Gree GK-H03NH3AS Service Manual

Gree GK-H03NH3AS Service Manual

Rooftop packaged
Hide thumbs Also See for GK-H03NH3AS:

Advertisement

Quick Links

ROOFTOP PACKAGED
(GC201810-VI)
CAPACITY RANGE:10.5~69.0kW (35800~235500Btu/h)
OPERATION RANGE:COOLING:18~48° C
HEATING:-10~24° C
Grupo Confort Nacional S.A. de C.V.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GK-H03NH3AS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Gree GK-H03NH3AS

  • Page 1 ROOFTOP PACKAGED (GC201810-VI) CAPACITY RANGE:10.5~69.0kW (35800~235500Btu/h) OPERATION RANGE:COOLING:18~48° C HEATING:-10~24° C Grupo Confort Nacional S.A. de C.V.
  • Page 2: Table Of Contents

    Contents PRODUCT INTRODUCTION ..................2 1 MODELS LIST ......................2 2 NOMENCLATURE ....................3 3 FUNCTION ....................... 3 4 PRODUCT DATA ..................... 4 4.1 PRODUCT DATA AT RATED CONDITION ..............4 4.2 OPERATION RANGE ..................... 7 4.3 ELECTRICAL DATA ....................... 8 5 PIPING DIAGRAM ....................
  • Page 3 6.1 DISPLAY OF ERROR CODE ..................25 INSTALLATION ......................29 1 UNITS INSTALL ..................... 29 1.1 INSTALLATION POSITIONS ..................29 1.2 MATTERS NEED ATTENTION ..................29 1.3 DIMENSION ......................... 33 2 DRAIN PIPING WORK ................... 37 2.1 INSTALLATION PROCEDURE ..................37 2.2 MATTERS OF ATTENTION ..................
  • Page 4 GREE ROOFTOP PACKAGED PRODUCT...
  • Page 5: Product Introduction

    1 MODELS LIST Power Model Nominal Supply Capacity Appearance Refrige Product (V, Ph, Model Name (Ton) rant Code 220~240V R410A GK-H03NH3AS EJ51000660 , 1Ph, 50/60Hz 220~240V R410A GK-H5.5NH3AS EJ51000740 , 1Ph, 50/60Hz 220~240V R410A GK-H5.5NH3AF EJ51000650 , 3Ph, 60Hz 220~240V...
  • Page 6: Nomenclature

    ① Above pictures may be different from actual model. ② 1Ton =12000Btu/h = 3.517kW. 2 NOMENCLATURE - Description Options Product Category GK=GREE Rooftop Packaged Air-condition C = Cooling only type; Product Function Code H = Heat pump type. 03=3Ton; Cooling/Heating Capacity 5.5=5.5Ton..
  • Page 7: Product Data

    GREE ROOFTOP PACKAGED 4 PRODUCT DATA 4.1 PRODUCT DATA AT RATED CONDITION Model GK-H03NH3AS GK-H5.5NH3AS Btu/h 35800(13650-42660) 66500(20500-66500) Cooling 10.5(4.0-12.5) 19.5(6.0-19.5) Total Capacity Btu/h 39250(17070-46100) 70000(27300-73400) Heating 11.5(5.0-13.5) 20.5(8.0-21.5) Power supply V-Hz-Ph 220-240V-50/60Hz-1Ph 220-240V-50/60Hz-1Ph Cooling Power input Electrical Heating Data Cooling 13.5...
  • Page 8 GREE ROOFTOP PACKAGED Model GK-H03NH3AS GK-H5.5NH3AS Outline dimension 1450×1120×815 1450×1120×815 (W×D×H) Dimension Package dimension 1463×1133×860 1463×1133×860 (W×D×H) Net weight Weight Gross weight 20'GP Loading quantity 40'GP 40'HQ Model GK-H5.5NH3AF GK-H10NH3AF Btu/h 71700(20500-75100) 116000(34100-119400) Cooling 21.0(6.0-22.0) 34.0(10.0-35.0) Total Capacity Btu/h 75100(27300-78500)
  • Page 9 GREE ROOFTOP PACKAGED Model GK-H5.5NH3AF GK-H10NH3AF 1.29 2.34 Fins per Inch(FPI) Permissible Excessive Operating Pressure for the Discharge Side Permissible Excessive Operating Pressure for the Suction Side Cooling ° C 18-48 18-48 Operation temp Heating ° C -10-24 -10-24 Filter...
  • Page 10: Operation Range

