilot M FMR 244 with HART/4...20 mA Commissioning Function "envelope curve display" (0E3) The envelope curve is displayed in this function. You can use it to obtain the following information: quality of evaluated echo full calibr. evaluated echo is marked empty calibr.
Page 52
Commissioning Micropilot M FMR 244 with HART/4...20 mA Move mode Then press to switch to Move mode. Either is displayed. • shifts the curve to the right. • shifts the curve to the left. L00-FMxxxxxx-07-00-00-yy-008 Vertical Zoom mode Press once more to switch to Vertical Zoom mode.
Micropilot M FMR 244 with HART/4...20 mA Commissioning Basic Setup with the ToF Tool To carry out the basic setup with the ToF Tool operating program, proceed as follows: • Start the ToF Tool operating program and establish a connection •...
Page 54
Commissioning Micropilot M FMR 244 with HART/4...20 mA Basic Setup step 2/4: • Enter the application parameters: – tank shape (for a description, see Page 41) – medium property (for a description, see Page 42) – process cond. (for a description, see Page 43)
Page 55
Micropilot M FMR 244 with HART/4...20 mA Commissioning If "horizontal cyl" or "sphere" is selected in the "tank shape" function, the following display appears on the screen: • empty calibr. (for a description, see Page 44) • full calibr.(for a description, see Page 45) L00-FMR2xxxx-20-00-00-en-004 If "stilling well"...
Page 56
Commissioning Micropilot M FMR 244 with HART/4...20 mA If "flat ceiling" is selected in the "tank shape" function, the following display appears on the screen: • empty calibr. (for a description, see Page 44) • full calibr.(for a description, see Page 45)
Micropilot M FMR 244 with HART/4...20 mA Commissioning 6.5.1 Envelope curve with the ToF Tool After the basic setup, an evaluation of the measurement using the envelope curve is recommended. L00-FMR2xxxx-20-00--00-en-008 Note! If the level of echo is very weak or there is a heavy interference echo, an orientation of the Micropilot can help optimise the measurement (increase of the useful echo/ reduction of the interference echo) (see "Orientation of the Micropilot"...
They contain the related replacement instructions. All the spare parts kits which you can order from Endress+Hauser for repairs to the Micropilot M are listed with their order numbers on and . Please contact Endress+Hauser Service for further information on service and spare parts.
Micropilot M FMR 244 with HART/4...20 mA Accessories Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Micropilot M. Weather protection cover A Weather protection cover made of stainless steel is available for outdoor mounting (order code: 543199-0001).
Page 60
Accessories Micropilot M FMR 244 with HART/4...20 mA Remote display FHX 40 Dimensions Wall-mounting Pipe-mounting (without mounting bracket) (mounting bracket and plate F12/F23 housing (IP 68) supplied optionally, s. product structure) Separate housing FHX 40 (IP 65) O rd O rd...
Micropilot M FMR 244 with HART/4...20 mA Trouble-shooting Trouble-shooting Trouble-shooting instructions Micropilot M FMR 2xx -Trouble Shooting Check voltage and Not ok Instrument does compare it with the Connect the Instrument works? Ready not respond specifications on the correct voltage nameplate.
Trouble-shooting Micropilot M FMR 244 with HART/4...20 mA System error messages Code Description Possible cause Remedy A102 checksum error device has been powered off before reset; general reset & new data could be stored; avoid emc problem; calibr.required emc problem;...
Page 63
Micropilot M FMR 244 with HART/4...20 mA Trouble-shooting Code Description Possible cause Remedy W621 simulation ch. 1 on simulation mode is active switch off simulation mode E641 no usable echo echo lost due to application check installation; channel 1 conditions or built up on antenna optimize orientation of antenna;...
Trouble-shooting Micropilot M FMR 244 with HART/4...20 mA Application errors Error Output Possible cause Remedy A warning or Depending on the configuration See table of error 1. See table of error messages alarm has occur- messages (see Page 62) red.
Page 65
Micropilot M FMR 244 with HART/4...20 mA Trouble-shooting Error Output Possible cause Remedy → If the surface is Signal is weakened 1. Carry out tank mapping by the rough surface basic setup not calm (e.g. fil- ling, emptying, – the interference 100% 2.
Trouble-shooting Micropilot M FMR 244 with HART/4...20 mA Orientation of the Micropilot For orientation a marker is found on the flange or threaded boss of the Micropilot. During installation this must be oriented as follows (see Page 9): • In tanks: to the vessel wall •...
Page 67
Micropilot M FMR 244 with HART/4...20 mA Trouble-shooting L00-FMRxxxxx-19-00-00-en-004 Fig. 7: Vessel empty, no interference echo L00-FMRxxxxx-19-00-00-en-005 Fig. 8: Vessel empty, interference echo obtained Fix the flange or threaded boss in this position. If necessary, replace the seal. Carry out tank mapping, see Page 47.
(see Page 6s. Seite 6 ff.). The corresponding spare part number also appears on each spare part. Installation instructions are given on the instruction card that is also delivered. Spare parts Micropilot M FMR 244, F12 housing with combined wiring and electronics compartment O rd...
