Lennox KGC Series Unit Information page 36

Table of Contents

Advertisement

TABLE 16 581131-01
KGC/KCC120S Fin/Tube - W & W/O Reheat
Outdoor
CIRCUIT 1
Coil
Discharge
Suction +
Entering
+ 10 psig
Air Temp
65°F
263
75°F
301
85°F
341
95°F
386
105°F
440
115°F
492
TABLE 17 581132-01
KGC/KCC150S Fin/Tube - W & W/O Reheat
Outdoor
CIRCUIT 1
Coil
Discharge
Suction +
Entering
+ 10 psig
Air Temp
65°F
281
75°F
320
85°F
364
95°F
407
105°F
456
115 °F
508
CIRCUIT 2
Discharge
Suction +
5 psig
+ 10 psig
5 psig
125
262
132
125
304
140
123
348
146
125
394
152
130
447
156
139
499
158
CIRCUIT 2
Discharge
Suction +
5 psig
+ 10 psig
5 psig
121
283
137
125
325
141
129
370
143
132
415
145
135
464
148
139
517
151
Charge Verification - Approach Method - AHRI Testing
(Fin/Tube Coil Continued)
1 - Using the same thermometer, compare liquid tem-
perature to outdoor ambient temperature.
Approach Temperature = Liquid temperature (at
condenser outlet) minus ambient temperature.
2 - Approach temperature should match values in
TABLE 18. An approach temperature greater than
value shown indicates an undercharge. An approach
temperature less than value shown indicates an
overcharge.
3 - The approach method is not valid for grossly over
or undercharged systems. Use TABLE 14 to TABLE
17 as a guide for typical operating pressures.
APPROACH TEMPERATURE - Fin/Tube - TXV
Unit
092S
7°F + 1 (3.9°C + 0.5)
102S
5°F + 1 (2.8°C + 0.5)
120S
3°F + 1 (1.6°C + 0.5)
150S
1°F + 1 (0.6°C + 0.5)
Page 36
TABLE 18
Liquid Temp. Minus Ambient Temp.
1st Stage
2nd Stage
9°F + 1 (5.0°C + 0.5)
15°F + 1 (8.3°C + 0.5)
2.0°F + 1 (1.1°C + 0.5)
3°F + 1 (1.6°C + 0.5)