    ③ The technical parameters are changed along with the products improvement; please refer to the nameplate of the unit for actual data. ④ Above data is subject to change without notice. 4.2 OPERATION RANGE GK-H03NH3AS,GK-H5.5NH3AS,GK-H5.5NH3AF,GK-H10NH3AF,GK-H15NH3AF,GK-H20NH3AF Item Outdoor Condition (DB ° C) Cooling...
  • Page 11: Electrical Data

    4.3 ELECTRICAL DATA Condenser Supply Blower Compressor Breaker Min. Power Fan Motors Motor Capacity Supply Cord Model Power Supply Qty. − V/Ph/Hz GK-H03NH3AS 220-240V, 1Ph,50/60Hz 13.0 GK-H5.5NH3AS 220-240V, 1Ph,50/60Hz 19.0 10.0 GK-H5.5NH3AF 220-240V, 3Ph,60Hz 28.0 10.0 GK-H10NH3AF 220-240V, 3Ph,60Hz 36.0 10.0...
  • Page 12 GREE ROOFTOP PACKAGED CONTROL...
  • Page 13: Units Control

    GREE ROOFTOP PACKAGED UNITS CONTROL 1 OPERATION FLOWCHART 1.1 COOLING OPERATION Power Open unit running at cool mode Indoor fan run Satisfying open Comp. condition Comp. and outdoor fan run Temp of indoor ≤Set temp Comp. and outdoor fan stop Comp.
  • Page 14: Heating Operation

    GREE ROOFTOP PACKAGED 1.2 HEATING OPERATION Power Open unit running at heat mode Satisfying open Comp. condition Comp. and outdoor fan run Avoid cool wind (only when comp start) Temp of indoor ≥Set temp Comp. and outdoor fan stop Comp. stop...
  • Page 15: Wireless Remote Controller

    GREE ROOFTOP PACKAGED 2 WIRELESS REMOTE CONTROLLER Notes: The wireless remote controller is an Optional Fitting 2.1 OPERATION AND DISPLAY VIEW Table 2-2-1 Operation instruction of wireless remote controller Name Function Description Signal Signal transmitter transmitter ON/OFF Press this button and the unit will be turned on; press it once more, and the unit will be turned off.
  • Page 16 GREE ROOFTOP PACKAGED Name Function Description Press this button to set up the swing angle, which circularly changes as below: When the guide louver starts to swing up and down, if SWING functions is canceled, the air guide SWING louver will stop and remains at the current position.
  • Page 17: Wired Controller

    GREE ROOFTOP PACKAGED 3 WIRED CONTROLLER 3.1 DISPLAY VIEW Figure 2-3-1 Appearance of wired controller Figure 2-3-2 LCD display of wired controller Table 2-3-1 Instruction to LCD Display Display Introduction Automatic mode (under auto mode, the indoor unit will select its operating mode...
  • Page 18: Operation View

    GREE ROOFTOP PACKAGED Display Introduction Health Display when health function is set Absent Display when absent function is set I-Demand Display when I-DEMAND function is set WIFI WIFI function icon Child-lock Child-lock status, display when child-lock function is set Up&down swing...
  • Page 19 GREE ROOFTOP PACKAGED 3.2.2 Instruction to Function of Buttons Table 2-3-2 Instruction to buttons of wired controller Description Functions  Function selection and canceling;  Press it for 5s to view the ambient temperature; press Mode button to Swing/Enter select viewing outdoor ambient temperature or indoor ambient temperature.
  • Page 20: Operation Instructions Of Special Functions

    GREE ROOFTOP PACKAGED 4 OPERATION INSTRUCTIONS OF SPECIAL FUNCTIONS 4.1 Setting of Filter Clean Reminder Function When unit is on, press Function button to switch to filter clean reminder function. The icon will blink and then enter setting of filter clean reminder function. Timer zone displays the set pollution level and you can press ▲...
  • Page 21: Lock Function

