Installation Procedure; Table 3.2 List Of Ups Weights (Lb.) - Mitsubishi Electric 2033G Series Owner Technical Manual

Table of Contents

Advertisement

MITSUBISHI
ELECTRIC

3.3 Installation Procedure

A) Note the load tolerance of the floor
Refer to Table 3.2 for list of UPS weights:
TABLE 3.2 List of UPS weights
UPS Capacity (kVA)
Weight (lb.)
Note: UPS have batteries external to module cabinet.
Please refer to the remote battery supply installation manual.
B) Minimum clearance required for ventilation
Right side
Left side
Back side
Top side
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
Sides
Rear
D)
External Battery Supply
Please refer to the following when installing and maintaining batteries:
1.
Refer to the External Battery Supply installation manual.
2.
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away from batteries.
3.
When installing or replacing batteries, install or replace with the same number
and type per the External Battery Supply installation manual.
2033G SERIES UPS
OWNERS / TECHNICAL MANUAL
30
50
530
665
1.0" (25 mm) (not required when sidecars are used)
1.0" (25 mm) (not required when sidecars are used)
7.8" (200 mm)
39.4" (1000 mm)
39.4" (1000 mm)
1.0" (25 mm)
7.8" (200 mm)
MITSUBISHI ELECTRIC 2033G SERIES UPS
Page Number:
3-2

Advertisement

Table of Contents
loading

Table of Contents