Image Wtchdg Flt; Constantsmsgivld; Constants Chksum; Nvs Checksum Flt - Carrier 19XR Start-Up And Service Instructions

Table of Contents

Advertisement

CONDITION
PORT
TYPE
CODE
Resettable
10118
10/11
Fault
11118
Resettable
10119
10/11
Fault
11119
Resettable
10120
10/11
Fault
11120
Resettable
12
12001

Image Wtchdg Flt

Fault
Resettable
12
12002

ConstantsMsgIvld

Fault
Non-Resettable
12
12003

Constants Chksum

Fault
Non-Resettable
12
12004

NVS Checksum Flt

Fault
Resettable
12
12005

Power Supply UV

Fault
Resettable
12
12006

Precharge Fault

Fault
Resettable
12
12007

MCS CL BayOTmp

Fault
Table 7 — Fault Codes by Port (cont)
DISPLAY
FAULT
TEXT
D-Axis Inductance at 0 Pct OutOfRange.
Parameter 10:910 [Autotune] is set to 3
'Rotate MtrID' and the value measured by
Ld00 Fail
the Autotune procedure for parameter
10:627 [u PM Ld at 0] is not in the range
of acceptable values (negative).
D-Axis Inductance at 100 Pct
OutOfRange. Parameter 10:910
[Autotune] is set to 3 'Rotate MtrID' and
Ld100 Fail
the value measured by the Autotune
procedure for parameter 10:629 [u PM Ld
at 100] is not in the range of acceptable
values (negative).
Q-Axis Inductance Out of Range.
Parameter 10:910 [Autotune] is set to 3
'Rotate MtrID' and the value measured by
the Autotune procedure for parameter
10:637 [u PM Lq at 25], 10:639 [u PM Lq
at 50], 10:641 [u PM Lq at 75], 10:643 [u
Lq Fail
PM Lq at 100], 10:645 [u PM Lq at 125],
10:647 [u PM Lq at 150], 10:649 [u PM Lq
at 175], or 10:651 [u PM Lq at 200] is not
in the range of acceptable values. This
could happen if current fails to rise up or
decreases too fast due to abnormal
conditions.
Image Watchdog Fault. Communication
between the main control board and the
image buffer in one of the power
peripherals (power layer interface board,
torque accuracy module, or DC
precharge board) has stopped
transmitting for 10 milliseconds.
Constants Message Invalid Fault. The
constants header information did not
match the content of the power peripheral
(power layer interface board, torque
accuracy module, or DC precharge
board).
Constants Checksum Fault. The
constants download failed the checksum
test by one of the power peripherals
(power layer interface board, torque
accuracy module, or DC precharge
board).
Nonvolatile Data Checksum Fault.
Checksum test failed for non-volatile data
for the DC precharge board.
Power Supply Undervoltage. An
undervoltage event occurred in the local
(internal to the PIB) power supply. A
possible cause is the DC bus voltage,
which feeds the power supply, has
dropped below 400-v DC. This power
supply provides power to the power layer
interface board or DC precharge board (if
present).
Precharge Fault. Main control board
firmware did not indicate that bus voltage
was good within the specified time period
following closure of the precharge
contactor.
MCS Failed to Close or Wiring Bay
Overtemp. Two conditions can cause
this fault:
Condition 1: The molded case switch
(MCS) in the DC precharge has failed
to close when commanded.
Condition 2: The temperature in the
input bay or entry wiring bay has risen
too high. This condition can only
cause the fault before the drive or bus
supply has completed precharge.
ACTION
Verify motor nameplate data and rerun
the rotate motor ID test. If fault
continues, obtain the motor datasheet
from motor vendor.
Verify motor nameplate data and rerun
the rotate motor ID test. If fault
continues, obtain the motor datasheet
from motor vendor.
Verify motor nameplate data and rerun
the rotate motor ID test. If fault
continues, obtain the motor datasheet
from motor vendor.
Power down and then check the fiber-
optic communication connections.
Cycle power.
Cycle power.
Cycle power. If the fault persists,
replace the DC precharge board. See
the hardware service manual,
publication 750-TG100 for PowerFlex
755T or publication 750-TG101 for
PowerFlex 755TS products, for the
replacement procedure.
Verify DC bus is present on the Mn
power module via the hardware
testpoints. If so, replace the Mn power
interface board (PIB). See hardware
service manual, publication 750-TG100
for PowerFlex 755T or publication 750-
TG101 for PowerFlex 755TS products,
for the replacement procedure.
Check the timing of the rise of the DC
bus following precharge.
Condition 1: Inspect the DC
precharge module and the thermal
sensor harness for the exit wiring
bay. Ensure MCS lockout device is
not closed. See the Service
Manual, publication 750-TG100 for
PowerFlex 755T or publication
750-TG101 for PowerFlex 755TS
products, for details.
Condition 2: Check the enclosure
filters and fans. Problems with the
baffling between these bay and
adjacent bays can be sources of
heat.
46
FAULT ACTION
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: Cannot override
this fault.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: Cannot override
this fault.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: Cannot override
this fault.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 7 'Board Faults'.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 3 'MS Pwr Flts'.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 3 'MS Pwr Flts'.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: Yes. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 3 'MS Pwr Flts'.