    GREE ROOFTOP PACKAGED (1) If cleaning time is not reached, no mater the setting is changed or not, the accumulated operating time won’t be recalculated when pressing Swing/Enter button; (2) If cleaning time is reached, in unit on or off state, will blink every 0.5s for reminder.
  • Page 22: Switch Between Fahrenheit And Centigrade

    GREE ROOFTOP PACKAGED 4.5 Switch between Fahrenheit and Centigrade Under off state of the unit, press Mode and ▼ buttons at the same time for 5s to switch between Fahrenheit and Centigrade. 4.6 Enquiry of Ambient Temperature Under off or on state of the unit, press Swing/Enter for 5s to view the ambient temperature. In this case, timer zone displays ambient temperature type 01 or 02.
  • Page 23 GREE ROOFTOP PACKAGED sensor at wired controller in heating and auto mode. 4.8.2 Displaying setting of freeze protection error code Under debugging state, press Mode button to adjust to “02” in temperature displaying zone. Timer zone displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:...
  • Page 24 GREE ROOFTOP PACKAGED 4.8.6 Selecting low-power consumption mode Under debugging state, press Mode button to adjust to “07” in temperature displaying zone. Timer zone displays setting state and press ▲ or ▼ button to adjust. There are 2 selections: (1) With low-power consumption mode (LCD displays 00) (2) Without low-power consumption mode (LCD displays 01) 4.8.7 Selecting door control function...
  • Page 25 GREE ROOFTOP PACKAGED 4.8.10 Selecting compensation of temperature sensor at air return Under debugging state, press Mode button to adjust to “12” in temperature displaying zone. Timer zone displays setting state and press ▲ or ▼ button to adjust. There are 16 selections: (1) Compensate 0°...
  • Page 26: Installation Of Wired Controller

    GREE ROOFTOP PACKAGED After finishing setting, press Swing/Enter button to save and exit setting. After entering this interface, the system will exit this menu if there is no operation on the button within 20s. Normal off state interface will be displayed and present setting will not be saved.
  • Page 27: Installation Of Wired Controller

    GREE ROOFTOP PACKAGED connecting wire, the shortest distance should be over 20cm, otherwise the communication cannot work normally; 3) If the unit is installed in the position where is likely to be impacted by electromagnetic interface, signal wire of wired controller should be made of STP (shielded twisted pair).
  • Page 28: Removal Of Wired Controller

    GREE ROOFTOP PACKAGED 5.4 Removal of Wired Controller Figure 2-5-3 Removal of wired controller 6 TROUBLESHOOTING 6.1 DISPLAY OF ERROR CODE Table 2-6-1 Error Code List 1 Error code Error Remarks Compressor high pressure protection Indoor anti-freeze protection Compressor low pressure protection, refrigerant lack...
  • Page 29 GREE ROOFTOP PACKAGED Error code Error Remarks Zero passage protection AC current protection Drive current error Sensor connecting protection Temperature drift protection Bus low voltage protection Bus high voltage protection Charge loop error Input voltage abnormality Drive memory chip error...
  • Page 30 GREE ROOFTOP PACKAGED For example, E1 means high pressure protection during operation. Figure 2-6-1...
  • Page 31 GREE ROOFTOP PACKAGED INSTALLATION...
  • Page 32: Installation

    GREE ROOFTOP PACKAGED INSTALLATION 1 UNITS INSTALL 1.1 INSTALLATION POSITIONS To ensure the unit in proper function, selection of installation location must be in accordance with following principles. (1) Unit shall be installed so that the air discharged by outdoor fan will not return and that sufficient space for repair shall be provided around the unit.
  • Page 33 And the unit must be fixed on the pedestal with bolt. The location of pedestal must be able to support the weight of the unit. If not, the unit may be overturning, declining or falling off in an extreme circumstance (just like earthquake, typhoon). GK-H03NH3AS...
  • Page 34 GREE ROOFTOP PACKAGED GK-H5.5NH3AS、GK-H5.5NH3AF GK-H10NH3AF GK-H15NH3AF...
  • Page 35 GREE ROOFTOP PACKAGED GK-H20NH3AF NOTE: ① The diagram may be different from actual model. The diagram is for pedestal made of concrete. ② The high dimension of the pedestal must be enough to install drainpipe (Refer to DRAIN PIPING WORK) 1.2.4 DUCTWORK...
  • Page 36: Dimension

