INSTALLER/cONSUMER SAFETY INFORMATION pLEASE READ THIS MANUAL BEFORE INSTALLING AND USING AppLIANcE WARNING! Oxford Direct Vent / IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED Natural Vent Gas Heater ExAcTLY, A FIRE OR ExpLO- SION MAY RESULT cAUSING Models: OxDV30NV pROpERTY DAMAGE, pER- SONAL INjURY OR LOSS OF LIFE.
Table of contents pLEASE READ THE INSTALLATION & OpERATING INSTRUcTIONS BEFORE USING AppLIANcE. Thank you and congratulations on your purchase of an MHSc stove. IMpORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard and will void the warranty.
Oxford Direct Vent / Natural Vent Gas Heater General Information The Oxford Direct Vent/Natural Vent Room Heater, Model WARNING: Operation of this heater when not connected No. OXDV30NV, is a vented gas appliance listed to the ANSI to a properly installed and maintained venting system standard Z21.88-2009 and CSA-2.33-2009 for Vented Room can result in carbon monoxide (cO) poisoning and pos- Heaters, and CSA 2.17-M91, Gas-Fired Appliances For Use...
Oxford Direct Vent / Natural Vent Gas Heater Installation Requirements Requirements for the commonwealth of Inspection Massachusetts The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not All gas fitting and installation of this heater shall only be approve the installation unless, upon inspection, the done by a licensed gas fitter or licensed plumber.
The Draft Hood Adapter is available in the 7FSDHASK stove kit or as a separate item. When the stove is converted to Natural Vent, it uses 4” vent pipe. For aesthetic purposes the MHSc direct vent system may be used up to the ceiling.
Oxford Direct Vent / Natural Vent Gas Heater Installation Requirements The installation must conform with local codes or, in Direct Vent System Only the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEP- TION: Do not derate this appliance for altitude.
Oxford Direct Vent / Natural Vent Gas Heater Horizontal Termination - Gas Specifications Direct Vent ONLY Max. Min. Input Input The vent must rise vertically a minimum of 24” (610 Model Fuel Gas control BTU/h BTU/h mm) off the top of the unit, before the first elbow. The 2465 Millivolt 28,000...
Oxford Direct Vent / Natural Vent Gas Heater Vertical Termination - Direct Vent ONLY Vent Termination clearances When planning the installation, consider the location A vertical vent system must terminate no less than 8’ of the vent terminal and clearances. Some of the most (2.44 m) and no more than 40’...
Page 11
Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termi- • Only MHSc and Simpson DuraVent venting com- nation area after snow falls, and clear to prevent ac- ponents specifically approved and labelled for cidental blockage of venting system.
2. The special venting system used on Direct Vent appliances are certified as part of the appliance, with clearances tested and approved by the listing agency. 3.MHSC assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.
(1) Side Wall Termination nents specified on this page. These parts are available from (1) Firestop DuraVent Corporation or your MHSC Dealer. (1) Zero-clearance sleeve Refer to Figure 4 for dimensions relevant to the standard (1) Hardware package minimum-vent kits.
Oxford Direct Vent / Natural Vent Gas Heater • Remove retaining nut from shaft of rheostat. (if Install the Optional Fan preinstalled) If you are installing the optional convection Fan Kit • Insert the rheostat through the hole in the back #2767 (FK26), continue here.
First Section of Vent Pipe Install the Vent Adapter pipe #8 x 1/2” Sheet (MHSc Vent components) Metal Screws 1. Install the Restrictor plate. Consult the ‘Vent Run Specifications’ on Page 8 to determine whether the restrictor plate is needed. If so, put the restrictor 4”...
Using the starter pipe assembly listed on Page Figure 22. 7, slide the inner section out to allow access. • Run a bead of sealant around the bottom end of MHSc System 9C\,” the starter pipe and attach the assembly to the stove (240 mm using three 1/4-20 x 3/8”...
Page 18
• Slide the wall plate over horizontal run before at- taching the horizontal run to the elbow. Fasten wall plate to wall. 4. For MHSC Vent Pipe only: If necessary, measure to determine the vertical length (X) of pipe required from the adapter pipe to the wall cutout centerline, ST215 including a 2”...
2. Plumb to the center of the inner (4”) flue collar from the ceiling above, and mark that location. 3. cut the opening: 4” Clearance MHSc System: 9C\,” x 9C\,” (240 x 240mm) DuraVent System: 10” x 10” (254 x 254mm) Gravel 4. Plumb any additional opening through the roof or other construction that may be needed.
The heater is approved for installation as a Natural overall height. Vent. MHSC Direct Vent pipe could be used directly 11. Apply cement to the inner and outer termination col- after the Draft Hood Adapter up to the ceiling, then lars and install the terminal cap.
