  • Page 1 Control Manual Group: Wall Mounted Part Number: CLIWP CM Date: May 20th, 2024 CLIWP Series Direct Expansion Unit with Scroll Compressor Model 3 RT / 5 RT Refrigerant R410A 60 Hz...
  • Page 2: Table Of Contents

    CONTENT NOMENCLATURE............3 GENERAL INFORMATION..........4 ANSI Z535.5 Definitions:..........5 LOYTEC CONTROL............6 Use And Operation Of The Hardware Interface...6 Quick Menu..............8 Control Operation............8 Bacnet/Ip Configuration..........10 BACNET IP TO MODBUS RS485 CONVERSION..13 THERMOSTAT LSTAT..........16 Use Wallpack System..........16 Alarms..............16 TROUBLESHOOTING..........18 EXPANSION VALVE COMMUNICATION....20 DRIVE................21 Switching From One Drive To Another.......21 USE THERMOSTAT LUXPRO P722UC......24 Front Panel Controls.............24 System Setting..............25...
  • Page 3: Nomenclature

    NOMENCLATURE CLIWP-036-AC-F-F-Y-Y-R-1-U-T-M-C-A-Y-Y-1-Y-G-X-4-Y-S-Y-Y-Y-Y CLIWP - Wall-Packaged Unit EXTENDED WARRANTY Y - None NOMINAL CAPACITY 036 - 36,000 Btu/h nominal cooling PLACE HOLDER 060 - 60,000 Btu/h nominal cooling Y - None OPERATING PLACE HOLDER AC - Air Conditioner Y - None THERMOSTAT 24V COMPRESSOR Y - None...
  • Page 4: General Information

    GENERAL INFORMATION ! WARNING ! ! WARNING ! Electric shock danger. If refrigerant leaks from the unit, there is a potential choking danger as the refrigerant will displace air in the immediate Improper handling of this equipment can cause personal area.
  • Page 5: Ansi Z535.5 Definitions

    GENERAL INFORMATION ANSI Z535.5 DEFINITIONS: ! DANGER ! Indicate[s] a hazardous situation which, if not avoided, will result in death or serious injury. The signal word “DANGER” is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.
  • Page 6: Loytec Control

    LOYTEC CONTROL The LIOB-585 I/O controllers are compact, IP-enabled, programmable automation stations designed for LonMark systems and BACnet/ IP networks, featuring physical inputs and outputs and an integrated graphical display (Figure 1). Figure 1. LIOB-585 controller front view. The LIOB-585 controller features a “power-saving” function that USE AND OPERATION OF THE HARDWARE INTERFACE may appear inactive or turned off.
  • Page 7: Quick Menu

    LOYTEC CONTROL Return to main menu. Status Led The status LED serves the purpose of indicating the current Figure 4. Device settings menu. operational status of the controller. This is achieved through two color-coded signals identified as: Green color: This LED indicates that the controller is in a healthy state according to the correct settings programmed.
  • Page 8: Control Operation

    LOYTEC CONTROL Table 1. Status led. Figure 6. Device settings. Addressing Wall-Mount To configure the IP address: Navigate to the IP address on the main screen and press the dial button to select, (See Figure 7). CONTROL OPERATION Communication Figure 7. LIOB-550 Main screen.
  • Page 9 LOYTEC CONTROL IoT Integration Hardware An LIOB-58x I/O controller is linked to a BACnet network via the The IoT function (Node.js) enables the system to establish Ethernet/IP port of the L-IOB device. To power the device, an connections with a wide range of cloud services, facilitating tasks LPOW-2415A power supply, for instance, should be utilized.
  • Page 10: Bacnet/Ip Configuration

    LOYTEC CONTROL The subsequent screen will appear, displaying the configu- BACnet/IP CONFIGURATION ration data (See Figure 12). Access the LOYTEC web page configuration. Upon entry, the system will request the following information (See Fig- Figure 12. Configuration settings. ure 9): User: admin Password: loytec4u Figure 9.
  • Page 11 LOYTEC CONTROL Configuration for communication port See Table 4 for the options provided by this configuration. From the Config menu, choose the Port Config configura- tion type. Table 4. BACnet settings. Please proceed to the Ethernet 1 (LAN) tab, see Figure 13 for detail of options portal.
  • Page 12 LOYTEC CONTROL Wallpack(Loytec Control) VS Condenser + Economizer Características: Control Exv • Control Low Ambient • Control de Economizador • Protección: INTERRUPTORES DE PRESIÓN Presión de Pressión de Activación Activación Reinicio Automático Superior [bar] Inferior [bar] HP (061F7517) 42.00 33.00 STST (NC) LP (061F6107) 6.00...
  • Page 13: Bacnet Ip To Modbus Rs485 Conversion