    GREE ROOFTOP PACKAGED 1.3 DIMENSION 1.3.1 DIMENSION OF UNITS GK-H03NH3AS GK-H5.5NH3AS、GK-H5.5NH3AF GK-H10NH3AF...
  • Page 37 GREE ROOFTOP PACKAGED GK-H15NH3AF GK-H20NH3AF Dimension (mm) GK-H03NH3AS 1450 1120 GK-H5.5NH3AS 1450 1120 GK-H5.5NH3AF 1450 1120 GK-H10NH3AF 1215 1450 1120 GK-H15NH3AF 1245 2260 1140 GK-H20NH3AF 1250 1880 2240 2021 1336 Note: Above diagrams may be different from actual mode.
  • Page 38 GREE ROOFTOP PACKAGED 1.3.2 INSTALLATION CLEARANCE DATA Note: Above diagrams may be different from actual mode. GK-H03NH3AS、GK-H5.5NH3AS、GK-H5.5NH3AF Installation Clearances DIMENSION (Minimum) inch 1100 1100 1100...
  • Page 39 GREE ROOFTOP PACKAGED GK-H10NH3AF GK-H15NH3AF...
  • Page 40: Drain Piping Work

    GREE ROOFTOP PACKAGED GK-H20NH3AF Note: Above diagrams may be different from actual mode. GK-H10NH3AF、GK-H15NH3AF、GK-H20NH3AF Installation Clearances DIMENSION (Minimum) inch 1000 1500 1100 1100 1100 2 DRAIN PIPING WORK 2.1 INSTALLATION PROCEDURE After the unit is installed, it is required to check the level of the whole unit. The unit must be placed horizontally to ensure the unit in proper function.
  • Page 41: Matters Of Attention

    Remark: P is the absolute pressure inside the unit. The unit of the pressure is Pa. After the electrical installation is completed, carry out the testing of the drainage system. Note: Above diagrams may be different from actual mode. Model Drain Connection Size(mm) GK-H03NH3AS GK-H5.5NH3AS GK-H5.5NH3AF GK-H10NH3AF GK-H15NH3AF...
  • Page 42 GREE ROOFTOP PACKAGED (8) Do not change the internal line connections inside the air-conditioning unit. The manufacturer shall not be liable for any loss or abnormal operation arising from wrong line connections. (9) If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
  • Page 43: Electric Wiring Design

    The signal line of the wire controller must be separated from the power line. In case the unit is installed in a place vulnerable by electromagnetic interference, it is better to use shielded cable or double-twisted cable as the signal line of the wire controller. 3.2 ELECTRIC WIRING DESIGN GK-H03NH3AS、GK-H5.5NH3AS...
  • Page 44: Adjust The Tightness Of The Belt (Only Above 10 Ton)

    GREE ROOFTOP PACKAGED GK-H5.5NH3AF、GK-H10NH3AF、GK-H15NH3AF、GK-H20NH3AF 4 Adjust the Tightness of the Belt (Only above 10 Ton) (1) The rotation of the fan is achieved by the transmission of the belt. The velocity and stability of the fan is associated with the tightness of the belt and the tightness should be adjusted after a period of time.
  • Page 45 GREE ROOFTOP PACKAGED GK-H20NH3AF Diameter of the Diameter of The total Tension(N) Section area Deviation small the big length of the of the belt length(mm) Min. Max. wheel(mm) wheel(mm) belt(mm) 1482 1457 1482 1432 1457 1500 Note: Above diagrams may be different from actual model.
  • Page 46 GREE ROOFTOP PACKAGED MAINTENANCE...
  • Page 47: Maintenance

    GREE ROOFTOP PACKAGED MAINTENANCE 1 MALFUNCTION TABLE 1.1 MAIN CONTROL MALFUNCTION Table 1 Fault Display on Wired Controller Origin of Error Malfunction malfunction Control description code name signal When unit detects the high pressure switch is cut off for 3s successively, high pressure protection will occur.
  • Page 48 GREE ROOFTOP PACKAGED Origin of Error Malfunction malfunction Control description code name signal If the indoor ambient temperature sensor is detected of open Malfunction of circuit or short circuit for 5s successively, indoor ambient Indoor indoor ambient temperature sensor malfunction will be reported. The unit can...
  • Page 49: Description Of Drive Malfunction

