Input Register (0x04)
Register
30001
30002
ODU operation Cycle
30003
Water inlet temp.
30004
Water outlet temp.
30005
Backup heater outlet temp.
30006
DHW tank water temp.
30007
Solar collector temp.
30008
Room air temp. (Circuit 1)
30009
Current Flow rate
30010
Flow temp. (Circuit 2)
30011
Room air temp. (Circuit 2)
30012
Energy State input
30013
Outdoor Air temp.
39998
39999
Description
Error Code
Produc Group
Product Info.
INSTALLER SETTING
Value explanation
Error Code
0 : Standby(OFF) / 1 : Cooling / 2 : Heating
[0.1 °C ×10]
[0.1 °C ×10]
[0.1 °C ×10]
[0.1 °C ×10]
[0.1 °C ×10]
[0.1 °C ×10]
[0.1 LPM ×10]
[0.1 °C ×10]
[0.1 °C ×10]
0 : Energy state 0; 1: Energy state 1....
[0.1 °C ×10]
0x8X (0x80, 0x83, 0x88, 0x89)
Split : 0 / Monobloc : 3 / High Temp. : 4 /
Medium Temp. : 5 / System Boiler : 6