Oxford Direct Vent / Natural Vent Gas Heater Attach the first section of venting to the draft hood. De- Left Log Right Log pending on the length of the individual venting sections and the lengths of the decorative pipe (if installed), you may need to slip the decorative pipe over the venting sections before attaching upper sections to lower ones.
Oxford Direct Vent / Natural Vent Gas Heater In the U.S.; Gas connection should be made in ac- Air Shutter Adjustment Instructions cordance with current National Fuel Gas Code, ANSI Z223.1/NFPA 54. Since some municipalities have To adjust the air shutter, the following procedures additional local codes, be sure to consult your local should be followed: authority.
Oxford Direct Vent / Natural Vent Gas Heater 8. The air shutter is located on the bottom of the burner Should color need further adjustment, repeat steps 1 to the left. (Fig. 37) Unfasten the two nuts holding - 12 for air shutter adjustment. the shutter in place.
Oxford Direct Vent / Natural Vent Gas Heater Thermostat connection (optional) Use only a thermostat rated for 500 millivolts. Check the table below for the appropriate gauge ther- mostat wire to use for the length of lead required in your installation.
Oxford Direct Vent / Natural Vent Gas Heater Operation Flame & Temperature Adjustment Your First Fire For stoves equipped with HI/LO valves, flame adjust- Read these instructions carefully and familiarize your- ment is accomplished by rotating the HI/LO adjustment self with the burner controls. Locate the pilot assembly, knob located near the center of the gas control valve.
Oxford Direct Vent / Natural Vent Gas Heater Lighting and Operating Instructions FOR YOUR SAFETY READ BEFORE LIGHTING WARNING:If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A.
Oxford Direct Vent / Natural Vent Gas Heater Troubleshooting the Gas control System SIT NOVA 820 MILLIVOLT VALVE NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position. possible causes corrective Action Symptom 1.
Oxford Direct Vent / Natural Vent Gas Heater Fuel conversion Instructions WARNING! This conversion kit shall be installed Remove Screws Rear Log Bracket by a qualified service agency in accordance with the manufacturer’s instructions and all applicable Pilot codes and requirements of the authority having jurisdiction.
Page 29
Oxford Direct Vent / Natural Vent Gas Heater pilot type 2 • Loosen pilot hood turning counterclockwise using a 7/16” wrench. (Fig. 54) NOTE: You may use penetrating oil to prevent pilot hood threads from seizing up. • Remove pilot orifice with needlenose pliers. (Fig. 55) NOTE: Use a wrench to hold pilot tube in place while removing the orifice.
Page 30
Oxford Direct Vent / Natural Vent Gas Heater 25.Replace logs. Left Burner Leg 26.Replace glass and stove front. Conversion is complete. Injector Shoulder 90¡ ST353 Fig. 56 Be sure to maintain 90° angle at left burner leg. ST353 air shutter adjust burner replace 3/20/00 Table 2.
6. Replace the glass panel and frame assembly. Glass Replacement 7. Replace the Stove Front. Replace glass only with MHSC approved parts. Refer to Page 33 for Replacement Parts. Refer to Figure 58 and previous instructions for removal of the damaged glass frame.
Oxford Direct Vent / Natural Vent Gas Heater Inspect the Vent System Annually Have the vent system inspected annually by a qualified technician. Shut off the main gas supply before inspect- ing the system. Both the inner exhaust pipe and the out- er combustion supply pipe must be checked to confirm that they are unblocked and in good condition.
10 8 11 15a,b, 31 36a,b MHSC reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice. 5123 Oxford Direct Vent / Natural Vent Gas Heater Oxford parts Models OxDV30NV Ref.
Page 35
Oxford Direct Vent / Natural Vent Gas Heater Oxford Direct Vent / Natural Vent Gas Heater Models OxDV30NV (continued) Ref. Description Oxford Glass, DV25 1601691 Glass Frame Assembly - SDV30 30000127 Gasket, Glass - Med. Knit - RDV40 1203702 Pilot Top Convertible 10002266 Pilot Assembly 3Way N/DV RN 0.199.706 10002264...
Oxford Direct Vent / Natural Vent Gas Heater Optional Accessories Fan Kits Remote controls FK26 Fan The remote control allows you to turn the heater on or off from anywhere in the room. Refer to Page 32 for The FK26 fan helps distribute heated air from within wiring diagrams.
Page 37
Oxford Direct Vent / Natural Vent Gas Heater 30005123...
Page 38
Oxford Direct Vent / Natural Vent Gas Heater 30005123...
Page 39
Oxford Direct Vent / Natural Vent Gas Heater 30005123...
AND LIMITATIONS a) The fireplace has been operated in atmospheres contaminated by • This new MHSC product must be installed by a competent, autho- chlorine, fluorine, or other damaging chemicals. rized, service contractor. A licensed technician, as prescribed by the b) The fireplace has been subjected to prolonged periods of damp- local jurisdiction must perform any installation/service work.