Please check the equipment carefully for damage upon receipt and after removal 1.3 INTENDED USE of all packaging. 1.6 SAFETY ADVICE REGARDING TRANSPORTATION for any other use. For further advice please contact a DST representative. Warning! position the unit. •...
• connecting terminals in main components of the fan circuits When the unit is no longer in use, dismantle the unit and recycle the components according to local regulations. Contact a DST representative if you have any • during installation questions.
4. Regeneration heater power P motors 0.23kW P tot 4.3 kW I tot 10 A Electric heater P nom 4 kW Seibu Giken DST AB Avestagatan 33 16353 SPÅNGA, Sweden FIGURE 1: Type plate 2.2 MODEL DESIGNATION 1. Principle type RECUSORB RLZ-102R 2.
3.2 APPLICATIONS DST desiccant-type dehumidifiers are normally used where dry air is essential to the various manufacturing processes used in chemical, pharmaceutical, food or confectionery industries, or where a dry environment is required for the storing and handling of moisture-sensitive products and raw materials.
Position the machine with adequate working space around the unit to allow inspection and service. Size of unit and the position of the access panels/doors vary depending on the model. To avoid incorrect positioning, see the dimensional drawing in the appendix for service space and foot bolt-hole dimensions. 111547 - DC-50 EN.05 22.03 Seibu Giken DST...
4.4.4 Units with optional connections points for an electronic humidity controller or another regulator signal is marked on the electrical diagram. for more details. See electrical diagram for connections. Seibu Giken DST 111547 - DC-50 EN.05 22.03...
• Regeneration fan indicator* • MAN/AUTO indicator • Process fan indicator* Each indicator, standard or optional, are marked on the electrical diagram to indicate whether it is a normally closed or a normally opened circuit. 111547 - DC-50 EN.05 22.03 Seibu Giken DST...
Reset is only required when a operation is halted by hardware failure or triggered a safety mechanism. See troubleshooting for more information. See the electrical diagram for correct layout and information of the reset devices. 111547 - DC-50 EN.05 22.03 Seibu Giken DST...
7.1.3 HUMIDISTAT CONNECTION Use a 1-step humidistat for heating output in two steps (maximum power and zero power). One-step humidistat Mode Humidistat inputs Output Humidistat (Closed) Full power Humidistat (Opened) Zero power* Seibu Giken DST 111547 - DC-50 EN.05 22.03...
Mechanical thermostat TH1* – reset on thermostat. thermostats. See electrical diagram for the location of the thermostats. Attention! Attention! FIGURE 13: TH3 with reset button 7.4 REGENERATION AIRFLOW GUARD recommended. See for default setting. to locate the issue. 111547 - DC-50 EN.05 22.03 Seibu Giken DST...
The default time setting for the process fan is: ON (5 min) and OFF (55 min). Adjusting the time setting is only possible with a PLC installed, without a PLC the default time setting applies. Note: Included in Energy saving 2. Seibu Giken DST 111547 - DC-50 EN.05 22.03...
Operation can be checked by lowering control setpoint or switching to ‘manual’ operation. A circuit is preventing Check remote control is set to ‘On/Run’ position and if the cable is undamaged. not appear to be operating. operation. FIGURE 17: General troubleshooting table and solution 111547 - DC-50 EN.05 22.03 Seibu Giken DST...
Isolate mains electrical power supply to the unit. arrow on fan motor casing. The incoming Change over two of the three incoming phase supply wires. Re-check fan rotation. phase supply is incorrect. FIGURE 18: Capacity troubleshooting and solution table Seibu Giken DST 111547 - DC-50 EN.05 22.03...
The content of in this document may be subject to change without prior notice. For questions and comments regarding the content in this document, please send it to Number of electric heater steps Seibu Giken DST AB, ATT: Documentation, Avestagatan 33, 163 53 SPÅNGA, Heating power in steps [kW] SWEDEN.
Page 23
Component list DC-50R Description Type, Drwg No etc Qty. Art No Notes Rotor unit Rotor DMR 450H05 108251 1470x47x1 50SH Peripheral sealing 107955 Teflon sealing 35x203mm 106392 Teflon sealing 35x242mm 106393 Teflon sealing 35x243mm 106394 Hose clip length=1,5 m 103345...
Page 25
Harmful chemicals and solvents for rotors SEIBU GIKEN CO.,LTD. Reduced performance and/or rotor degradation is possible when adsorping the following substances. Chemical Substance Note Cause formula Oil vapor Cloggs the micro pores on the silica gel/zeolite. Ammonia 2ppm and above, prolonged exposure Degrades the silica gel/zeolite.
Page 28
Seibu Giken DST AB Avestagatan 33 | 163 53 Spånga, Sweden Phone: +46 8 445 77 20 | Fax: +46 8 445 77 39 info@dst-sg.com | www.dst-sg.com Seibu Giken DST is certified according to ISO 9001...