Page 70
Trouble-shooting Micropilot M FMR 244 with HART/4...20 mA 65 Sealing kit 535720-9010 consists of: 2 x gasket Pg13.5 FA 2 x O-ring 17.0x2.0 EPDM 1 x O-ring 49.21x3.53 EPDM 2 x O-ring 17.12x2.62 FKM 1 x O-ring 113.9x3.63 EPDM 1 x O-ring 72.0x3.0 EPDM...
Page 71
Micropilot M FMR 244 with HART/4...20 mA Trouble-shooting Spare parts Micropilot M FMR 244, T12 housing with separate wiring and electronics compartment O rd d e : r. -N I L O o .: s s b e re a s u...
Page 72
Trouble-shooting Micropilot M FMR 244 with HART/4...20 mA 10 Housing 543180-0022 Housing T12, Aluminium, coated, G1/2, PAL 543180-0023 Housing T12, Aluminium, coated, NPT1/2, PAL 543180-0024 Housing T12, Aluminium, coated, M20, PAL 543180-1023 Housing T12, Aluminium, NPT1/2, PAL, cover, EEx d...
Page 73
Micropilot M FMR 244 with HART/4...20 mA Trouble-shooting 65 Sealing kit 535720-9010 consists of: 2 x gasket Pg13.5 FA 2 x O-ring 17.0x2.0 EPDM 1 x O-ring 49.21x3.53 EPDM 2 x O-ring 17.12x2.62 FKM 1 x O-ring 113.9x3.63 EPDM 1 x O-ring 72.0x3.0 EPDM...
– HART communicator DXR 375 with Rev. 1, DD 1. Contact addresses of Endress+Hauser The addresses of Endress+Hauser are given on the back cover of this operating manual. If you have any questions, please do not hesitate to contact your E+H representative.
Micropilot M FMR 244 with HART/4...20 mA Technical data Technical data 10.1 Additional technical data 10.1.1 Input Measured variable The measured variable is the distance between a reference point and a reflective surface (i.e. medium surface). The level is calculated based on the tank height entered.
Technical data Micropilot M FMR 244 with HART/4...20 mA Resolution Digital / analog in % 4…20 mA • FMR 244: 1mm / 0.03 % of measuring range Reaction time The reaction time depends on the parameter settings (min. 1 s). In case of fast level changes, the instrument needs the reaction time to indicate the new value.
Weight 10.1.8 Certificates and approvals CE approval The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument passing the required tests by attaching the CE-mark. RF approvals R&TTE, FCC Overspill protection german WHG, see ZE 244F/00/de.
Technical data Micropilot M FMR 244 with HART/4...20 mA Ex approval XA 103F-D Installation Micropilot M FMR 2xx (F12 / PTFE antenna, non-conductive / EEx ia IIC T6) PTB 00 ATEX 2117 X, Equipment marking: (II 1/2 G) XA 105F-D...
Page 79
Micropilot M FMR 244 with HART/4...20 mA Technical data Endress + Hauser...
Appendix Micropilot M FMR 244 with HART/4...20 mA Appendix 11.1 Operating menu HART (display modul), ToF Tool basic setup tank shape medium cond. process cond. empty calibr. full calibr. dome ceiling unknown standard enter value enter value horizontal cyl. DK: < 1.9 calm surface DK: 1.9 …...
Page 81
Micropilot M FMR 244 with HART/4...20 mA Appendix dist./meas.value check distance range of mapping start mapping dist./meas.value distance = ok input of D and L dist. too small mapping range are displayed D and L manual are displayed dist. unknown dist.
Micropilot M FMR 244 with HART/4...20 mA Appendix 11.3 Description of functions Note! A detailed description of the function groups, functions and parameters is given in the documentation BA 221F/00/en "Description of the instrument functions of the Micropilot M" on the enclosed CD-ROM.
Appendix Micropilot M FMR 244 with HART/4...20 mA 11.4 Function and system design 11.4.1 Function (Measuring principle) The Micropilot is a "downward-looking" measuring system, operating based on the time- of-flight method. It measures the distance from the reference point (process connection) to the product surface.
Micropilot M FMR 244 with HART/4...20 mA Appendix Output The Micropilot is commissioned by entering an empty distance E (=zero), a full distance F (=span) and an application parameter. The application parameter automatically adapts the instrument to the process cond.. The data points “E” and “F” correspond with 4mA and 20mA for instruments with current output.
Page 86
• with display and operating module VU 331, • with a Personal Computer, FXA 193 and the operating software ToF Tool. The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided micro- impulse).
Micropilot M FMR 244 with HART/4...20 mA Endress + Hauser Index accessories....... . 59 installation in stilling well .
Page 88
Micropilot M FMR 244 with HART/4...20 mA Endress + Hauser spare parts ....... . 68 stilling well .
Page 91
Declaration of contamination Dear customer, Because of legal determinations and for the safety of our employes and operating equipment we need this “Declaration of contamination” with your signature before your order can be handled. Please put the completely filled in declaration to the instrument and to the shipping documents in any case. Add also safety sheets and/or specific handling instructions if necessary.
Page 92
Poland – Wroclaw Costa Rica – San Jose ❑ Sakura Endress Co. Ltd. ❑ Endress+Hauser Polska Sp. z o.o. Tel. (01) 88 05 60, Fax (01) 88 05 63 35 Euro-Tec S.A. Tel. (0422) 54 06 11, Fax (0422) 55 02 75 Tel.
Need help?
Do you have a question about the micropilot M FMR 244 and is the answer not in the manual?
Questions and answers