Table 1-5.1: Indoor and outdoor unit combination ratio limitations
Minimum
Type
combination ratio
V8 Series outdoor
units
V8i Series
outdoor units
Notes:
1.
All the indoor units connected should be indoor units with ø5mm size copper tube heater exchanger. This limitation is to avoid too big indoor unit
exchanger cause reliability and performance problem.
2.
Piping between farthest indoor unit and first indoor branch joint should less than 40m.
3.
Combination ratio greater than 130% is available as a customization option.
4.
When fresh air processing units are installed together with standard indoor units, the total capacity of the fresh air processing units must not exceed 30%
of the total capacity of the outdoor units and the total combination ratio must not exceed 100%.
Table 1-5.2: Combinations of indoor and outdoor units (V8i)