INSTALLATION MANUAL
R-410A OUTDOOR SPLIT-SYSTEM
HEAT PUMP
MODELS: 14.5 SEER - YHJF/THJF/THGF60
5 TONS - 1 PHASE
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
TXV INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Typical Installation with Required Clearances . . . . . . . . . . . . . . . . . . .2
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Outdoor Unit Control Box - 14.5 SEER 60 Only . . . . . . . . . . . . . . . . . .5
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a matching indoor coil plus 15 feet of field supplied
lines.
Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some indoor-out-
door unit combinations, elevation differences, or total line lengths. Refer
to Application Data covering "General Piping Recommendations and
Refrigerant Line Length" (Part Number 036-61920-001).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
LIST OF SECTIONS
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SYSTEM START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
LIST OF FIGURES
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CFM Selection Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Heat Pump Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
LIST OF TABLES
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer, or service agency.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier's delivery receipt. A separate request for
inspection by the carrier's agent should be made in writing. See Local
Distributor for more information.
®
835959-UIM-B-0413

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls YHJF60

  • Page 1: Table Of Contents

    INSTALLATION MANUAL R-410A OUTDOOR SPLIT-SYSTEM HEAT PUMP MODELS: 14.5 SEER - YHJF/THJF/THGF60 ® 5 TONS – 1 PHASE LIST OF SECTIONS GENERAL ..........1 SYSTEM CHARGE .
  • Page 2: Unit Installation

    AROUND PERIMETER AIR HANDLER TERMINAL BLOCK NEC CLASS 2 WIRING TO INDOOR COIL NOTE: ALL OUTDOOR WIRING CONTROL MUST BE WEATHERPROOF. ACCESS SEAL OPENING(S) WITH PANEL PERMAGUM OR EQUIVALENT FIGURE 1: Typical Installation with Required Clearances Johnson Controls Unitary Products...
  • Page 3: Tubing Hanger

    15 feet. See Application Data Serious service problems can be avoided by taking adequate precau- Part Number 036-61920-001 for installing tubing of longer lengths and tions to assure an internally clean and dry system. elevation differences. Johnson Controls Unitary Products...
  • Page 4: Txv Installations

    FIGURE 4: Heat Protection turn an additional 1/8 turn to seal. Do not overtighten fittings. Reinstall the liquid line to the top of the thermal expansion valve. Hand modify the liquid line to align with casing opening. Johnson Controls Unitary Products...
  • Page 5: Electrical Connections

    If a dehumidification control is installed, it is recommended that a mini- and within sight of the unit. mum air flow of 325 cfm/ton be supplied at all times. Remove the screws from the control box cover and remove from unit. Johnson Controls Unitary Products...
  • Page 6: Thermostat Wiring - Two-Stage Heat Pump

    159481 = 031-09157 126768 = 031-09137 heat pump control when 18395 = 031-01996 wired as shown. 340512 = 031-09178 FIGURE 6: Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Air Handler Johnson Controls Unitary Products...
  • Page 7: Thermostat Wiring - Two-Stage Heat Pump - Variable Speed Air Handler

    Part Numbers: Source is Electric SAP = Legacy SAP = Legacy 159481 = 031-09157 126768 = 031-09137 18395 = 031-01996 340512 = 031-09178 FIGURE 7: Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Air Handler Johnson Controls Unitary Products...
  • Page 8: Evacuation

    Do not leave the system open to the atmosphere. Unit damage could occur due to moisture being absorbed by the POE oil in the System will cycle with thermostat demand to provide cooling as system. This type of oil is highly susceptible to moisture absorption. needed. Johnson Controls Unitary Products...
  • Page 9: Instructing The Owner

    OF THIS UNIT. other parts in the air circuit. Clean as often as necessary to keep the unit clean. Use a brush, vacuum cleaner attachment, or other SUBCOOLING CHARGE TABLE IS ON THE UNIT RATING suitable means. PLATE. Johnson Controls Unitary Products...
  • Page 10: Wiring Diagram

    835959-UIM-B-0413 SECTION VI: WIRING DIAGRAM FIGURE 10: Wiring Diagram - Single Phase - 14.5 SEER - 5 Ton Johnson Controls Unitary Products...
  • Page 11 835959-UIM-B-0413 NOTES Johnson Controls Unitary Products...
  • Page 12: Start Up Sheet

    Venting system properly sized, within the limitations of the charts in the installation instructions. Intake Size # of 90 Degree Ells # 0f 45 Degree Ells Length Exhaust Size # of 90 Degree Ells # 0f 45 Degree Ells Length Continued on next Page Johnson Controls Unitary Products...
  • Page 13 Operate the unit through a cooling cycles, noting and correcting any problems Operate the unit through an emergency heating cycles, noting and correcting any problems Clean Up Installation debris disposed of and indoor and outdoor areas cleaned up? Continued on next Page Johnson Controls Unitary Products...
  • Page 14 Explain the importance of regular filter replacement and equipment maintenance Comments Section Subject to change without notice. Published in U.S.A. 835959-UIM-B-0413 Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: 835959-UIM-A-0112 York International Corp. 5005 York Drive Norman, OK 73069...