Installation At Seaside - LG THERMA V HN0613M Installation Manual

Air-to-water heat pump
Table of Contents

Advertisement

INSTALLATION OF OUTDOOR UNIT
44

Installation at Seaside

CAUTION
!
• Unit should not be installed in areas where corrosive gases, such as acid or alkaline gas,
are produced.
• Do not install the product where it could be exposed to sea wind (salty wind) directly. It
can result corrosion on the product. Corrosion, particularly on the condenser and
evaporator fins, could cause product malfunction or inefficient performance.
• If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea
wind. Otherwise it needs additional anti-corrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
- If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should
be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind
- In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the
sea wind.
Windbreak
Sea wind
- Select a well-drained place.
Periodic (more than once/year) cleaning of the dust or salt particles stuck on the heat exchanger
by using water.
- If you can't meet above guide line in the seaside installation, please contact your supplier for the
additional anti-corrosion treatment.
Sea wind
- It should be strong enough like concrete to
prevent the sea wind from the sea.
- The height and width should be more than 150%
of the outdoor unit.
- It should be keep more than 700 mm of space
between outdoor unit and the windbreak for easy
air flow.

Advertisement

Table of Contents
loading

Table of Contents