Refrigerant Circuit; Evaporator Airflow; Metering Device; Pressure Switches - Carrier PHR5 Installation Instructions Manual

15+ seer2 2-stage packaged heat pump system with r-410a refrigerant single and three phase 2-5 nominal tons (sizes 24-60)
Table of Contents

Advertisement

PHR5: Installation Instructions
with the proper electrical instrumentation. Refer to the unit wiring label
when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of operation in
this publication as an aid in determining proper control operation

Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil
accumulations annually. Detecting oil generally indicates a refrigerant
leak.
CAUTION
!
EXPLOSION, SAFETY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal injury, death or
equipment damage.
This system uses R-410A refrigerant which has higher operating
pressures than R-22 and other refrigerants. No other refrigerant may be
used in this system. Gauge set, hoses, and recovery system must be
designed to handle R-410A. If you are unsure, consult the equipment
manufacturer.
If oil is detected or if low cooling performance is suspected, leak-test all
refrigerant tubing using an electronic leak-detector, halide torch, or
liquid-soap solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low cooling performance is
suspected, refer to Checking and Adjusting Refrigerant Charge section.

Evaporator Airflow

The heating and/or cooling air-flow does not require checking unless
improper performance is suspected. If a problem exists, be sure that all
supply- and return-air grilles are open and free from obstructions, and
that the air filter is clean. When necessary, refer to Indoor Airflow and
Airflow Adjustments section to check the system airflow.

Metering Device

This unit uses 2 types of metering devices. The outdoor metering device
is a fixed orifice and is contained in the brass hex-body in each liquid
line feeding the outdoor coils. The indoor metering device is a TXV type
device.

Pressure Switches

Pressure switches are protective devices wired into the control circuit
(low voltage). They shut off compressor if abnormally high or low
pressures are present in the refrigeration circuit. These pressure switches
are specifically designed to operate with R-410A systems. R-22 pressure
switches must not be used as replacements for the R-410Aair
conditioner.

Loss of Charge Switch

This switch is located on the liquid line and protects against low suction
pressures caused by such events as loss of charge, low airflow across
indoor coil, dirty filters, etc. It opens on a pressure drop at about 20 psig.
If system pressure is above this, switch should be closed. To check
switch:
NOTE: Because these switches are attached to refrigeration system
under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem exists.
If switch must be removed, remove and recover all system charge so that
pressure gauges read 0 psi (0 Pa). Never open system without breaking
vacuum with dry nitrogen.

High-Pressure Switch

The high-pressure switch is located in the discharge line and protects
against excessive condenser coil pressure. It opens at 650 psig (31.1
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
kPa). High pressure may be caused by a dirty condenser coil, failed fan
motor, or condenser air recirculation.
To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohmmeter leads across switch. You should have continuity
on a good switch.

Copeland Scroll Compressor R-410A Refrigerant)

The compressor used in this product is specifically designed to operate
with R-410A refrigerant and cannot be interchanged.
The compressor is an electrical (as well as mechanical) device. Exercise
extreme caution when working near compressors. Power should be shut
off, if possible, for most troubleshooting techniques. Refrigerants
present additional safety hazards.
!
FIRE/EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death
and/or property damage.
Wear safety glasses and gloves when handling refrigerants. Keep
torches and other ignition sources away from refrigerants and oils.
The scroll compressor pumps refrigerant throughout the system by the
interaction of a stationary and an orbiting scroll. The scroll compressor
has no dynamic suction or discharge valves, and it is more tolerant of
stresses caused by debris, liquid slugging, and flooded starts. The
compressor is equipped with a noise reducing shutdown device and an
internal pressure relief port. The pressure relief port is a safety device,
designed to protect against extreme high pressure. The relief port has an
operating range between 550 (26.3 kPa) and 625 (29.9 kPa) psig
differential pressure.

Refrigerant

!
EXPLOSION, ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or
equipment damage.
This system uses R-410A refrigerant which has higher operating
pressures than R-22 and other refrigerants. No other refrigerant may be
used in this system. Gauge set, hoses, and recovery system must be
designed to handle R-410A. If you are unsure, consult the equipment
manufacturer.
This system uses R-410A refrigerant which has higher operating
pressures than R-22 and other refrigerants. No other refrigerant may be
used in this system. Gage set, hoses, and recovery system must be
designed to handle R-410A. If you are unsure, consult the equipment
manufacturer. Failure to use R-410A compatible servicing equipment or
replacement components may result in property damage or injury.

Compressor Oil

The Copeland scroll compressor uses 3MAF POE oil. If additional oil is
needed, use Uniqema RL32-3MAF. If this oil is not available, use
Copeland Ultra 32 CC or Mobil Arctic EAL22 CC. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE oils can absorb 15
times as much water as other oils designed for HCFC and CFC
refrigerants. Take all necessary precautions to avoid exposure of the oil
to the atmosphere.

Servicing Systems on Roofs with Synthetic Materials

POE (polyolester) compressor lubricants are known to cause long term
damage to some synthetic roofing materials. Exposure, even if
27
WARNING
CAUTION

Advertisement

Table of Contents
loading

Table of Contents