Generator Shutdown Procedure (Single Unit) - MQ Power WHISPERWATT DCA300SSJU4F3PD Operation Manual

60 hz generator
Table of Contents

Advertisement

GENERATOR SHUTDOWN PROCEDURE ( SINGLE UNIT )
NORMAL SHUTDOWN PROCEDURE
WARNING
NEVER stop the engine suddenly except in an
emergency.
1. Place the load's ON/OFF switch in the OFF position.
2. Place the GFCI and auxiliary circuit breakers
(Figure 73) in the OFF position.
Figure 73. GFCI and Auxiliary
Circuit Breakers (OFF)
3. Press the Main Circuit Breaker OFF button
(Figure 74) on the touch display.
Figure 74. Main Circuit Breaker OFF Button
4. Verify that the Main Circuit Breaker OFF lamp
(Figure 75) is illuminated (RED). This indicates that
the circuit breaker contacts are open.
Figure 75. Main Circuit Breaker OFF Lamp
(ON/RED)
PAGE 40 — DCA300SSJU4F3PD 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/08/24)
5. Press the STOP button (Figure 76) on the touch
display. The engine will stop after a 30-second
cool-down period.
Figure 76. Stop Button
6. Place the Control Power switch (Figure 77) in the
OFF (down) position.
Figure 77. Control Power Switch (OFF)
7. Wait at least two minutes to allow the DEF system
to regenerate, then place the Battery switch (if
equipped) in the OFF position. See Figure 78.
Figure 78. Battery Switch (OFF)