Omron EJ1G User Manual page 121

Modular temperature controllers for gradient temperature control
Hide thumbs Also See for EJ1G:
Table of Contents

Advertisement

Programless Communications
Channel
CH1
CH2
Common
for both
CH1 and
CH2
Note
Data register
D0
Read Response Bits
D1
Setting Change Response Bits
D2
Operation Command Response Bits
D3
Communications Status
D4
Monitor Value A
D5
Monitor Value B
100
2. Make the PLC settings.
Use the GX Developer to make the settings outlined below for the commu-
nications port used.
Switch
Bit
number.
Position
Setting
SW01
b0
OFF
b1
ON
b2
ON
b3
ON
OFF
b4
b5
ON
b6
ON
b7
ON
b8 to b15
---
SW02
---
SW03
Same settings as SW01.
SW04
Same settings as SW02.
SW05
---
(1) To set a different baud rate from that given above, refer to Baud Rate Set-
ting on page 107 and change 0B.
(2) Refer to MELSEC-QnAS Series on page 107 if using a Communications
Module for the QnAS Series.
3. Make the EJ1G settings.
When using RS-232C, turn ON pin 8 on SW 2 (to select RS-232C) and
make the settings shown in the following table. No other settings are re-
quired.
Variable type
F0/B0
Programless Communications Protocol
Port C Send Wait Time
For the default settings, data registers in the PLC are allocated to the EJ1G
monitor and set values as shown in the following table. If the allocated words
shown below are already in use, change the words referring to Programless
Communications Upload/Download Data Area (Variable Type: F0/B0) on
page 104 and to Programless Communications Upload/Download Start
Address (Variable Type: F0/B0) on page 105.
Contents (monitor value)
Description
Transmission
Operation setting
setting
Data bits
Parity bit
Even/odd parity
Stop bits
Checksum
Write during RUN
Setting modifica-
tions
Communications
rate setting
Communications protocol setting
Station number setting
Parameter name
(Common)
(Common)
Data register
D500
Read Request Bits
D501
Setting Change Request Bits
D502
Operation Command Request
Bits
D503
Operation Command Code
D504
Set Value A
D505
Set Value B
Section 5-6
Set
value
Independent
0BEEH
8
Yes
Even
1
Yes
Allowed
Allowed
115200 bps (0BH)
MC protocol format 5 0005H
0
0000H
Setting/Monitor values
5:MC protocol (format 5)
1:1 ms
Contents (set value)