Trane S8B1A040M3PSCA/C Installation, Operation And Maintenance Manual page 73

Upflow/downflow/horizontal gas-fired, 1–stage and 2–stage induced draft furnaces with high efficiency motor
Table of Contents

Advertisement

DEFINITION: External Gas Valve
Circuit Error (24 volts is present
when it should not be present)
S8XB-SVX001-1C-EN
7.1 Fault Code
Turn Comfort
Control to "OFF"
posi on
Is 24 VAC nominal voltage present
between Red lead at gas valve
connec on to chassis ground?
NO
Replace IFC
T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g
Correct wiring
YES
Check opera on
73

Advertisement

Table of Contents
loading

Table of Contents