1-2. Heating operation

A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
• If the room temperature is 6.0°C lower than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
• If the room temperature is 1.0°C higher than a set temperature, the compressor will be stopped.
• →hen the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
rotation number of compressor is controlled within the range shown below.
• Rotation number range of compressor
Model name
ASEH09KHCBN
ASEH12KHCBN
ASEH14KHCBN
• Limit of maximum speed based on outdoor temperature
In heating operation, maximum rotation number is defined by outdoor temperature and fan mode.
Model name
ASEH09KHCBN
ASEH12KHCBN
ASEH14KHCBN
1-2. Heating operation
Minimum rotation number
Outdoor
temperature rises
14°C
-10°C
Outdoor
temperature
HIGH
zone
A zone
130
B zone
130
C zone
130
A zone
140
B zone
140
C zone
140
A zone
140
B zone
140
C zone
140
- (04-3) -
Maximum rotation number
8
8
Outdoor
temperature drops
C zone
12°C
B zone
-12°C
A zone
Indoor unit fan mode
MED—
MED—
MED
HIGH
LOW
111
87
111
87
120
102
111
94
111
94
120
111
111
94
111
94
120
111
Unit: rps
130
140
Unit: rps
LOW
QUIET
68
54
32
68
54
36
94
87
74
74
58
34
74
58
39
102
94
80
80
63
36
80
63
46
102
94
80
1. Rotation number control of compressor