DIAGNOSTIC GUIDES
OPERATION LAMP
TIMER LAMP
☆ 1 time
☆ 2 times
☆ 4 times
☆ 5 times
☆ 6 times
☆ 7 times
☆ 8 times
☆ 1 time
☆ 2 times
☆ 3 times
☆ 4 times
☆ 5 times
☆ 6 times
☆ 7 times
☆ 8 times
☆ 9 times
☆ 10 times
☆ 1 time
☆ 2 times
☆ 3 times
☆ 4 times
☆ 5 times
☆ 6 times
☆ 7 times
☆ 8 times
Table 14—Diagnostic Guides Indoor Units
DISPLAY
X
E0
Indoor unit EEPROM parameter error
X
E1
Communication malfunction between indoor and outdoor units
X
E3
Indoor fan speed malfunction
X
E4
Indoor room temperature sensor (T1 ) malfunction
X
E5
Evaporator coil temperature sensor (T2) malfunction
X
EC
Refrigerant leakage detection
X
EE
Water-level alarm malfunction
O
F0
Current overload protection
O
F1
Outdoor ambient temperature sensor (T4 ) malfunction
O
F2
Condenser coil temperature sensor (T3) malfunction
O
F3
Compressor discharge temperature sensor (T5) malfunction
O
F4
Outdoor unit EEPROM parameter error
O
F5
Outdoor fan speed malfunction
O
F6
Indoor coil outlet pipe sensor(Located on outdoor unit low pressure valve)
O
F7
Communication malfunction between the cassette optional lift panel and the unit
O
F8
Cassette optional lift panel malfunction
O
F9
Cassette optional lift panel not closed
☆
P0
Inverter module (IPM) malfunction
☆
P1
Over-voltage or under-voltage protection
☆
P2
Compressor top high temperature protection (OLP)
☆
P3
Low ambient temperature cut off in heating
☆
P4
Compressor drive malfunction
☆
P5
Indoor units mode conflict
☆
P6
Low pressure protection
☆
P7
Outdoor IPM temperature sensor error
O(light)
LED STATUS
☆(flash)
X(off)
17