7-SEGMENT indication
1
Exmaple of program code: 17 89 A3 16
2
Then tracking of FCU KIT will be on progress, and
3
After tracking is done, communicating address of FCU KIT will be indicated in order when the communication is
normal.
4
be indicated alternatively.
Check the communication cable connection between FCU KIT and FCU interface module, and reset the power of FCU
interface module.
5
FCU KIT and FCU interface module may not be installed correctly. Check the installation, and reset the power of FCU
interface module.
6
EEPROM is memory part that saves settings of the interface module.
If the error is occurred, reset the power of FCU interface module. If the error occurs continuously, the replacement of
FCU interface moudle is necessary.
7
ule.
8
Install the FCU KIT less than 16, and reset the power of FCU interface module.
9
Indoor units and FCU KITs cannot be installed together. Remove the indoor units, and reset the power of FCU interface
module.
Notes on interface module installation
1
Indoor units and FCU KITs should not be installed to the same communication line (F1, F2).
2
Interface module for an air conditioner is different, make sure AIM-N01 model is connected to an air conditioner.
3
Power of the FCU interface module should be reset after changing the installation condition of the FCU KIT.