Poe buffer power supply for up to 16 ip cameras. (8 pages)
Summary of Contents for Pulsar DSOS24V-PRA
Page 1
1438 Power supply unit for fire systems used DSOS24V-PRA type Declared performance: Fire safety. Certificate of constancy of performance: 1438-CPR-1019 Certificate of approval: 5402/2024 Compliant: EN 54-4:1997+ AC:1999 + A1:2002 + A2:2006 USER MANUAL Edition: 1 from 09.07.2023 Supersedes edition: ------ DSOS24V-PRA v.1.0...
Page 2
DSOS24V-PRA GENERAL SAFETY RULES Before installation, read the instruction manual to avoid errors that can damage the device and give you an electric shock. Before installation, cut off the voltage in the 230 V power-supply circuit. To switch power off, use an external switch, in which the distance between the contacts of all poles in the disconnection state is not less than 3 mm.
DSOS24V-PRA 1. Features. Conformity with Battery overcharge protection Battery output protection against short circuit and EN 54-4:1997+AC:1999+A1:2002+A2:2006, and pt. 12.2 according to Decree of the Ministry of Internal reverse connection Output voltage control Affairs and Administration of 20.06.2007 (Journal of ...
DSOS24V-PRA 2. Functional requirements of the PSU. The buffer power supply for fire alarm systems has been designed in accordance with the following standards: - EN 54-4:1997+AC:1999+A1:2002+A2:2006 fire detection and fire alarm systems. - pt. 12.2 according to Decree of the Ministry of Internal Affairs and Administration of 20.06.2007 (Journal of Laws No.
4. Technical description. 4.1. General description. DSOS24V-PRA is designed for uninterruptible power supply of call stations (firefighter’s microphone) used in DSO (Voice Alarm Systems) requiring stabilized voltage of 48 V DC (-5%/+5%). In case of lack of main power, battery back-up is activated immediately. Power supply unit is placed in metal enclosure (color red RAL 3001) with space for 2x 17Ah/12V batteries.
DSOS24V-PRA 4.3. Description of PSU components and connectors. Table 2. Description of components and connectors. Element Description LEDs - optical indication: – AC voltage – output voltage 24 V DC FAILURE – common failure Microphone hanging point (mounting plate included with PRA-CSLW station) Space for PRA-CSLW microphone station Space for PRA-CSE extensions, max.
DSOS24V-PRA 5. Installation. 5.1. Requirements. Buffer power supply is designed to be installed only by qualified installer with necessary permits and authorisations (required in installation country) to connect (interfere) with the 230 V mains supply. Because the power supply is designed for the continuous operation and is not equipped with ON/OFF switch, the power supply circuit should have the appropriate overload protection.
DSOS24V-PRA 5.2. Installation procedure. CAUTION Before installation, cut off voltage in 230 V power-supply circuit. To switch power off, use an external switch, in which distance between contacts of all poles in disconnection state is not less than 3mm.
DSOS24V-PRA 5.3. Procedure for checking power supply. Check indication displayed on front panel of power supply unit: a) 230 V AC LED should remain lit to indicate presence of mains supply voltage. b) LED DC should remain lit to indicate presence of supply voltage.
DSOS24V-PRA 6. Functions. 6.1. Optical indication. The power supply is equipped with three LEDs on the front panel: AC voltage on – the PSU is supplied with 230 V AC off – no 230V AC supply Output voltage 48 V DC ...
DSOS24V-PRA Fig. 10. Technical output ALARM. CAUTION! The figure set of contacts shows a potential-free status of relay, which corresponds to power supply failur. 6.3 Common failure input EXTi. EXT IN (external input) technical input indicating common failure is intended for additional, external devices that generate failure signal.
DSOS24V-PRA 7. Reserve power supply circuit. PSU is fitted with intelligent circuits: battery charging circuit with function of accelerated charging and battery control, which main task is to monitor condition of batteries and connections in circuit. If controller detects a power failure in battery circuit, appropriate indication and change of ALARM technical output.
DSOS24V-PRA Fig. 12. Mounting of temperature sensor. Nominal battery operating temperature recommended by many manufacturers is 25°C. Working at elevated temperatures will significantly shorten battery lifetime. Service life is reduced by half for each sustained temperature rise of 8°C above nominal temperature. This means that battery lifespan, when operated at 33°C, can be decreased by 50%!
DSOS24V-PRA 8. Specifications. Table 5. Electrical parameters. Supply voltage ~230 V Current consumption 0,34 A @230 V AC Power frequency 50 Hz Output power PSU 14,4 W Efficiency Rated voltage (-5%/+5%) 48 V DC Output current 300 mA 300 mΩ...
CAUTION! The power supply unit is adapted for cooperation with the sealed lead-acid batteries (SLA). After the operation period they must not be thrown but recycled according to the applicable law. Pulsar sp. j. Siedlec 150, 32-744 Łapczyca, Poland Tel.