GE GL317D Instruction Manual page 33

Sf6 circuit- breaker
Table of Contents

Advertisement

Operating principle, continued
Reloading the closing
spring
Diagram
11- 2016
Description and operation
Operating device of circuit- breaker
D When the motor (12) is supplied with current, it immediately starts to load
the closing spring (9) by means of the reducing gears (13) of the inertia fly-
wheel (8) and the chain (15).
D At the full stroke, the gear (19) is at the no tooth sector of the inertia flywheel
(8) and the reducing gears (13) can decelerate without causing strain on the
closing latch (14).
NOTE : During the loading of the closing spring, the supplying circuit
of the closing coil is cut to avoid an untimely closing operation.
15
12
13
GE Information
9
8
19
8
14
19
Continued on next page.