Setting Mode

3-2-5 Setup Menu (

FUNCTION
SETTING
32
)

Input Mode

All parameters will be set to default values if any change in made in this menu.
Selects the individual or phase-difference input.
The counting mode can be set to either individual input or phase-difference in-
put. Pulses of up to 50 kHz can be input. The minimum pulse width is 9 s for
both the ON and OFF sides.
Individual Inputs
This input mode counts by using input A as the increment input and input B as
the decrement input. The count is incremented at the rising edge of input A and
decremented at the rising edge of input B. The count is left unchanged if the in-
puts are simultaneous.
Input A
Input B
Count
Phase-difference Inputs
This input mode increments the count when input A precedes input B and decre-
ments the count when input B precedes input A. The count is incremented at the
rising edge of input B and decremented at the rising edge of input A.
Input A
Input B
Count
Setting
:
Individual input
:
Phase-difference input
Default
Section 3-2