FRAME 9, 10 AND LARGER (19XR PRODUCT)

The 19XR units with Frame 9, 10, and larger contain:
PE-A - MOV on the AC precharge control circuit board
PE-A1 - MOV on the TVSS module
PE-A2 - Common mode capacitors on the AC common
mode filter circuit board
PE-B1 - Common mode capacitors on the line side and
motor side power interface circuit boards.
For solidly grounded equipment PE-A, PE-A1, PE-A2 are all con-
nected (in) and PE-B1 is disconnected (out). This is the default
setting for the drive. For high resistance ground system all jumpers
are disconnected (out). High resistance ground systems applica-
tions are non-standard and should be reviewed with Service Engi-
neering/Technical Service Manager and may affect warranty. See
Fig. 18-21.
Fig. 18 — 19XR, Frame 9, 10, and Larger, PE-A MOV
on AC Precharge Control Circuit Board
Fig. 19 — 19XR, Frame 9, 10, and Larger,
PE-A1 MOV on TVSS
Fig. 20 — 19XR, Frame 9, 10, and Larger, PE-A2,
Capacitors on AC Common Mode Filter Circuit Board
Fig. 21 — 19XR, Frame 9, 10, and Larger, PE-B1,
Common Mode Capacitors on Line Side and
Motor Side Power Interface Circuit Boards