    BACNET IP TO MODBUS RS485 CONVERSION NOTICE IMPORTANT: THIS CONFIGURATION IS OPTIONAL, ONLY IF THE CUSTOMER REQUIRES IT AND IF IT IS APPLICABLE TO THE MODEL HE HAS IN THE FIELD. Table 5. Loytec Inputs And Outputs NAME NOMENCLATURE SENSOR TYPE PHYSICS (TRIAC) (500 Pa)
  • Page 14 BACNET IP TO MODBUS RS485 CONVERSION IP address configuration of the LIOB-585 controller Upon selecting the previous menu, you will enter the de- vice’s IP configuration. Follow procedure to modify IP ad- To ensure effective communication with the MODBUS converter, dress and confirm (Figure 20): it is essential to configure the controller’s IP address so that the Figure 19.
  • Page 15 BACNET IP TO MODBUS RS485 CONVERSION Remote Config: This parameter allows for the selection of • remote configuration of the device. In the event of having a VPN connection, it will allow for remote configuration of the device. Save: This parameter allows you to save the network con- •...
  • Page 16: Thermostat Lstat

    THERMOSTAT LSTAT Once the previous step is completed, the display screen will USE WALLPACK SYSTEM change (See Figure 22). The system features a digital thermostat that can be used as a temperature sensor, by default, is configured to turn on the Figure 22.
  • Page 17 THERMOSTAT LSTAT Outdoor temperature probe alarm: BACNET/IP communication is carried out using an RJ45 Ethernet cable that can be connected to a LOCAL network or a DHCP This alarm will be present when the ambient temperature probe is network with the Internet. Through this port, different information in a defective or broken state, and it will be represented through from the controller can be obtained.
  • Page 18: Troubleshooting

    TROUBLESHOOTING The Wallpack unit equipped with Loytec features various types of alarms designed to prevent equipment damage and provide protection. It’s important to understand that tampering with or bypassing any of these alarms could lead to the equipment operating without adequate protection, potentially resulting in permanent failures.
  • Page 19 TROUBLESHOOTING Table 6. Troubleshooting chart. CODE NAME DESCRIPTION POSSIBLE SOLUTIONS Verify that the high and low pressure signals are electrically wired. Check continuity of the signals electrically and verify false contacts. Verify pressures with pressure gauges and check pressures according to High Pressure data sheet.
  • Page 20: Expansion Valve Communication

    EXPANSION VALVE COMMUNICATION The Wallpack unit features electronic valve control, enabling Figure 27. Device Information . refrigerant control during equipment operation. This valve communicates via Modbus (See Figure 26). Figure 26. Communication . If the two RS-485 devices are not present, proceed to configure the EXV Twin Carel device.
  • Page 21: Drive

    DRIVE SWITCHING FROM ONE DRIVE TO ANOTHER Network Address The network address assigns the controller an address for serial Figure 30. Drive. connection to a supervisory system via RS485 and to a pCO controller via pLAN, tLAN, Modbus. It is a common parameter for both driver A and B (See Table 7).
  • Page 22 DRIVE Pressure Probe S1 and S2 Main Control When configuring the primary control, the operational mode of To define the measuring range and alarm range for driver A each driver is established. This includes setting the superheat and driver B, set the type of pressure probe as S1 for driver A set point, configuring PID control parameters, defining protector and S2 for driver B.
  • Page 23 DRIVE By pressing the down key, scroll the regulation menu to Figure 35. Adjustment screen. number 1. Press enter and use the up and down keys to select the desired super heat setpoint, then press the enter key and then the esc key to return to the menu selection (Figure 33).
  • Page 24: Use Thermostat Luxpro P722Uc

    USE THERMOSTAT LUXPRO P722UC FRONT PANEL CONTROLS NOTICE Figure 36. Thermostat control. IMPORTANT: THIS PRODUCT IS NOT SUPPLY BY THE MANUFACTURER, UNLESS THIS THERMOSTAT MODEL IS REQUESTED. The electrical rating for this thermostat is 1.5 A per terminal, with a maximum total combined load of 3.0A for all terminals combined.
  • Page 25: System Setting

    USE THERMOSTAT LUXPRO P722UC For heat pump systems: this button activates the Emergency Item #05 (Early recovery): Heat mode and prevents the outdoor unit from running. For conventional systems (without heat pumps), this button will have [Off, default] Temperature schedule values begin to be presented no effect on the normal RUN mode (Figure 36).
  • Page 26: Standar Control Operation

    USE THERMOSTAT LUXPRO P722UC switch is normally closed (NC) and opens during a low-pressure Temperature Programming event. To set a temperature program, choose the cooling mode. Phase Detector (PD) – Phase Detector control module is Move the setting slide switch to TEMP PROG mode. The standard in all air conditioner units, and interrupts unit operation programming will start on a Monday.
  • Page 27: Control Diagrams 208-2230/1/60