    GREE ROOFTOP PACKAGED Origin of Error Malfunction malfunction Control description code name signal If the unit does not receive signal from condenser fan motor for 30s successively when the fan motor is operating, condenser fan Malfunction of motor malfunction will be reported. In this case, the unit can...
  • Page 50 GREE ROOFTOP PACKAGED Malfunction Item Wired Controller Display Unit display of dual 8 numeral tube Condenser Fan AC current protection (input side) Condenser Fan IPM module protection Condenser Fan PFC abnormality Condenser Fan startup failure Condenser Fan Missing phase Condenser Fan Drive module resetting...
  • Page 51: Flow Chart Of Troubleshooting

    GREE ROOFTOP PACKAGED 2 FLOW CHART OF TROUBLESHOOTING 2.1 TROUBLESHOOTING FLOW CHART OF MAIN CONTROL MALFUNCTION  E1 High Pressure Protection protection Reconnect wire according to the circuit diagram Check if the system high Check if the wiring Check if the high...
  • Page 52 GREE ROOFTOP PACKAGED E3 protection Enter Charge debugging mode refrigerant through wired Check if the according to the controller and select system low requirement and without refrigerant pressure is lower then turn on the unit lacking protection; then than 0.05MPa...
  • Page 53 GREE ROOFTOP PACKAGED  E4 Discharge Protection E4 protection Replace the discharge temperature sensor Check if the discharge Check if the temperature around discharge Replace the outdoor compressor discharge temperature sensor main control board temperature sensor is normal exceeds 115℃...
  • Page 54 GREE ROOFTOP PACKAGED  E6 Communication Malfunction Communication malfunction Check if the communication wire between indoor mainboard and Reconnect the outdoor mainboard or between indoor communication wire mainboard and wired controller is connected well Check if there is open circuit in the communication...
  • Page 55 GREE ROOFTOP PACKAGED  F0 Malfunction of Indoor Ambient Temperature Sensor Malfunction of indoor ambient temperature sensor Check if the indoor ambient temperature Correctly insert the sensor on mainboard is inserted temperature sensor on the needle on the needle stand...
  • Page 56 GREE ROOFTOP PACKAGED  F2 Malfunction of Condenser Temperature Sensor Malfunction of condenser temperature sensor Check if the condenser Correctly insert the temperature sensor on temperature sensor mainboard is inserted on the on the needle stand needle stand correctly Disconnect...
  • Page 57 GREE ROOFTOP PACKAGED  F4 Malfunction of Discharge Temperature Sensor Malfunction of discharge temperature sensor Check if the Correctly insert the discharge temperature sensor on temperature sensor mainboard is inserted on the on the needle stand needle stand correctly Disconnect...
  • Page 58 GREE ROOFTOP PACKAGED  H6 Malfunction of Outdoor Fan Motor Malfunction of Outdoor Fan Motor Check if the Correctly connect the control wire of outdoor fan motor is control wire of fan motor connected on the outdoor on the mainboard...
  • Page 59: Troubleshooting Flow Chart Of Drive Malfunction

    GREE ROOFTOP PACKAGED  E8 Malfunction of Indoor Fan Motor Malfunction of indoor fan motor Check if the Correctly connect the control wire of indoor fan motor is control wire of fan motor connected on the outdoor on the mainboard...
  • Page 60 GREE ROOFTOP PACKAGED  PH DC busbar over-voltage protection  PL DC busbar under-voltage protection PH or PL is displayed on the wired controller PH or PL is displayed in the mainboard 88 indicating lamp Is input voltage ranged from 185VAC...
  • Page 61 GREE ROOFTOP PACKAGED  P5 Compressor current protection  H7 Compressor motor desynchronizing  H5 IPM protection  Ld Phase loss P5, H7, H5 or Ld is displayed on the wired controller P5, H7, H5 or Ld is displayed in the mainboard 88...
  • Page 62 GREE ROOFTOP PACKAGED  ee driving board chip error  H6 DC fan error H6 is displayed on the wired controller H6 is displayed in the mainboard 88 indicating lamp Is the motor phase sequence Adjust the motor right? phase sequence Tighten the fan Is the Fan wire terminal loose?...
  • Page 63: Wiring Diagram

