Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation
Guide
First Published: 2024-03-27
Americas Headquarters
Cisco Systems, Inc.
170 West Tasman Drive
San Jose, CA 95134-1706
USA
http://www.cisco.com
Tel: 408 526-4000
800 553-NETS (6387)
Fax: 408 527-0883

Advertisement

Table of Contents
loading

Summary of Contents for Cisco Nexus 9364C-H1

  • Page 1 Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide First Published: 2024-03-27 Americas Headquarters Cisco Systems, Inc. 170 West Tasman Drive San Jose, CA 95134-1706 http://www.cisco.com Tel: 408 526-4000 800 553-NETS (6387) Fax: 408 527-0883...
  • Page 2 Any products and features described herein as in development or available at a future date remain in varying stages of development and will be offered on a when-and if-available basis. Any such product or feature roadmaps are subject to change at the sole discretion of Cisco and Cisco will have no liability for delay in the delivery or failure to deliver any products or feature roadmap items that may be set forth in this document.
  • Page 3: Table Of Contents

    Unpacking and Inspecting a New Switch Planning How to Position the Chassis in the Rack Installing the Chassis in a Four-Post Rack Installing the Switch using the NXK-ACC-KIT2-2RU Rack-Mount Kit Grounding the Chassis Starting the Switch Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 4 Transceiver and Cable Specifications Switch Power Input Requirements Power Specifications 1400-W AC Power Supply Specifications 2000-W AC Power Supply Specifications 2000-W HVAC/HVDC Power Supply Specifications 2000-W DC Power Supply Specifications Power Cable Specifications Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 5 A P P E N D I X D Additional Kits A P P E N D I X E Site Preparation and Maintenance Records Site Preparation Checklist Contact and Site Information Chassis and Module Information Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 6 Contents Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 7: Overview

    Overview, on page 1 Overview The Cisco Nexus 9364C-H1 switch (N9K-C9364C-H1) is a 2-rack unit (RU), fixed-port switch designed for Top-of-Rack deployment in data centers. This switch has the following ports: • Port 1-64 support 25G speed by using CVR-QSFP28-SFP25G, and support 10G speed by using CVR-QSFP-SFP10G •...
  • Page 8 15 minutes. • All the fan modules and power supplies must use the same airflow direction. The following figure shows the switch features on the port side of the chassis. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 9 Overview Overview Figure 2: Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 10 To determine which transceivers, adapters, and cables are supported by this switch, see the Cisco Transceiver Modules Compatibility Information document. The following figure shows the switch features on the power supply side of the chassis. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 11 Overview Overview Figure 4: Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 12 If you have only one power supply installed, you can install the replacement power supply in the open slot before removing the original power supply. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 13 If the switch has port-side exhaust airflow (blue coloring for fan modules), you must locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut down. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 14 Overview Overview Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 15: Preparing The Site

    Exhaust fans cool power supplies and system fans cool switches by drawing in air and exhausting air out through various openings in the chassis. However, fans also ingest dust and other particles, causing contaminant Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 16: Minimizing Electromagnetic And Radio Frequency Interference

    You will want to consult experts in electrical surge suppression and shielding if you had similar problems in the past. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 17: Shock And Vibration Requirements

    • Two 2000-W DC power supplies • One 2000-W HVDC power supplies Note For 1+1 redundancy, you must use two power sources and connect each power supply to a separate power source. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 18: Airflow Requirements

    You can identify the airflow direction of each fan and power supply module by its coloring as follows: • Blue coloring indicates port-side exhaust airflow. • Red coloring indicates port-side intake airflow. • Red coloring on DC power supplies indicates port-side intake airflow. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 19: Rack And Cabinet Requirements

    Statement 1048 Rack Stabilization The rack stabilizing mechanism must be in place, or the rack must be bolted to the floor before installation or servicing. Failure to stabilize the rack can cause bodily injury. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 20 Preparing the Site Rack and Cabinet Requirements Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 21: Installing The Chassis

    You can install the switch using the following rack-mount options: • Rack-mount kit (N9K-C9300-RMK) which you can order from Cisco. For four post racks. The rack or cabinet that you use must meet the requirements listed the in...
  • Page 22: Unpacking And Inspecting A New Switch

