Figure 2.7-A Main Screen (En)(Battery Operation); Figure 2.7-B Main Screen (Cn)(Battery Operation); Figure 2.7-C Measurement Screen (En)(Battery Operation); Figure 2.7-D Measurement Screen (Cn)(Battery Operation) - Mitsubishi Electric M9950 Series Technical Manual

Uninterruptible power supply system 60-600kva, inclusive parallel operation system
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC
2.3.2 INPUT POWER FAILURE (FIGURE 2.7)
During an Input Power Failure, the UPS inverter will be powered by the UPS batteries.
The following will be displayed on the main and measurement screen (Indication of
battery operation and remaining battery life).
FIGURE 2.7-a Main screen(EN)
(Battery operation)
FIGURE 2.7-c Measurement screen(EN)
(Battery operation)
The LCD will display a battery low voltage message when the battery capacity is near
depletion. The End of Battery Discharge announcement is displayed when the battery
end voltage is reached. At this time, the inverter will perform an electronic shutdown to
prevent battery loss of life typical from extreme deep discharge conditions. When the
input power is restored, the inverter will automatically restart to power the load, and
the batteries will be simultaneously recharged. The End of Battery announcement is
shown at the bottom of the screen.
M9950 SERIES UPS
OWNERS / TECHNICAL MANUAL
MITSUBISHI ELECTRIC M9950 SERIES UPS
FIGURE 2.7-b Main screen(CN)
(Battery operation)
FIGURE 2.7-d Measurement screen(CN)
(Battery operation)
Page Number:
2-8

Advertisement

Table of Contents
loading

Table of Contents