    GREE ROOFTOP PACKAGED 3 WIRING DIAGRAM The actual wiring should always refer to the wiring diagram of the unit. Model: GK-H03NH3AS Note: Above data is subject to change without notice.
  • Page 64 GREE ROOFTOP PACKAGED Model: GK-H5.5NH3AS Note: Above data is subject to change without notice.
  • Page 65 GREE ROOFTOP PACKAGED Model: GK-H5.5NH3AF Note: Above data is subject to change without notice.
  • Page 66 GREE ROOFTOP PACKAGED Model: GK-H10NH3AF Note: Above data is subject to change without notice.
  • Page 67 GREE ROOFTOP PACKAGED Model: GK-H15NH3AF Note: Above data is subject to change without notice.
  • Page 68 GREE ROOFTOP PACKAGED Model: GK-H20NH3AF Note: Above data is subject to change without notice.
  • Page 69: Disassembly And Assembly Procedure Of Main Parts

    ROOFTOP PACKAGED 4 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS 4.1 Model: GK-H03NH3AS Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor.
  • Page 70 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction  Unscrew the nuts on compressor base with a wrench 5.
  • Page 71 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction  9. Re-install the Put the cover plate back and tighten the screws.
  • Page 72 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew the screw (indcated by the arrow) fixing fan to take the fan out.
  • Page 73 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  7. Re-install the Put the cover plate back and tighten the screws.
  • Page 74 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  3. Remove the Unscrew the screws on fan...
  • Page 75 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction 7. Install the fan  Install the fan volute.
  • Page 76 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off before removal. Step Illustration Handling Instruction connection lines of motor.  Unscrew the screws (indicated by the arrows),and then take down the electric 5.
  • Page 77 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off before removal. Step Illustration Handling Instruction  9. Re-install the Put the side plate back and tighten the screws.
  • Page 78 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction  Heat the connection pipes 4. Cut off the...
  • Page 79 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction such as fan.  9. Re-install the Put the cover plate back and tighten the screws.
  • Page 80 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew the screw (indcated by the arrow) fixing fan to take the fan out.
  • Page 81 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Put the cover plate back and 7.
  • Page 82 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew holding bolt(indicated 3. Take down the...
  • Page 83 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction 7. Fix the fan  Then screw down the holding sub-assembly on bolt with a wrench.
  • Page 84 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off before removal. Step Illustration Handling Instruction  Pull out power cord or disconnect the power cord after unscrewing the screws.
  • Page 85 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off before removal. Step Illustration Handling Instruction  7. Re-install the Put the electric box back and tighten the screws.
  • Page 86 GREE ROOFTOP PACKAGED 4.3 Model: GK-H10NH3AF Model: GK-H10NH3AF Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction Connect vacuum recovery tank with nozzle for adding freon for 1.
  • Page 87 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction 4. Cut off the Heat the connection pipes...
  • Page 88 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction cord. The line connection must accord to the schematic diagram.
  • Page 89 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew the screws fixing 2. Take out the cover plate (indicated by cover plate.
  • Page 90 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Put the repaired or replaced motor onto brakcet as the direction during removing.
  • Page 91 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew the screws fixing cover plate .Lift the handles, 1.
  • Page 92 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew the holding screw of...
