Redbusbar SmokeSight 10 Product Bulletin

Smoke alarm sensor, contaminant sensitivity

Advertisement

Quick Links

SmokeSight – Smoke alarm sensor, contaminant sensitivity
Symptom
3, low volume chirps every 40 to 50 secs. No corresponding LED indications. Chirping is local to an
individual smoke alarm unit.
Units affected
Only units that meet all of the following conditions are affected:
Part#SS10MANN or #SS10MAMA or SS10LNAN, and
Date of Manufacture DOM: 06-2020-01, and
Received by you before 27 Apr 2021
Safety Exposure
Nil
Problem
Smoke alarm has been exposed to lint or fibre contaminants, and
Internal smoke sensor, component failure threshold too high
Customer Action
If the symptoms above have been experienced:
Clean the smoke alarm, sensor chamber using a vacuum or clean, dry, compressed air
(available in a can). Do not use an air compressor as the air is not dry or clean. Place the
nozzle near the alarm lip and adjacent to the wording "To remove – Push rear tab <<< slide"
as follows:
U:\advertising\Smokey\SmokeSight_10_pb_2_r0.doc
SmokeSight 10
Product Bulletin No.2
30 Apr 2021
Page 1 of 2

Advertisement

loading
Need help?

Need help?

Do you have a question about the SmokeSight 10 and is the answer not in the manual?

Questions and answers

Summary of Contents for Redbusbar SmokeSight 10

  • Page 1 30 Apr 2021 SmokeSight 10 Product Bulletin No.2 SmokeSight – Smoke alarm sensor, contaminant sensitivity Symptom 3, low volume chirps every 40 to 50 secs. No corresponding LED indications. Chirping is local to an individual smoke alarm unit. Units affected Only units that meet all of the following conditions are affected: ...
  • Page 2 If the symptoms above have not been experienced:  If you wish, remove the SmokeSight alarm, remove the batteries, place in a dust free plastic bag and return to Redbusbar for reprogramming. The ceiling mounted base can remain installed. ...