Hitachi ADVANCED COLOR PC-ARFG2-E1 Installation & Operation Manual page 56

Wired remote controller
Table of Contents

Advertisement

SERVICE & INSTALLATION MENU
Element
Optional function
Not used
CC
Only for DX-Interface,
KPI-E4E and KPI-X4E:
High ventilation speed
Stop of indoor unit fan
during cooling Thermo-OFF
conditions
?
Cd
N O T E
For model RPI(L/H)-FSRE and
RCD-FSR, this function is NOT
available.
Stop of indoor unit fan
during heating Thermo-OFF
conditions (with remote
CE
control switch temperature
sensor)
Modification of louver swing
angle
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
CF
Models:
RPK-FSR(H)M
Management of indoor unit
operation after a power
d1
supply cut off - option 1
d2
Not available
Management of indoor unit
operation after a power
d3
supply cut off - option 2
44
PMML0601 rev.0 - 07/2022
Individual
Settings
setting
00
-
01
00
Function disabled (factory setting)
01
Function enabled
Fan speed during cooling Thermo-OFF:
00
Low (factory setting)
O
Indoor unit fan is stopped during cooling
01
Thermo-OFF
Fan speed setting during heating Thermo-
00
OFF: Low (factory setting)
O
Indoor unit fan is stopped during heating
Thermo-OFF
01
(In case that automatic louver is set, the lou-
vers will keep operating in both Thermo-ON
and Thermo-OFF conditions)
00
Standard (7 steps) (factory setting)
Cold draft prevention (5 steps)
(Cannot be set to the lower two steps; lower
01
2 steps cut off)
High ceilings (5 steps)
(Cannot be set the upper two steps; upper
02
2 steps cut off)
O
Standard (7 steps)
00
(5 steps for cooling / dry mode)
Cold draft prevention
(5 steps for heating and fan only)
01
(Cannot be set to the lower two steps,
lower 2 steps cut off)
02
Not used
00
Function disabled (factory setting)
O
01
Function enabled
"- -"
permanent
00
Function disabled (factory setting)
O
01
Function enabled
Setting conditions
(4)
(5)
(5)
Description
Use at 00 conditions
This function sets the unit to run
in high fan speed regardless
the setting from remote control
switch.
The operation of the indoor
unit fan is stopped in cooling
Thermo-OFF conditions when
using the additional remote
temperature sensor THM-R2AE
(connected to THM4) or the
PC-ARFG2E-(B)(1-5)
temperature sensor.
C8 must be set to 01 to use the
Cd=01 setting.
The indoor unit uses the
PC-ARFG2E-(B)(1-5)
temperature sensor to monitor
the room temperature when the
fan is stopped (heating Thermo-
OFF fan stop sequence).
C8 must be set to 01 to use the
CE=01 setting.
Control by remote temperature
sensor connected to THM4 is
not permitted (use E8 function
in that case).
This function adjusts the angle
of the air outlet louver.
(Changes to the setting of this
function are applied after turning
the power supply off and on again,
or after the automatic louver has
made a full cycle in automatic
mode).
When power supply is restored,
the indoor units controlled by
the wired remote control switch
are turned on regardless of their
ON/OFF status at the time of
the last power cut off.
When power supply is restored,
the indoor units controlled by
the wired remote control switch
are turned on automatically
ONLY if they were already ON
at the time of the last power
cut off.
If indoor units were OFF when
power was turned OFF, they
remain in OFF status when
power is restored.

Advertisement

Table of Contents
loading

Table of Contents