  • Page 93 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction 7. Fix the fan  Then screw down the holding sub-assembly on bolt with a wrench.
  • Page 94 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off before removal. Step Illustration Handling Instruction  Unscrew the screws fixing side plate. Lift the handles, slightly 1.
  • Page 95 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off before removal. Step Illustration Handling Instruction  Unscrew the screws (indicated by the arrows),and then take down the electric box.
  • Page 96 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off before removal. Step Illustration Handling Instruction  Re-connect power cord according to wiring diagram adhered on eletric box.
  • Page 97 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction  Unscrew the screws fixing side 2.
  • Page 98 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction  Unscrew the nuts on compressor 6.
  • Page 99 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction  put the axial fan assy back with lifting 9.
  • Page 100 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Disconnect all connection lines between motor and elements in electric box.
  • Page 101 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Put the cover plate back and tighten 7.
  • Page 102 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew the screws fixing air duct 3.
  • Page 103 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew the screws fixing fan 7.
  • Page 104 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew position control bolts of motors bracket (indicated by the 12.
  • Page 105 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  16. Re-install the Put the cover plate back and tighten cover plate.
  • Page 106 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off bef ore removal. Step Illustration Handling Instruction  Unscrew the screws fixing 3. Take out cover (indicated by the the electric arrows).Then take out the...
  • Page 107 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off bef ore removal. Step Illustration Handling Instruction  Re-connect power cord according to wiring diagram adhered on eletric box.
  • Page 108 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction Screws Screws  Unscrew the screws fixing cover 2.
  • Page 109 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction  Unscrew the nuts on compressor 6.
  • Page 110 GREE ROOFTOP PACKAGED Disassembly and Assembly of Compressor Remark: Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal of the compressor. Step Illustration Handling Instruction  Reconnect the power cord into...
  • Page 111 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew the screws fixing cover 2.
  • Page 112 GREE ROOFTOP PACKAGED Disassembly and Assembly of Condenser Fan Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Re-install fan blade and screw down the holidng bolt indicated by the arrow with a wrench.
  • Page 113 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew the screws fixing side plate 2.
  • Page 114 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Anticlockwise screw the 2 bolts...
  • Page 115 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction Nuts  Re-assemble repaired or replaced motor.
  • Page 116 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  Unscrew position control bolts of motors bracket (indicated by the 14.
  • Page 117 GREE ROOFTOP PACKAGED Disassembly and Assembly of Supply Blower Motor Remark: Make sure that the unit is stopped running and power supply is cut off before removal of the motor. Step Illustration Handling Instruction  18. Re-install the Put the cover plate back and tighten cover plate.
  • Page 118 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off before removal . Step Illustration Handling Instruction  Unscrew the screws fixing cover 3. Take out the electric (indicated by the arrows).Then take...
  • Page 119 GREE ROOFTOP PACKAGED Disassembly and Assembly of Electric Box Remark: Make sure that the unit is stopped running and power supply is cut off before removal . Step Illustration Handling Instruction  Put the side plate back and tighten 8. Re-install the side plate.
  • Page 120: Exploded Views And Spare Part List

