Omron P2RF S Datasheet

Screwless clamp terminal socket

Advertisement

Quick Links

Screwless Clamp Terminal Socket
P2RF@@S
• Screwless clamping greatly contributes to reducing wiring time.
• No over or under tightening of cable connection so better con-
tact reliability is achieved.
• Double wiring possible on all the terminals, and easy bridge and
branch connections.
• Use either solid or stranded wires from 0.2 to
1.5 mm
2
(AWG24 to AWG16).
• Safe terminal arrangement: Coil terminals separated from con-
tact terminals.
• Unique ejector enables easy relay replacement.
• Nameplate available
• Finger-protection
Ordering Information
■ List of Models
Socket
Clip & Release Lever
Nameplate
Socket Bridge
Specifications
■ Ratings/Characteristics
Item
Relay
Dimensions (W×H×D)
Rated voltage
Rated carry current
Applicable wires
Number of wire connections
Clamping force
■ Approved Standards
Standard
VDE0627 (IEC664, EN60999)
UL508 (UL1059)
CSA C22.2 No. 14 (CSA C22.2 No. 158)
1-pole for G2R1S
P2RF-05-S
P2RF05S
G2R-1-S Series
18×92×38.2 max.
10 A at 70°C
0.2 to 1.5 mm
Solid wire, Standard wire
2 wires per terminal (1 wire per hole)
10 N min. (0.2 mm
40002313UG
E87929
LR31928 (1281408)
P2RF-08-S
P2CM-S
R99-11
P2RM-SR, P2RM-SB
P2RF08S
G2R-2-S Series
250 VAC
5 A at 70°C
2
(AWG24 to AWG16)
2
), 40 N min. (1.5 mm
2
)
File No. (status)
Screwless Clamp Terminal Socket
2-pole for G2R2S
Remarks
---
---
---
VDE0627
---
---
EN60999
P2RF@@S
1

Advertisement

loading

Summary of Contents for Omron P2RF S

  • Page 1 Screwless Clamp Terminal Socket P2RF@@S • Screwless clamping greatly contributes to reducing wiring time. • No over or under tightening of cable connection so better con- tact reliability is achieved. • Double wiring possible on all the terminals, and easy bridge and branch connections.
  • Page 2 P2RF-05-S 38.2 max. 36.5 max. 32.6 27.6 22.6 Standard model (5.3) 28.5 61.3 TYP 18.0 max. 32.6 Option (with ejector and Option (with ejector and label attached) label attached) P2RF-08-S 38.2 max. 36.5 max. 32.6 27.6 (3.4) 22.6 Standard model (5.3)
  • Page 3: Terminal Arrangement

    60.6 TYP 55.7 56.9 28.6 28.6 (5.30) (5.30) ■ Accessories (Option) Socket Bridge for P2RF-S Clip and Release Lever for P2RF-S Insulating coating P2CM-S 16.8 TYP 40.1 TYP Diameter conductor 1.2 mm 6 TYP List of models (32.0) 36 TYP...
  • Page 4: Installation

    , AWG24 to AWG16 Applicable Wire Type Note: 1. If the outer diameter D of the wire is less than 2.2 mm and the exposed conductor length is less than 8mm potentially Solid wires, standard wires, flexible wires, or wires with ferules can bad connection might occur in case wire is pushed to far in- be used.
  • Page 5 ■ Wiring Wire connection hole Use wires of the applicable sizes specified above. The length of the exposed conductor should be 8 to 9 mm. Release hole Insert Screwdriver 8.5 ±0.5 mm Fig. 3 Section A-A of Fig. 2 Fig. 1 Exposed Conductor Length Use the following wiring procedure.
  • Page 6: Precautions For Connection

    ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. Cat. No. J132-E2-02-X...

This manual is also suitable for: