DSO-PRA TABLE OF CONTENTS 1. SYSTEM FEATURES ..........................3 2. TECHNICAL DESCRIPTION......................4 2.1. G ................................ 4 ENERAL DESCRIPTION 2.2. E ................................4 LECTRICAL SCHEME 3. DESIGN OF VOICE ALARM SYSTEM..................... 5 4. COMPONENTS OF THE DSO CABINET..................7 4.1.
24U, standard for 36U, 42U, 45U, single-phase or 3-phase power supply 230 V AC LDxxxx voltage distribution terminal warranty for DSO-PRA cabin – 2 years from production date warranty for batteries – 1 year from installation date...
DSO-PRA 2. Technical description. 2.1. General description. 19" DSO-PRA RACK cabinet is designed for installation of PRAESENSA voice alarm system devices by Bosch. Devices of DSO system are placed in 19" RACK cabinet together with appropriate battery banks. Power supply from power grid can be supplied to cabinet in form of 1-phase or 3-phase connection, which depends on total power consumed by DSOdevices.
DSO-PRA 3. Design of Voice Alarm System. The design and all components of the DSO are based on the RACK 19" cabinet (Protection Class: IP30), containing all components of the system. Depending on the system and the number of devices, the height of the cabinet is adjusted individually.
DSO-PRA 4. Components of the DSO cabinet. Equipment of each DSO cabinet includes elements necessary for proper operation of system. These components, depending on their intended use, protect electrical system against overvoltage or short circuit, supply power to receivers, and ensure proper signaling or cooling of installed equipment in RACK cabinet.
Page 8
DSO-PRA Table 3. Components of the safety strip. Element Description A 230 V maintenance socket Overcurrent circuit breaker of 230 V maintenance socket Surge arresters Overcurrent circuit breaker of fan Main overcurrent circuit breaker Safety contact strip is connected to mains. Access is obtained by removing front cover. Connection to power system is shown below.
DSO-PRA 4.3. PSG3LA panel for optical and acoustic indication. The optional panel for optical and acoustic indication compliant with the PN-EN54-16 standard indicates the status of the entire DSO system. It is equipped with three LEDs, a sounder, and a reset button of acoustic indication.
DSO-PRA Table 7. Technical parameters of indication panel. 10÷30 V DC Supply voltage Current consumption 30mA Optical indication LED lights: – „CONTROL” Green – „ACOUSTIC INDICATION” – „FAILURE” Yellow Acoustic indication - Piezoelectric indicator ~60dB /1m Technical outputs: - „ACOUSTIC INDICATION”...
Page 12
DSO-PRA DSO cabinet is equipped with a ventilation panel located in upper part of housing to force air flow to heat emitting devices. Normally, ventilation panel is mounted in a 36U, 42U, 45U, 50U, and (optionally) 24U cabinet. Fans are controlled by a nearby bimetallic thermostat that allows setting activation temperature in range 0-60ºC with adjustment knob.
DSO-PRA 5. CONFI-DSO program for designers. CONFI-DSO software is a tool supporting design of power supplies for voice alarm systems. Configuration tool is designed for BOSCH PRAESENSA systems. Based on implemented design parameters, program selects a complete power supply system taking into account the required backup time.
230 / 400V AC and low-voltage installations. Installer should be trained in commissioning and operation of power supply system of DSO by Pulsar Company. Electrical system shall follow valid standards and regulations. DSO cabinet should be mounted in such a way to provide both front and rear access for service personnel.
Page 16
The data can be read remotely or locally by employees of the PULSAR company In the case of unjustified claim, the claimant may be charged with the travel and manhour costs of a PULSAR employee incurred by the PULSAR company.
Need help?