    GREE ROOFTOP PACKAGED 5 EXPLODED VIEWS AND SPARE PART LIST Model: GK-H03NH3AS GK-H03NH3AS Name of Part Product Code EJ51000660 Part Code Quantity Main Board '300027060219 Main Board '30221000026 Radiator 430034000014 Main Board '300002060345 Main Board '30223000046 Radiator 49018000001 Terminal Board...
  • Page 121 GREE ROOFTOP PACKAGED GK-H03NH3AS Name of Part Product Code EJ51000660 Part Code Quantity Terminal Board '42200000000701 Electric Box Assy '100002061827 Air Outlet Panel '012233060008P Filter Sub-Assy '11100100000602 Evaporator Assy '011001060257 Clapboard Sub-Assy '017021060114P Filter Sub-Assy 111001000086 Side Plate '017110060027P Side Plate...
  • Page 122 GREE ROOFTOP PACKAGED Model: GK-H5.5NH3AS GK-H5.5NH3AS Name of Part Product Code EJ51000740 Part Code Quantity Radiator '430034000004 ‘300027060479 Main Board Power Switch '300012060010 Radiator '49018000001 ’30223000046 Main Board ‘300027060219 Main Board Filter Board '300020000003 Terminal Board '422000060003 Terminal Board '42200000000701...
  • Page 123 GREE ROOFTOP PACKAGED GK-H5.5NH3AS Name of Part Product Code EJ51000740 Part Code Quantity Filter Sub-Assy '11100100000602 Evaporator Assy '011001060249 Clapboard Sub-Assy '017021060114P Side Plate '017110060027P Side Plate '017110060026P Handle '26235253 Rear Grill '016001060024 Filter Sub-Assy '111001000086 Water Tray Sub-Assy '017055060072P...
  • Page 124 GREE ROOFTOP PACKAGED Model: GK-H5.5NH3AF GK-H5.5NH3AF Name of Part Product Code EJ51000650 Part Code Quantity Radiator '4901800000201 Main Board '300027060204 Reactor '43138000049 Rectifier '46010604 AC Contactor '44010265 Radiator '49018000001 Main Board '30223000046 Filter Board '30228000032 Terminal Board '42200006000303 Terminal Board...
  • Page 125 GREE ROOFTOP PACKAGED GK-H5.5NH3AF Name of Part Product Code EJ51000650 Part Code Quantity Side Plate '017110060027P Side Plate '017110060026P Handle '26235253 Clapboard Sub-Assy '017021060114P Water Tray Sub-Assy '017055060072P Base Plate Sub-Assy '017000060116P Gas-Liquid Separator 07423902 Compressor and Fittings 00209400005 Choke Plug of Drain Pipe...
  • Page 126 GREE ROOFTOP PACKAGED Model: GK-H10NH3AF GK-H10NH3AF Name of Part Product Code EJ51000710 Part Code Quantity Filter Sub-Assy '11100100000603 Handle '26235253 Side Plate '017110060045P Side Plate '017110060044P Rear Grill '016001060029 Air Outlet Panel Sub-Assy '017097060008P Choke Plug of Drain Pipe '76712455...
  • Page 127 GREE ROOFTOP PACKAGED GK-H10NH3AF Name of Part Product Code EJ51000710 Part Code Quantity Clapboard Sub-Assy '017021060182P Nozzle for Adding Freon '06130002 Compressor and Fittings '009001060108 Gas-Liquid Separator '07424188 Base Frame Assy '000043060104 Pressure Switch '4602001531 4-Way Valve '43000339 Condenser Assy...
  • Page 128 GREE ROOFTOP PACKAGED Model: GK-H15NH3AF GK-H15NH3AF Name of Part Product Code EJ51000700 Part Code Quantity Coping '012049060036P Rear Grill 1 '016001000006 Diversion Circle '012193000001P Axial Flow Fan '10434100007 Fan Motor '150101000054 Air Scroll '012277060013P Blower '15018317 Evaporator Assy '011001060425 Filter Sub-Assy...
  • Page 129 GREE ROOFTOP PACKAGED GK-H15NH3AF Name of Part Product Code EJ51000700 Part Code Quantity Terminal Board '42011103 Terminal Board '42200000000701 Phase Reverse Protector '32214101 Terminal Board '42018000558 AC Contactor '44010226 Side Plate '017110060050P Filter Board '30228000032 Chassis Sub-Assy '017000060196P Chassis Sub-Assy...
  • Page 130 GREE ROOFTOP PACKAGED Model: GK-H20NH3AF GK-H20NH3AF Name of Part Product Code EJ51000720 Part Code Quantity Rear Grill 1 '016001000006 Diversion Circle '012193000001P Top Cover '012148060067P Top Cover '012148060066P Air Outlet Panel '012233060016P Blower '15018319 Filter Sub-Assy '111001060061 Evaporator Assy '011001060442...
  • Page 131 GREE ROOFTOP PACKAGED GK-H20NH3AF Name of Part Product Code EJ51000720 Part Code Quantity Radiator '4901800008001 Main Board '300027060235 Terminal Board '42018000558 Terminal Board '42200000000701 Terminal Board '42200000001601 Terminal Board '42200006000303 Anti-phase Protector '46020066 Terminal Board '42011103 Main Board '300027060219 Side Plate...
  • Page 132 GRUPO CONFORT NACIONAL, S.A. de C.V. Blvd. Lazaro Cardenas #537 Fracc. Jardines del Lago Cp. 21330, Mexicali B.Cfa. Tel. (686) 557- 5777 Sucursal: Tijuana, B.C. Sucursal: Hermosillo, Son. Sucursal: Guadalajara, Jal. Sucursal Mexicali Vía Rápida Oriente Zona del Rio Juan de Dios Bojórquez 1-B Ángel Romero No.