    CONTROL DIAGRAMS 208-2230/1/60 Figure 38. Control Diagram Wallpack 3 and 5 RT 208-230/1/60 Title/ Titulo: Dim Units/Unidades: Size/ Tamaño: Ing. Juan Jose Perez Customer/ Cliente: Logo: Designer/ Diseñador: CONTROL DIAGRAM MO/OF: WALLPACK 3&5 TR 220-1-60 Tolerances/ Tolerancias: Scale/ Escala: Ing. Agustin Espinoza Reviewer/ Revisor: Dwg num/ Num dibujo : Doc.
  • Page 28 CONTROL DIAGRAMS 208-2230/1/60 Figure 40. Thermostat Diagram Wallpack 3 and 5 RT 208-230/1/60 Title/ Titulo: Size/ Tamaño: Dim Units/Unidades: Ing. Juan Jose Perez Customer/ Cliente: Logo: Designer/ Diseñador: THERMOSTAT DIAGRAM MO/OF: WALLPACK 3&5 TR 220-1-60 Tolerances/ Tolerancias: Scale/ Escala: Ing. Agustin Espinoza Reviewer/ Revisor: Dwg num/ Num dibujo : Doc.
  • Page 29 CONTROL DIAGRAMS 208-2230/1/60 Figure 42. Loytec Control Diagram Wallpack 3 and 5 RT 208-230/1/60 Title/ Titulo: Dim Units/Unidades: Size/ Tamaño: Customer/ Cliente: Logo: Ing. Juan Jose Perez Designer/ Diseñador: LOYTEC CONTROL DIAGRAM MO/OF: WALLPACK 3&5 TR 220-1-60 Tolerances/ Tolerancias: Scale/ Escala: Reviewer/ Revisor: Ing.
  • Page 30: Control Diagrams 208-2230/3/60

    CONTROL DIAGRAMS 208-2230/3/60 Figure 43. Control Diagram Wallpack 3 and 5 RT 208-230/3/60 Title/ Titulo: Dim Units/Unidades: Size/ Tamaño: Ing. Juan Jose Perez Customer/ Cliente: Logo: Designer/ Diseñador: CONTROL DIAGRAM MO/OF: WALLPACK 3&5 TR 220-3-60 Tolerances/ Tolerancias: Scale/ Escala: Ing. Agustin Espinoza Reviewer/ Revisor: Figure 44.
  • Page 31 CONTROL DIAGRAMS 208-2230/3/60 Figure 45. Thermostat Diagram Wallpack 3 and 5 RT 208-230/3/60 Title/ Titulo: Dim Units/Unidades: Size/ Tamaño: Customer/ Cliente: Logo: Designer/ Diseñador: Ing. Juan Jose Perez THERMOSTAT DIAGRAM MO/OF: Figure 46. Loytec and Heater Control Diagram Wallpack 3 and 5 RT 208-230/3/60 WALLPACK 3&5 TR 220-3-60 Tolerances/ Tolerancias: Scale/ Escala:...
  • Page 32 CONTROL DIAGRAMS 208-230/3/60 Figure 47. Loytec Control Diagram Wallpack 3 and 5 RT 208-230/3/60 Title/ Titulo: Dim Units/Unidades: Size/ Tamaño: Ing. Juan Jose Perez Customer/ Cliente: Logo: Designer/ Diseñador: LOYTEC CONTROL DIAGRAM MO/OF: WALLPACK 3&5 TR 220-3-60 Tolerances/ Tolerancias: Scale/ Escala: Ing.
  • Page 33: Control Diagrams 460/3/60

    CONTROL DIAGRAMS 460/3/60 Figure 48. Control Diagram Wallpack 3 and 5 RT 460/3/60 Title/ Titulo: Dim Units/Unidades: Size/ Tamaño: Customer/ Cliente: Logo: Designer/ Diseñador: Ing. Juan Jose Perez CONTROL DIAGRAM MO/OF: WALLPACK 3&5 TR 460-3-60 Tolerances/ Tolerancias: Scale/ Escala: Reviewer/ Revisor: Ing.
  • Page 34 CONTROL DIAGRAMS 460/3/60 Figure 50. Thermostat Diagram Wallpack 3 and 5 RT 460/3/60 Title/ Titulo: Dim Units/Unidades: Size/ Tamaño: Ing. Juan Jose Perez Customer/ Cliente: Logo: Designer/ Diseñador: THERMOSTAT DIAGRAM MO/OF: WALLPACK 3&5 TR 460-3-60 Tolerances/ Tolerancias: Scale/ Escala: Ing. Agustin Espinoza Reviewer/ Revisor: Dwg num/ Num dibujo : Doc.
  • Page 35 CONTROL DIAGRAMS 460/3/60 Figure 52. Loytec Control Diagram Wallpack 3 and 5 RT 460/3/60 Title/ Titulo: Dim Units/Unidades: Size/ Tamaño: Customer/ Cliente: Logo: Designer/ Diseñador: Ing. Juan Jose Perez LOYTEC CONTROL DIAGRAM MO/OF: WALLPACK 3&5 TR 460-3-60 Tolerances/ Tolerancias: Scale/ Escala: Reviewer/ Revisor: Ing.
  • Page 36 cm-cliwp-cf-eng www.clima-flex.com.mx...