DIAGNOSIS AND SOLUTION (CONT)
N
00
Normal display
01
Indoor unit capacity demand code
02
Amendatory capacity demand code
03
The frequency after the capacity requirement transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341 chip
Indoor unit evaporator outlet temp.(heating T2,cooling
06
T2B)
07
Condenser pipe temp.(T3)
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(T5)
10
AD value of current
11
AD value of voltage
12
Indoor unit running mode code
13
Outdoor unit running mode code
14
EXV open angle
15
Frequency limit symbol
16
DC fan motor speed
17
IGBT radiator temp.
18
Indoor unit number
19
Evaporator pipe temp. T2 of 1# indoor unit
20
Evaporator pipe temp. T2 of 2# indoor unit
21
Evaporator pipe temp. T2 of 3# indoor unit
22
1# Indoor unit capacity demand code
23
2# Indoor unit capacity demand code
24
3# Indoor unit capacity demand code
25
Room temp. T1 of 1# indoor unit
26
Room temp. T1 of 2# indoor unit
27
Average room temp. T1
28
Reason of stop
29
Evaporator pipe temp. T2B of 1# indoor unit
Table 16—Outdoor Check Function
DISPLAY
REMARK
Display running frequency, running state or malfunction code
Actual data*HP*10
If the capacity demand code is higher than 99, the digital display tube
displays a single digit and tens digit. (For example, the digital display tube
displays "5.0",it means the capacity demand is 15. The digital display
tube show "60",it means the capacity demand is 6.0)
If the temp. is lower than 0 degree, the digital display tube displays "0". If
the temp. is higher than 70 degree, the digital display tube displays "70".
If the temp. is lower than -9 degree, the digital display tube displays
"-9".If the temp. is higher than 70 degree, the digital display tube
displays "70". If the indoor unit is not connected, the digital display tube
displays: "--"
The display value is between 13~129 degree. If the temp. is lower than
13 degree, the digital display tube displays "13". If the temp. is higher
than 99 degree, the digital display tube displays a single digit and a tens
digit. (For example, if the digital display tube displays "0.5",it means the
compressor discharge temp. is 105 degree. If the digital display tube
displays "1.6",it means the compressor discharge temp. is 116 degrees).
The display value is a hex number.
Off:0, Fan only 1,Cooling:2, Heating:3
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
Actual data/4.
If the value is higher than 99, the digital display tube displays a single digit
and a tens digit.
For example, if the digital display tube displays "2.0",it means the EXV
open angle is 120×4=480p.).
Frequency limit caused by IGBT
Bit7
radiator
Bit6
Frequency limit caused by PFC
Bit5
Frequency limit caused by T4
Bit4
Frequency limit caused by T2
Bit3
Frequency limit caused by T3
Bit2
Frequency limit caused by T5
Bit1
Frequency limit caused by current
Bit0
Frequency limit caused by voltage
The display value is between 30~120 degrees. If the temp. is lower than
30 degrees, the digital display tube displays "30".If the temp. is higher
than 99 degrees, the digital display tube displays a single digit and a tens
digit. (For example, if the digital display tube displays "0.5",it means the
IGBT radiator temp. is 105 degrees. If the digital display tube displays
"1.6", it means the IGBT radiator temp. is 116 degrees).
The indoor unit can communicate well with the outdoor unit.
General:1, Twins:2
If the temp. is lower than 0 degree, the digital display tube displays "0".If
the temp. is higher than 70 degrees, the digital display tube displays "70".
If the indoor unit is not connected, the digital display tube displays: "--".
Actual data*HP*10
If the capacity demand code is higher than 99, the digital display tube
displays a single digit and a tens digit. (For example, the digital display
tube displays "5.0",it means the capacity demand is 15. If the digital
display tube displays "60",it means the capacity demand is 6.0). If the
indoor unit is not connected, the digital display tube displays: "--".
If the temp. is lower than 0 degree, the digital display tube displays "0".If
the temp. is higher than 70 degrees, the digital display tube displays "70".
If the indoor unit is not connected, the digital display tube displays: "--".
If the temp. is lower than 0 degree, the digital display tube displays "0".If
the temp. is higher than 70 degrees, the digital display tube displays "70".
If the indoor unit is not connected, the digital display tube displays: "--".
19
The display value is a
hex number. For ex.,
the digital display tube
displays 2A, then
Bit5=1, Bit3=1, Bit1=1.
It represents the
frequency limit caused
by T4, T3 and current.