    • Two power supplies (any combination of the following with the airflow direction being the same as for the fan modules): • 1400-W AC power supply • Port-side exhaust AC power supply with blue coloring (NXA-PAC-1400W-PE) Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 23: Planning How To Position The Chassis In The Rack

    For port-side exhaust airflow, the switch must have port-side exhaust fan and AC power supply modules with one or more of the following colorings: Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 24: Installing The Chassis In A Four-Post Rack

    • The rack is installed and secured to its location. Step 1 Install the two inner rails to the sides of the chassis using flat-head screws, as shown in the following illustration: Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 25 Install the two outer rails to the front posts of the rack by aligning the rails to the post holes, as shown in the following illustration: Step 3 Fasten the two outer rails to the front posts of the rack by pushing the latch into place, as shown in the following illustration: Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 26 Installing the Switch using the NXK-ACC-KIT2-2RU Rack-Mount Kit Step 4 Install the two outer rails to the back posts of the rack by extending them into place, as shown in the following illustration: Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 27 Installing the Switch using the NXK-ACC-KIT2-2RU Rack-Mount Kit Step 5 Fasten the two outer rails to the back posts of the rack by pushing the latch into place, as shown in the following illustration: Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 28 Then secure the retainer screws on the inner rails into the rack, as shown in the following illustration: Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 29 Then slide the retainer screws out to align with the rack and then secure the thumb-screws on the inner rails into the rack, as shown in the following illustration: Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 30: Grounding The Chassis

    Any paint or other non-conductive coatings shall be removed on the surfaces between the mounting hardware and the enclosure or rack. The surfaces shall be cleaned and an antioxidant applied before installation. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 31 Secure the grounding lug to the chassis grounding pad with two M4 screws, see the previous figure. Tighten the screws to 11 to 15 in-lb (1.24 to 1.69 N·m) of torque. Step 4 Prepare the other end of the grounding wire and connect it to the facility ground. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 32: Starting The Switch

    2. Verify that the power is turned off at a circuit breaker for the power source terminals. 3. Remove the nuts from each of the terminal posts for the power supply. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 33 A setup utility automatically launches the first time that you access the switch and guides you through the basic configuration. For instructions on how to configure the switch and check module connectivity, see the appropriate Cisco Nexus 9000 Series configuration guide.
  • Page 34 Installing the Chassis Starting the Switch Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 35 Invisible laser radiation may be emitted from disconnected fibers or connectors. Do not stare into beams or view directly with optical instruments. Connecting to Host Servers To determine which transceivers and cables are supported by this switch, see http://www.cisco.com/c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 36 Warning Statement 1051 Laser Radiation Invisible laser radiation may be emitted from disconnected fibers or connectors. Do not stare into beams or view directly with optical instruments. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 37 • Inspect routinely for dust and damage. If you suspect damage, clean and then inspect fiber ends under a microscope to determine if damage has occurred. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 38 Connecting the Switch to the Network Maintaining Transceivers and Optical Cables Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 39 Remove the fan module that you need to replace as follows: a) Press the two colored sides of the fan module handle towards each other and pull the handle to slide the module out of the chassis. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 40 If you are not able to push the module all the way into the slot, carefully slide the module out of the slot Note and check its electrical connectors for damage. If damaged, contact Cisco Technical Assistance for help. If undamaged, repeat this step to reinstall the module.
  • Page 41 If the STS LED does not turn on, slide the module out of the chassis, and visually check the electrical connectors on the back side of the chassis for damage. If damaged, contact Cisco Technical Assistance for help. If undamaged, repeat the previous step to reinstall the module.
  • Page 42 If the power supply does not move out of place, it is secured in the slot. If the power supply moves, carefully press it all the way into the slot until it clicks in place. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 43 Turn on the circuit breaker for the DC power source connected to the power supply. Step 4 Verify that the power supply is operational by making sure that the power supply LED is green. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 44 Replacing Components Installing a DC Power Supply Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 45 • Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see Requirements Specific to Perforated Cabinets, on page Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 46 To help with cable management, you might want to allow additional space in the rack above and below the chassis to make it easier to route all of the fiber optic or copper cables through the rack. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 47: Environmental Specifications

