FIGURE 3.3 Diagram of Power Wire & Control Wire Inter-Connect between UPS and Battery
External signal
terminal
IOAU-09 - [TN1]
DC24V
Power terminal
BN
UPS module
Note1)DC24V is outputted to 72B UVT coil through a terminal box from IOAU-09 PWB.
(DC24V power supply capability: maximum current 1.25A, rated current 0.41A)
If DC24V loses, the trip state of 72B will be carried out.
Note2)Even if a 72B UVT coil carries out reset operation of the breaker from a trip state
in the state of no magnetizing, it cannot turn OFF.
Note3)When the magnetization voltage of a coil returns to 24V, it is possible to reset a breaker in the OFF state.
Note4)DC24V-16mA is impressed to 72B auxiliary contact through a terminal box from IOAU-09 PWB.
M9950 SERIES UPS
OWNERS / TECHNICAL MANUAL
User supplied
+
1
2
-
3
4
BP
MITSUBISHI ELECTRIC M9950 SERIES UPS
Page Number:
3-11
72B (DC circuit breaker)
UVT
DC24V /Reset
prevention type
Auxiliary
DC24V 16mV
"-" Negative
"+" Positive
User supplied