Technical Data; Product; Input; Output - WAGO 787-3861/800-000 Product Manual

Electronic circuit breaker
Table of Contents

Advertisement

787-3861/800-000
Button
Hold down for > 3 seconds
For more information on configuration mode, see

3.4 Technical Data

3.4.1 Product

Property
Dimensions
Width x Depth x Height from upper-edge of DIN-rail
Weight
Degree of protection

3.4.2 Input

Property
Nominal input voltage
Input voltage range
Required input voltage at which the channel is switched on
(activation threshold)
Input voltage at which the channel is tripped (trip level)
Maximum continuous current for the device
Overvoltage protection
Closed current for open-circuit operation at 24 V 
Power loss for open-circuit operation at 24 V
1)
Default setting triggered and switched off; see
Property
Control Input

3.4.3 Output

Property
Nominal output voltage
Trip current
Voltage drop between input and output
Wait time after a channel has tripped
(temperature returns to normal)
Product manual | Version: 1.0.0
Electronic Circuit Breaker
1)
1)
8 Configuration via Button [ }
Voltage Level
Value
Non-isolated 24 VDC input (relative to the device GND input)
High level
Minimum 15 VDC, maximum 30 VDC
Low level
Minimum 0 VDC, maximum 5 VDC
Description
In the event of error:
Resets channel
Requirement: The channel is switched off.
The product switches to configuration mode.
8 Configuration via Button
Table 3: Technichal Data – Product
Value
6 mm x 94 mm x 97,8 mm;
0,236 in x 3,701 in x 3,85 in
53.6 g
IP20
Table 4: Technical Data – Input
Value
24 VDC
18 ... 30 VDC
20 VDC
18 VDC (a possible undervoltage is allowed for
approx. 10 ms.)
8 A
33 V (suppressor diode at input)
< 15 mA
< 400 mW
 31].
Table 5: Technical Data – Control Input
Table 6: Technical Data – Output
Value
24 VDC
8 A
≤ 240 mV
At least 5 s (depending on the trip current)
Properties
[} 31].
13

Advertisement

Table of Contents
loading

Table of Contents