Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series York International Corporation, 5005 6396605-UIM-B-0724 York Drive, Norman, OK 73069 Supersedes: 6396605-UIM-A-0224 2024-07-22 Johnson Controls Ducted Systems...
Page 2
Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Completing the field control wiring connections................35 Control wiring diagrams........................... 37 Using the optional S1-2HU16700124 dehumidification control............. 40 Charging the system............................41 Measuring indoor airflow........................42 Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 4
Cooling operation..........................65 Heating operation..........................65 Emergency heat........................... 65 Pressure switch fault detection and lockout..................66 Third-party trademarks notice........................66 Wiring diagrams............................. 67 Start-up sheet..............................69 Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Certification DS Solutions App Johnson Controls believes in empowering our customers with unit-specific information at all times. Download the Ducted Systems Solutions Mobile App (DS Solutions App), which is available through the App Store for iOS and Google Play for Android. Users can use the DS Solutions App to scan the QR code located on the rating plate that is unique to each unit and provides information specific to the product.
Important indicates information that is essential to complete a task or may result in damage to the device if not followed. Note indicates something of special interest or importance. Notes can contain any type of information except safety information. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
R-454B systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-454B equipment. Service equipment must be rated for R-454B. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
If conducting any hot work on the refrigerating equipment or any associated parts, you must have appropriate fire-extinguishing equipment on hand. Have a dry powder or fire extinguisher adjacent to the charging area. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Table 3: Minimum room area System charge (lb-oz) Minimum room area Minimum total Minimum system airflow (CFM) conditioned area (ft 4-12 5-12 6-12 7-12 Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Remove refrigerant according to the Removal and evacuations section of the outdoor unit's Installation Manual. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Note: The 10-pin mitigation harness is included in the loose parts kit. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 14
NC (Normally Closed) to Test. Make sure to return the test jumper to NC once testing is complete. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 15
When the system is in standby mode, repeat the above test for a W call for heating. When testing is complete, re-install the front cover on the contol box. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Figure 4. You may not need to perform tasks indicated with a dashed outline, depending on the specific installation. Figure 4: Installation overview Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Coastal regions where the equipment is prone to atmospheric corrosion • Near hot springs where the equipment is prone to sulfide gas corrosion • In proximity to high-frequency or wireless equipment Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 18
The outdoor unit can be accessed safely when mounted, for example, for servicing. • The location of the outdoor unit allows you provide adequate support for the base pan. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Examples of leak detection methods include the bubble method and fluorescent agents. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 20
Install refrigerant pipes and components in locations where they are unlikely to be exposed to corrosive substances, unless the components are made from corrosion-resistant materials or adequately protected against corrosion. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Install the unit in as level a position as possible while maintaining the clearances shown in Figure 5 Figure Fasten the outdoor unit tightly to prevent noise. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 22
Figure 5: Typical installation clearances Figure 6: Alternative installation clearances Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Replace the refrigeration piping when replacing an R-22, R-410A, or other refrigerant unit with an R454B unit to reduce cross-contamination of oils and refrigerants. See Table Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 24
After a total of 10 h runtime where the suction-line pressure drop has not exceeded 3 psig, replace the liquid-line drier, and remove the suction-line drier. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary. If soft copper must be used, take care to avoid sharp bends which may cause a restriction. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 26
Calibration of liquid line pressure loss or gain Determination of vapor line velocity Elevation limitations TXV connections System charging Traps Crankcase heater Figure 8: Underground installation Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
You can avoid serious service problems by taking adequate precautions to ensure an internally clean and dry system. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 28
WARNING Never attempt to repair any brazed connections while the system is under pressure. Personal injury could result. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Install the TXV to the distributor assembly with the supplied fittings. Ensure that the PTFE washer is seated in the distributor. Hand tighten and turn an additional quarter turn to seal. Do not over-tighten fittings. See Figure Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 30
Install the TXV equalizer line onto the vapor line by hand tightening the 1/4 in. SAE coupling nut to the equalizer fitting, and applying an additional third turn to seal. See Figure Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 31
Insulate the bulb using thermal insulation provided to protect it from the effect of the surrounding ambient temperature. Cover completely to insulate. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Replace the service valve cap finger tight, then tighten an additional 1/12 turn (1/2 hex flat). Replace the cap to prevent leaks. See for checking and recording system charge. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Wire size must be sized per NEC requirements. • The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Do not place it on an outside wall or where it is exposed to the radiant effect from exposed glass or appliances, drafts from outside doors or supply air grilles. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 36
Figure 14: Outdoor unit control box (208/230 V single-phase 18, 24, 36, 48, and 60 models only) Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
See JHE air handler Installation Instructions for full details. For single-stage applications, JHE outdoor unit harness connections Y1 IN and Y2 IN must be bonded together as shown. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 38
*W2 input only available on two-stage gas heat models. NOTICE Fossil fuel operation must be controlled by room thermostat. NOTICE Gas furnace heat pump jumper must be set to YES. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 39
Figure 17: Standard ECM air handler and standard multi-stage heat pump - conventional wiring Figure 18: Standard ECM modular air handler and standard multi-stage heat pump - conventional wiring Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
If a dehumidification control is installed, it is recommended that a minimum air flow of 325 CFM/ton be supplied at all times. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Ensure that the refrigerating system is properly grounded before charging it with refrigerant. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Calculate the additional charge for the refrigerant piping using the Tabular Data Sheet if the line length is greater than 15 ft (4.6 m) (item 3). Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
For all other cooling charging charts and the heating charging charts, see Table Table 44. You can also access these charts in the Service Application Data section at www.simplygettingthejobdone.com. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Note: An asterisk (*) on indoor match names is used in place of the cabinet width, refrigerant type, and metering device characters. Refer to the indoor unit manuals for the details on indoor unit nomenclature. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
With the fan switch in the AUTO position, a circuit is made from the thermostat cooling contact through the blower relay to provide blower operation. The system cycles with thermostat demand to provide cooling as needed. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
The compressor body must not be heated by an open flame or other ignition sources to accelerate this process. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Table 45: A2L required procedures Procedure Safely remove refrigerant, following local and Required national codes. Purge circuit with inert gas (oxygen-free Required nitrogen). Evacuate the refrigerant. Required Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Label the equipment stating that it has been decommissioned and emptied of refrigerant. Date and sign the label. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating that the equipment contains a flammable refrigerant. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
6 h PS timer and flashes > 5 the STATUS LED six times (0.1 s ON / 0.1 s OFF) to indicate that the error memory is clear. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Page 61
Figure 19: Heat pump flow diagram Figure 20: Demand defrost control module Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
1/3 s on, 1/3 s off flashes, waits 2 s, then energizes the output for three more 1/3 s on, 1/3 s off flashes and repeats. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
This happens only if the coil sensor temperature conditions allow defrost to occur. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
When power is applied to the control and after the completion or termination of each defrost cycle, the control starts a 40 min timer. When this timer expires, the Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
Emergency heat When the thermostat calls for emergency heat operation (W signal without a Y signal), the control energizes the W out terminal immediately. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...
When the soft lockout condition is reset, the control stops displaying the fault code and responds to thermostat inputs normally. Third-party trademarks notice Third-Party Trademarks Notice: For information about third-party trademarks, refer to the relevant company websites. Installation Manual: R-454B Outdoor Split-System Single-Phase Heat Pump - YH5 and XH5 Series Johnson Controls Ducted Systems...