3.2 INSTALLATION PROCEDURE
A) Note the load tolerance of the floor
Refer to TABLE 3.2 for list of UPS weights.
TABLE 3.2 List of UPS weights
UPS Capacity (kVA)
Weight (kg.)
B) Minimum clearance required for ventilation
Front side
Right side
Left side
Back side
Top side
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
Sides
Back side
Top side
D) External Battery Supply
Please refer to the following when installing and maintaining batteries:
1.
The customer shall refer to the battery manufacturer's installation manual for
!
battery installation and maintenance instructions.
2.
The maximum permitted fault current from the remote battery supply.
NOTE
M9950 SERIES UPS
OWNERS / TECHNICAL MANUAL
60
120
610
1000 mm (39.4 inch) (for air flow)
0 mm (0 inch)
0 mm (0 inch)
0 mm (0 inch)
600 mm (23.6 inches) (for air flow)
1000 mm (39.4 inches)
0.0 mm (0 inch)
500mm (19.7 inch)
(Required for parts changes, also can be 0.0mm)
600 mm (23.6 inches)
MITSUBISHI ELECTRIC M9950 SERIES UPS
160
200
300
1050
Page Number:
3-2
400
500
600
1650