    Quantity Cisco Nexus 9364C-H1 Chassis (N9K-C9364C-H1) 44 lb (20 kg) Fan Module — – Port-side exhaust (blue) (NXASFAN-160CFM-2PE) 1.3 lb (0.59 kg) – Port-side intake (red) (NXA-FAN-160CFM-2PI) 1.3 lb (0.59 kg) Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 48: Cisco Nexus 9364C-H1

    605 W 1100 W 4248.116 BTUs per hour Power Specifications Power specifications include the specifications for each type of power supply module. 1400-W AC Power Supply Specifications Property Specification Power 1400 W Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 49 Hot Swappable 2000-W HVAC/HVDC Power Supply Specifications These specifications apply to the NXA-PHV-2KW power supplies. Property Specification Power 2000 W Input Voltage 180 to 305 VAC or 192 to 400 VDC Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 50: Power Cable Specifications

    Cabinet jumper power cord, 250 VAC, 10 A, C14-C13 connectors, 2.3 feet (0.7 m) Argentina CAB-250V-10A-AR 250 V, 10 A, 8.2 feet (2.5 m) Australia CAB-9K10A-AU 250 VAC, 10 A, 3112 plug, 8.2 feet (2.5 m) Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 51 250 VAC, 10 A, BS1363 plug (13 A fuse), 8.2 (2.5 All except Argentina, Brazil, NO-POWER-CORD No power cord included with switch and Japan Power Cables for NXA-PAC-2KW Power Supplies Cable Description Illustration CAB-TA-NA North America AC Type A Power Cable Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 52 Europe AC Type A Power Cable CAB-C15-CBN Cabinet Jumper Power Cord, 250 VAC 13A, C14-C15 Connectors CAB-ACBZ-12A AC Power Cord (Brazil) 12A/125V BR-3-20 plug up to 12A CAB-TA-IN India AC Type A Power Cable Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 53 6.6-foot (2.0 m) cable with Saf-D-Grid and three terminal connectors 300V AC / 400V DC (+200/-200 V DC) NO-POWER-CORD All except Argentina, Not applicable Brazil, and Japan No power cord included with switch Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 54: Regulatory Standards Compliance Specifications

    • AS/NZS CISPR22 Class A • CISPR22 Class A • EN55022 Class A • ICES003 Class A • VCCI Class A • EN61000-3-2 • EN61000-3-3 • KN22 Class A • CNS13438 Class A Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 55 Specification Description EMC: Immunity • EN55024 • CISPR24 • EN300386 • KN 61000-4 series RoHS The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 56 System Specifications System Specifications Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 57: Appendix

    Amber Port admin state is 'Disabled, or the SFP is absent, or both. Port admin state is 'Enabled' and SFP is present, but interface is not connected. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 58 The power supply may not be properly installed in the chassis. Either all the installed power supplies are not receiving power or an uninstalled power supply is not receiving power. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 59 Power supply is installed without a connection to a power source. (10 seconds) then amber Amber Power supply failure—possibly one of the following conditions: • Over voltage • Over current • Over temperature • Power supply fan failure Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 60 LEDs LEDs Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 61 A P P E N D I X Additional Kits Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 62 Additional Kits Additional Kits Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 63 Your completion of each task ensures a successful switch installation. Planning Activity Verification Time and Date Space evaluation: Space and layout Floor covering Impact and vibration Lighting Physical access Maintenance access Environmental evaluation: Ambient temperature Humidity Altitude Atmospheric contamination Airflow Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 64 EMI evaluation: Distance limitations for signaling Site wiring RFI levels Contact and Site Information Use the following worksheet to record contact and site information for the installation. Contact person Contact phone Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 65 Use the following worksheet to record network-related information. Switch IP address Switch IP netmask Hostname Domain name IP broadcast address Gateway/router address DNS address Use the following worksheet to record information about the modules in the switch. Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...
  • Page 66 Site Preparation and Maintenance Records Chassis and Module Information Cisco Nexus 9364C-H1 NX-OS Mode Switch Hardware Installation Guide...